ML20154L670

From kanterella
Jump to navigation Jump to search
Primary Reactor Containment Integrated Leakage Rate Test Rept
ML20154L670
Person / Time
Site: Calvert Cliffs 
Issue date: 11/30/1985
From:
BECHTEL GROUP, INC.
To:
Shared Package
ML20154L668 List:
References
NUDOCS 8603120113
Download: ML20154L670 (83)


Text

-

O Baltimore Gas and Electric Company Calvert Cliffs Nuclear Power Plant Unit 2 FINAL REPORT O

November 1985 Primary Reactor Containment Integrated Leakage Rate Test Bechtel Power Corporation O

$$A*$80$RSIo"$$$2s P

PDR

m_

O BALTIMORE GAS AND ELECTRIC COMPANY CALVERT CLIFFS NUCLEAR POWER PLANT UNIT 2 i

PRIMARY REACTOR CONTAINMENT 1

INTEGRATED L2AKAGE RATE TEST REPORT i

4 I

O t

I-NOVEMBER 1985' l

l i

1 l

PREPARED BY BECHTEL POWER CORPORATION i

SAN FRANCISCO, CA 1

lO SU-089/002/1

---.y.

-,g--r--,

.., - ~,e-.

,-_n,..e,.,

,-.-.-a---

- - - -n

\\

CONTENTS SECTION Page

]

INTRODUCTION 1

a TEST SYNOPSIS 1

i TEST DATA

SUMMARY

2 ANALYSIS AND INTERPRETATION 7

REFERENCES 9

i APPENDICES A.

Description of Bechtel ILRT Computer Program B.

Stabilization Summary Data C.

ILRT Trend Report i

D.

ILRT Summary Data, Mass Point, and Total Time Reports E.

Plots: Airmass, Temperature, Pressure, Vapor Pressure, and Leakage Rate F.

Verific'ation Flow Summary and _ Data G.

ISG Calculations H.

Local Leakage Rate Test Evaluation

'1 I.

Sensor Plots

O SU-089/002/2

, - - - - - - - +,,,.

---y,_.

-c,y,

%.,_,,,c,

,.m.m.,

y,

()

. EXECUTIVE

SUMMARY

A Primary Containment Integrated Leakage Rate Test (ILRT) was successfully completed at the Calvert Clif fs Nuclear Power Plant, Unitd2, on November 24, 1985.

The test met the requirements set forth in 10CFR50, Appendix J.

Listed below is the summary of the test results for both the ' ass point m

and total' time data analysis techniques. The actual measured leakage pe@Ee)nt (L

and the 95 percenc upper confidence limit (UCL), in units of weight per day, are compared to the acceptance criteria.

Mass Point Test Result Acceptance Criteria ILRT Lam 0.052 0.150 ILRT UCL 0.060 0.150 Verification Test Lam 0.243 0.202 Lam 0.302 Total Time ILRT Lam 0.050 0.150 ILRT UCL 0.104 0.150 Verification Test Lam 0.251 0.200 Lam 0.300 r~

The total local leakage rate measured for the eight penetrations not in

(_%)

the postLOCA lineup during the ILRT was 0.001%/ day.

A chronological summary of events, summary of plant technical data, and discussion of test results are included in this report.

('D SU-089/002/3

I.

INTRODUCTION

-s This report presents data, analysis, and conclusions pertaining to the Calvert Clif fs Nuclear Power Plant, Unit 2, Integrated Leakage Rate Test (ILRT) performed in November, 1985. The Integrated Leakage Rate Test (Type A) is performed periodically to demonstrate that the combined leakage through the reactor containment and those systems penetrating the containment does not exceed the allowable leakage rate specified in the Plant Technical Specifications.

The successful periodic Type A and supplemental verification tests were performed according to the requirements of the Calvert Clif fs Nuclear Pbwer Plant, Unit 2, Technical Specifications and 10CFR50, Appendix J.

The Calvert Clif fs Type A test method is the Absolute Method described in ANSI N45.4-1972, " Leakage Rate Testing of Containment Structures for Nuclear Reactors" and ANSI /ANS 56.8-1981,

" Containment System Leakage Testing Requirements." The leakage rate was calculated using formulas f rom the above ANSI Standards and BN-TOP-1, Rev. 1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plants."

Type A and verification test durations were according to the criteria of EN-TOP-1.

A 95% upper confidence level was calculated for leakage rate data as required by Reference 6.

This is to ensure a 95% probability that the calculated leakage rate value is within the acceptance limits. All

('53 calculations were done with Bechtel's ILRT computer program described K/

in Appendix A.

The temperature and pressure history and the containment air mass variations were plotted by the computer program and are contained in Appendix E.

II.

