Text
. _
MAR 2 6 1933 i
MEMORANDUM FOR:
Edward L. Jordan, Director, Division of Emergency Preparedness and Engineering Response, IE FROM:
Charles E. Norelius, Director, Division of Reactor Projects, Region III 3
SUBJECT:
POTENTIAL FAILURE OF FIRE EXTItGUISHER HOSE i
t The attached draft of a proposed NRC Information Notice is transmitted to you for your review and action.
We believe that the condition described in the attached draft is important to nuclear plant fire brigades and is generic in nature, in that the subject portable fire extinguishers are likely~to be in common use in nuclear plants nationwide.
ThNAnsulahnouncement(attached)regardedthepotentialfailureoftwohose models, the EX-607 and EX-589 for fire 1 extinguishing equipment was forwarded to us from a Region III resident inspector (Braidwood).
It is our understanding tht the EX-607 hose is manufactured by Uniroyal and the EX-589 hose by Goodyear.
Th:ese hoses are used in other portable fire extinguishers such as those manufactured by Badger Fire Equipment Company and by' General Fire Equipment Company. The attached draft Information Notice has been developed to inform licensees of this potential problem.
For further information, please' contact J. Muffett (FTS 388-5763), or J. Holmes (FTS388-5594), or J. Ulie (FTS 388-5712) of the Regior/ III staff.
i Charles E. Norelius, Director Divison of Reactor Projects Attachments:
1.
Draft of Proposed NRC Information Notice i,j) og EN, L ( b,, A enf u.gg 2.
Ansul Announcement (1
C cc w/ attachment-C. J. Paperiello, RIII 1
l W
,) JtA E?/N
^'
kIII
'RIII RIII RIII Holmes /qg Uli Muffett Schweibinz
~b 3 [ 29 %
3l% { th
}/[ S 3/2M
@/&
8603310131 860326 PDR 18E
,o f MISC.
PDR t
- J me.
_,_._m._
____,__._..___m.
DRAFT IE INFORMATION NOTICE N0.
FIRE EXTINGUISHER NOTICE:
HOSE MAY RUPTURE DURING OPERATION IN A FIRE EMERGENCY Addressees:
All nuclear power reactor. facilities holding an operating license (OL) or a construction permit (CP), research and test reactor licensees, fuel cycle
~
licensees, and material licensees.
Purpose:
This Information Notice is to alert licensees of an announcement made by Ansul Fire Equipment Company in the January 1986 Fire Journal, published by the National Fire Protection Association, regarding the potential fcilure of-EX-607 and EX-589 model hoses on Ansul fire extinguishing equipment. The EX-607 and EX-589 hoses are manufactured by Uniroyal and Goodyear, respectively.
It is expected that licensees will review the information for applicability to their facilities and consider actions, if appropriate, to preclude use of these potentially defective' fire extinguisher hoses.
It is our understanding that these hoses are used by at least two other companies, Badger and General Fire Equipment Companies. Suggestions contained in this notice do not constitute NRC requirements;.therefore, no specific action or response is required.
DRAFT Description of Circumstances:
The Ansul announcement indicated that a small number of Underwriter Laboratories listed fire extinguisher hoses, Model Number EX-607 (manufactured I
by Uniroyal), have failed. These are used on Ansul Red Line cartridge-operated hand-held portable types; wheeled extinguishers; stationary units; and hoses-l provided as replacement for Ansul Red Line equipment. Ansul emphasized that the EX-607 hose may rupture during operation rendering the unit inoperable i
and possibly causing injury to the person using the fire extinguisher.
The Ansul announcement also warned that in a few instances the hose coupling on certain model EX-589 extinguisher hoses (manufactured by Goodyear) had separated from the hose.
It is believed that this extinguisher hose type is also used with the portable hand-held cartridge-operated extinguishers, wheeled extinguishers, and stationary extinguishers. Badger and General Fire Equipment Companies also supply fire extinguishers using these type hoses.
Ansul has initiated a program (free of charge) to replace the EX-607 and EX-589 hoses. No information is available on programs that may have been
)
initiated by Badger or General Fire Equipment Companies.
No specific action or written response is required to this Infonnation Notice.
If you have any questions regarding this matter, additional information may be obtained by calling Ansul's toll-free telephone number.
\\
1-800-435-0687 between the hours of 7:30 AM and 4:30 PM.
2
DRAFT Edward L. Jordan, Director Division of Emergency Preparedness and Engineering Response Office of. Inspection and Enforcement Technical
Contact:
Jeff Holmes (312)790-5594
%.D u r o :-
QJ5se'ph Ulie (312)790-5712 James Muffett (312)790-5763
Attachment:
Ansul Announcement 3
</n peg, g!
l l
i Weintermpt this magazineto bringyou an important announcement from Ansul.
r l l{
$5. ' '
y pg >Ufa%
+
r Thisis an EX-607 extinguisher hose.
