ML20155G219

From kanterella
Jump to navigation Jump to search
Forwards Addl Info Re 880128 Fire Event Involving Annuciator Cabinets.Encl Addresses Three Specific Issues Raised in .Util Concludes That Event Was Isolated Incident Caused by Random Equipment Failure
ML20155G219
Person / Time
Site: Beaver Valley
Issue date: 06/08/1988
From: Sieber J
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NUDOCS 8806170208
Download: ML20155G219 (5)


Text

_ _ - ~

g gv;ney %, sme Sewngport PA.84770)D4 M,EUlm c,.

ma ms:ss June 8, 1988 U.

S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555

Reference:

Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 Follow-up Actions on Annunciator Cabinet Fire of 1/28/88 Gentlemen:

Provided is a response to your request for additional information regarding the fire event at our BVPS Unit 2 facility involving the annunciator cabinets on January 28, 1988.

The enclosure (Attachment A) addresses each of the three (3) specific issues raised in your letter of April 18, 1988.

If there are any additional questicns or clarifications relative to this matter, please contact my office.

Very truly yours,

. D.

Sieber Vice President Nuclear Group l

Enclosure cc:

Mr. J.

Beall, Sr. Resident Inspector Mr. W. T. Russell, NRC Region I Administrator Mr. P. Tam, Project Manager h

(\\

8806170208 880608 PDR ADOCK 05000412 g

DCD

Attachment A BVPS-2 Followup Actions on Annunciator Cabinet Fire of 1/28/88 Issues and Responses ISSUE #1:

Any significant findings identified during the course of your on-going investigation of the fire.

Response

A complete description of the

event, root cause analysis and conclusions are provided below.

Description of Event:

At about 1908 hours0.0221 days <br />0.53 hours <br />0.00315 weeks <br />7.25994e-4 months <br /> on January 28, 1988 the Unit 2 control room experienced a

total loss of annunciators.

Status of the plant was Cold Shutdown Mode 5.

Approximately one-half (1/2) hour prior to the

incident, the gaseous waste system trouble alarm had flashed in and out with no message on the computer display cr the printer.

This alarm originates from MI Card

  1. 65 where the fire initiated.

Operations personnel were dispatched to the instrument rack room where they discovered a fire in logic cabinet #5.

The fire was put out with portable CO2 fire extinguishers.

At the power supply bay, Inverters

  1. 1 and
  1. 3 had tripped.

Inverter

  1. 2 was on-line and oscillating, and subsequently was turned off.

Upon a

close inspection of logic cabinet #5, it became apparent that the fire damage was limited to a specific group of P.C.

cards.

All the cards in the affected card frames were pulled'out except the most severely burned, which had to be removed with pliers.

The system was then re-energized, the cards inserted one at a time, and each alarm point verified.

A total of six (6)

MI cards were found to be damaged.

A list of all affected alarm points was compiled by computer group personnel and a temporary loJ established to monitor

]

the out-of-service alarm points.

At 2140 hours0.0248 days <br />0.594 hours <br />0.00354 weeks <br />8.1427e-4 months <br /> on January 28,

1988, approximately 95%

of the annunciator alarms had been restored.

By 2200 hours0.0255 days <br />0.611 hours <br />0.00364 weeks <br />8.371e-4 months <br /> on January 31,

1988, all repairs had been completed and the system was Zully functional.

Root Cause Analysis:

Following the incident and upon restoring the annunciator system tu normal operation, DLC undertook a

series of activities aimed at pinpointing the root cause of the incident.

The following potential causes were analyzed:

1.

Personnel Error i

2.

Procedure Deficiency 3.

Equipment Failure 4.

Programmatic Deficiency

  • A'ttachm3nt A (Cont'd)

Iss as and Rosponses Page 2 Personnel Error No testing, surveillance or maintenance activities on the annunciator system were in progress at the time of the incident.

Therefore, personnel error was not a contributing factor to this incident.

Procedure Deficiency As stated above, no procedures were being performed. when the incident occurred and therefore procedure deficiency could not have caused the incident.

Indications are that a random component Equipment Failure failure occured on Multiple-Input (MI) Card #65 causing the initial electrical fault.

A complete system check was performed and no abnormalities were observed.

The system was checked for grounds and input voltages.

The input / output of the inverters and power supplies were tested and found to be within limits.

Soon after the incident it was observed that input breakers of Inverters

  1. 1 and #3 tripped, but the power supply fuses did not blow.

Inverter

  1. 2, set at the lowest output voltage, did not trip because the fault had cleared by this time.

A review of the rating of the fuses and breakers was performed and it was determined that although the breakers have a higher continuous rating (30 Amps) than the fuses (10 kups),

the breakers are magnetic while the fuses are dual-element time-delay.

This explains why the fuses did not blow, and actual tests conducted in the shop confirmed this to be true.

Programmatic Deficiency Although there is no required periodic surveillance or preventive maintenance program for i

the annunciator

system, functional checks are performed on those alarm points associated with system that have scheduled surveillance or PM tasks.

In

addition, Maintenance Work Requests (MWR's) are generated for any suspect alarm point.

In summary, no programmatic deficiency exists

and, therefore, could not have been a contributing factor to the fire incident.

==

Conclusion:==

Based on observations and information available, we have concluded that this was an isolated incident caused by a random equipment failure.

However, due to inadequate fuse protection of the system, a resulting failure increases the potential for a fire event.

o -

Attachment A (Cont'd)

- Issues and Responses Page 3 ISSUE #2:

Corrective actions taken or planned to be taken to increase your level of confidence in the reliability of the suspect printed circuit boards and associated solid-state components.

Response

Immediate corrective actions were discussed previously regarding

repairs, system checkout and return to service of the Annunciator System.

Since the system is relatively new (less than 4 years since initial energization),

there are no plans for replacement of the equipment.

Monitoring of the subject cabinets for abnormalities or indications of overheating is being conducted once-per-shift on an interim bases until the long-term corrective actions are implemented.

Long term corrective actions include:

1.

Providing adequate fault protection by the addition of supervised fusing at a card group level which will limit the maximum fault current on a per card basis.

2.

Providing ionization-type smoke detectors inside the cabinet bays which will be interlocked with the fans and provide remote indication in the Control Room.

l Attachment A (Cont'd)

Issues and Responses Page 4 ISSUE #3:

Your conclusions pertaining to similar control systems in service at your

facility, especially those control systems that can inadvertently operate at high temperature conditions which could lead to other potential fire hazards.

Response

An evaluation was conducted pertaining to similar electronic systems in service at our facility.

The scope of the review was directed towards all high-density electronic enclosures and local annunciators supplied by Electro-Devices.

To determine if similar systems could inadvertently lead to a

potential fire hazard condition, the following characteristics were reviewed:

adequacy of local fusing existence of fire barriers between rows inside the cabinets type of power source The results of the review concluded the following:

1.

Adequate fault protection exists for all other high density electronic circuit card systems which would limit maximum fault current and prevent an ignition source and subsequent fire condition.

2.

The construction of the cabinets would mitigate the potential for spread of fire damage due to the physical barriers (i.e.,

metal plates) located between the racks within the cabinets.

3.

In all

cases, the equipment reviewed was determined acceptable and does not pose a fire hazard as experienced with the annunciator system.

._