TEST SYNOPSIS Valve line-ups were conducted on all systems to establish post-accident conditions except for shutdown cooling, demineralized water, and three penetrations necessary to conduct the ILRT. The inspection of the containment's accessible interior and exterior surf aces was conducted prior to pressurization.

No evidence of structural deterioration was noted which would have af fected containment integrity or leak tightness.

Containment pressurization commenced at 12: 25 a.m., November 23, 1985.

The containment coolers and fans were stopped at 12:00 noon. Te st prensure of 50.1 psig was reached at 1:00 p.m., November 23, 1985, and the pressurization line was vented. The temperature stabiliza-tion criteria were satisfied suring the four hours f rom 12:00 midnight to 4:00 a.m.

SU-089/003 1

9

Collection of data' to determine the integrated leakage rate commenced

( ])

- at 4:00 a.m., November 24, 1985, and was completed at 12:30 p.m.

The verification flow test was initiated at 12:30 p.m., November 24, 1985.

l The verification flow test was completed satisfactorily and depressur-ization of the containment commenced at 11:15 p.m., November 24, 1985.

i Af ter the containment was completely 'depressurized, a containment i

entry was made. Determination was made that no measurable water level changes requiring corrections to the measured leakage rate had occurred during the test. A summary of test phases follows:

Test Phase Time Duration hr.

Date i

Pre s surization 0025-1300 12.75

' November 23 Stabilization 1300-0400 15.0 November 23-24 ILRT 0400-1230 8.5 November 24 Verification Stabilization 1230-1900 6.5 November 24 Verification Test 1900-2315 4.25 November 24 During the test four temperature. sensors were malfunctioning. Temper-ature sensor 17 f ailed when pressurization began at 12:25 a.m.,

November 23. The sensor was destroyed by pressurization air flow turbule nc e.

Sensor 17 volume fraction was reassigned equally among sensors 10,15, and 16, all below elevation 45 f eet. Temperature sensors 2 and 3 decreased about 3*F at 1:00 a.m., November 24, which

, ()

was inconsistent with adjacent sensors.

Sensors 2 and 3 were declared inoperable and volume f ractions reassigned to sensors 1, 4, 7,.8, 9,

11, and 13, all in the open volume above elevation 69 feet. Temper-ature sensor 6 consistently indicated temperatures 5 to 8'F higher than adjacent sensors.

Sensor 6'was declared inoperable and its volume f raction reassigned to sensor 14, also at elevation 50 feet and outside the steam generator cavities. Dewpoint sensors 1, 2, 3, and 6 j

were not operational until 12:00 midnight November 24 The stabil-ization period was longer than the minimum-required because the dew cell power was inadvertently turned off. When the power was turned on, a dramatic jump in calculated air mass was observed, shown clearly in the airmass plot of Appendix E.

The reassigned volume fractions were used to calculate the containment dry air mass during the entire j

teat.

Plots of sensors are in Appendix I.

III. TEST DATA

SUMMARY

A.

Plant Inf o rmat ion Owner:

Baltimore Gas and Electric Company Plant:

Calvert Clif f s Nuclear Power Plant Unit 2 Location:

Lusby, Maryland Containment Type:

Post-tensioned concrete Date Test Completed:

Novembe r 24, 1985 Docket No.:

50318 S -089/003 2

i I

.-q

,g--

y

,_-i,,.%-ee-=

====c*

-===-eTv-t

- " ~ ' -: - - '

-tew--

'-"w-e

    • W-i-wr
  • 's'r-'---s' - ' " * - - * * " '

^

"'"'"m 8-

""-*** ~ '" ' *

r B.

Technical Data h's 1.

Containment Net Free Air Volume 2,000,000 cu. ft.

2.

Design Pressure 50 psig 3.

Design Temperature 276*F 4

Calculated Peak Accident 50 psig pressure Pa 5.

Containment ILRT Average 60-120*F Temperature Limits C.

Type A Test Result 1.

Test Method Absolute 2.

Leakage Rate Data Analysis Total Time per BN-TOP-1 and Techniques Mass Point per ANSI /ANS 56.8-1981 3.

Test Pressure 50.0 psig + 0.5

- 0.0 4.

Maximum Allowable Leakage Rate.

0. 2%/ day

()

La, per Technical Specification 5,

75% of La 0.15%/ day D.

Type A Test Results Integrated Leakage Rate From Regression At Upper 95%

,Line, %/ day (Lam) Confidence Limit a.

Mass Point Analysis 0.052 0.060 b'.

Total Time Analys'is 0.050 0.104 E.

Verification Test 1.

Imposed flow rate (Li) 12.34 scfm (0.2%/ day) 2.

Verification Test Results Leakage Rate, %/ day a.

Mass Point Analysis 0.243 b.

Total Time Analysis 0.251 SU-089/003 3

3.