It could failin a fire emergency.
6 t
S,
n.
r c ; g.c a. ne-v y 4
,A y.
j 1m The problem.
9 The solution.
Amu Since 1977, the EX-607-a U.L. listed bose-has been When confronted with a product performance prob!em, supplied on many Ansul Red Line cartridge-operated some companies would opt to ignore the sit'J: tion..cr hand portables, wiieeled extinguishers and stationary develop a quick " band-aid" Solution.
units... and provided as replacement hoses for Ansul Red Une equipment.
That's not our style.
A very small number of these hoses have failed. We instead, we rolled up our sleeves and set about to believe the problem doesn't affect every hose. However, develop a long-term solution. Working closely with the fact remains that the EX-607 could rupture during the experts at Goodyear, we've come up with an operation... rendering the unit inoperable and possibly improved hose and hose coupling assembfy. Both causing injury to the person using the extinguisher.
have been tested extensively against exacting A related problem involves the hose couplings on a lim-ited number of Ansul Red Une Model 20 cartridge-So now we are implementing a program that will operated hand portabics. In a few instances, the hose improve the performance of your Red Une extinguishers:
couplings on certain EX-589 hoses have separated And we need your help.
from the hose.
.U1
,, m,..
n cg
-A
[c.
". y s.
Fh
- y o
i I
(
i
(
f.
1 3
We' retaking stepsto make sure that doesn't happen.
i 1
3a 1-800 435-0687 g= Ourreplacementprogram is the number to call.
won't cost you a dime, f you own any of the Ansul Red Une units shown There are no special terms, conditions or small print elow, please call our toll-free number anytime during attached to the Red Une Hose Replacement Prooram.
msul business hours (7:30 a.m. to 4:30 p.m. CST).
We have a genuine desire to replace as many of these hoses as humanly possible. So whether or not your Ve'll have friend $ knowledgeable people standing Red Une extinguishers are under warranty, call us.
/ to explain the details of the Ansul Red Une Hose Replacement Program and answer any questions We'll perform the replacement service free of charDe.
you might have.
You have our word on M..
And that's allthereis to it.
Working directly with you-or through our extensive network of Authorized Ansul Distributors--we will see to it that the Ansul extinguishers in question are located and the hose replacement performed.
~S
i RSRMtfDb81' th8 RUmh07...
n your direct Enk to people who care about the quality jM pro n
the performana of your
+.
bIfh inli%
' kr bk,w
'Nd 4
6
V,1
>A- @ 'l.
ANDUL. = =th HOSE REPLACEMENT IDENTIFICATl2N CHART Use this chart to ldenefy suspect hoses on Ansul Red Line Hand Portable Extinguishers ard any Ansul extenguishers equipped with hoses, including wheeled and stat 6onary units. (Ansul Sentry extinguishers are not included in this program.)
1.
Il extinguisher has a yellow " Inspected" sticker on the front, go to step g.
2.
Find U.L. Usting information printed on hoes (either white print or molded on hose cover). (See silustration 1 below.)
[ ens est s ecosun now ron om oom uss a usno een oes usuo to ese ** suen on aan coor exav e a ns m u.a va e usno rwa tai a ecosten e<m tw inn a
...u.
ILLUSTRATION 1 If there is no printing. or printing is unreadable, replace hose assembly and destroy old hose.
l S.
Refer to EX number on hose, if it is NOT EX-607 or EX-589, hose is good, do NOT reptsee.
4.
5.
11 EX-607 OR If EX-589
/
\\
EX 589 EX 807 8.
If EX-807, refer to date code (Example 1080 means
- 6. If unit is NOT Ansul Model 20 Hand Portable. hose assenably is good. go to step 9. (To identify unit, refer 1st Quarter 1980) to maintenance nameplate on back of extinguisher.)
7.
If Date Code is between 1077 and 4083. replace hose assembly, destroy old hose. If dated SEFORE 1077, hose as good, go to step 9.
E'.lM' ILLUSTRATION 2 7.
If it is an Ansul Model 20 Hand PortatWe with EX-589 Hose, check hex nut between hose and nozzle on hose assembly. If part number is preceded by an "H" (Example - H6305) or if hex nut is notched as in illustration 2, hose assembly is good,go to step 9.
8.
It hex nut is NOT notched or part number has NO H. (Example 6305) rep! ace hose assembly, des'roy old hose.
Perform recommended inspection and maintenance on ALL extinguishers. ' NOTE - Hoses p
i.
9.
not included in this program may need replacement due to normal wear.
When all work is completed, place yellow " inspected" sticker on extinguisher as shown in 10.
1 illustration 3.
ll.t.USTRATION 3 w on eewt sees we o os w se -usa