ML20155E984

From kanterella
Jump to navigation Jump to search
Special Rept Spr 86-005:on 860321,routine Review of Meterological Data Indicated Possible Failure of 61 to 10 Meter Differential Temp (Delta T) Detection Sys.Caused by Entangled Aspirator Fan Power Supply Cord.Part 21 Related
ML20155E984
Person / Time
Site: Summer 
Issue date: 04/07/1986
From: Nauman D
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-86-133-000 PT21-86-133, PT21-86-133-000, SPR-86-005, SPR-86-5, NUDOCS 8604210073
Download: ML20155E984 (2)


Text

south c g Eiectric a c.. company gngs n

go,m, egg 29218 Nucleir Operations SCE&G April 7, 1986

,, j l,f,' 11 P U. : 45 Dr. J. Nelson Grace Regional Administrator U. S. Nuclear Regulatory Commission Region II, Suite 2900 101 Marietta Street. N.W.

i Atlanta, Georgia 30323 l

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report (SPR 86-005) i

Dear Dr.' Grace:

Attached is a Special Report for the Virgil C. Summer Nuclear Station.

This report is submitted pursuant to the requirements of Technical Specification 3.3.3.4 and 6.9.2.

I Should there be any questions, please call us at your convenience.

l l

O

\\

l ry truly yours, 1

O.

.(Nau n POL: DAN / led Attachment pc:

V. C. Summer K. E. Nodland

0. W. Olxon, Jr./T. C. Nichols, Jr.

R. A. Stough E. H. Crews, Jr.

G. O. Percival E. C. Roberts R. L. Prevatte J. G. Connelly, Jr.

J. B. Knotts, Jr.

W. A. Williams, Jr.

S. D. Hogge t

Group Managers I&E Washington

0. S. Bradham Document Management l
0. R. Moore Branch C. A. Price INPO Records Center W. T. Frady ANI Library C. L. Ligon (NSRC)

NPCF R. M. Campbell File 96o4210073 8 M 395 l

peg ADOCK PDR e

Ii 1

. FEIT

a Dr. J. Nelson Grace SPR 86-005 Page Two April 7, 1986 EVENT DESCRIPTION On March 21, 1965, routine review of meteroJogical data indicated a possible failure of the 61 to 10 meter differential temperature (AT) detection system.

Licensee investigation determined the problem was an aspirator fan power supply cord that had become entangled in the fan blade and resistance i

temperature detector system (RTO's) that had drifted outside the l

allowable limits.

CORRECTIVE ACTION The fan power cord was rerouted and tied down. The RTO calibration curves were verified to correlate to the hardware. The RTD's were reinstalled and the system calibration verified. On April 3, 1986 the meterological AT system was returned to operability l

l

!