Verification Test Limits Test Limit, %/ day a.

Mass Point Analysis (1) Upper Limit 0.302 (Li + Lam + 0.25 La)

(2) Lower Limit 0.202 (Li + Lam - 0.25 La) b.

Total Time Analysis (1) Upper Limit 0.300 (2) ' Lower Limit 0.200 F.

Repo rt Printout s The Report Printouts of the Type A and Verification Test ca'culations are provided for the Mass.oint and Total Time Analyses (Appendices C through F). Stabilization data are also provided ( Appendix B).

G.

Local Leakage Rate Test Results - Type B and C Tests 1.

LLRT Results - The Type B and C leakage tests were conducted prior to the Type A test. The total as lef t LLRT measurement

( }-

for Unit 2 was 20,594.55 sccm. This value converts to 0.012%/ day which is less than the technical specification limit of.12%/ day. An evaluation of "as lef t" compared to "as f ound" data is contained in Appendix H.

2.

During the ILRT the following penetrations were.not in the postaccident position. The following is the local leakage rate measurement for these penetrations.

Pe netration System As Lef t, SCCM 7A ILRT Instrumentation 5.3 7B ILRT Instrumentation 2.7 48 Demineralized Water 63.2 41 Shutdown Cooling Return 1716.54 50 ILRT Pressurization 239 Total:

2026.74 sccm

%/ day:

.001%/ day 3.

Periodic Type B and Type C Test Results Since Last ILRT Outage Date LLRT Acceptance Criteria July 1984 23,056.8

.6 La = 207,700 scem O

SU-089/003 4

4 ' 10CFR50, Appendix J, paragraph V.B.3, requires that leakage O

-test results f rom Type A, B, and C tests that f ailed to meet the acceptance criteria of III.A.5(b), III.B.3, and III.C.3, respectively, shall be reported in a separate accompanying summary report that includes an analysis and interpretation of the test data, the least-squares fit analysis of the test-data, the instrumentation error analysis, and the structural condition of the containment or components, if any, which contributed to the failure in meeting the acceptance c rit e ria.

Since the tests meet the acceptance criteria no further analysis is submitted.

Instruments used during local

~

leakage rate testing are calibrated as follows: + 1% full scale for flowmeters, and + 0.1% full scale for temperature and pressure gauges. Field checks of flowmeters are performed prior to each test to check calibration.

H.

Integrated Leakage Rate Measurement System The following instrument system was used:

Description Data 1.

Absolute Pressure

~

2 Precision Pressure Gauges Range:

0-100 psia Mensor Model 10100 Accuracy:

0.015% reading O

Sensitivity:

0.001 psia Repeatability:

0.001 psia Calibration Date:

11/17/85 2.

Drybulb Temperature 18 Temperature Sensors Range:

32-120*F Volumetrics 100 ohe Accuracy:

0.20*F Platinum RTD, part no.

Sensitivity:

0.01*F VSTD-347 Repeatability:

0.01*F Calibration Date:

8/30/85 3.

Dewpoint Temperature 6 Dewpoint Sensors Ra nge:

40-100*F EG&G Model 660 Chilled Accuracy:

0. 5 4
  • F Mirror Hygrometers Sensitivity:

0.1* F Repeatability:

0.1*F Calibration Date:

8/30/85 O

SU-089/003 5

9 Description Data 4

Flowmeters 2 Mass Flowmeters Range :

0-10 scfm (1) TSI Model 2013 0-20 scfm (2) Model 2014 Accuracy:

1% F.S.

Sensitivity:

1% F.S.

Repeatability:

0.1 scfm Calibration Date:

11/15/85 5.

Overall Instrumentation Selection Guide (ISG) Value (f rom ANSI /ANS 56.8-1981, Appendix G) based on ILRT instrumentation and 8.5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> minimum test duration = 0.0077%/ day.

(Calcula-tions are in Appendix C).

6.

Drybulb and Dewpoint Temperature Sensor Volume Fractions -

Ta ble 1.

I.

Information Retained at Plant The following information is available for review at the Plant:

1.

Listing of all containment penetrations, including the total number of like penetrations, penetration size and function.

(}

2.

System lineups (at time of test).

3.

A continuous sequential log of events during the test.

4 Documentation of instrumentation calibration and standards.

5.

The working copy of test procedure that would include signature sign-off of procedural steps.

6.

The procedure and all data f rom local leakage rate testing of penetrations and valves.

7.

The Quality Assurance audit plan that was used to monitor ILRT.

8.

A listing of all test exceptions including changes in containment system boundaries instituted by licensee to conclude successful testing.

9.

Description of method of leak rate verification of instrument measuring system (superimposed leakage), with calibration information on flowmeters along with calculations that were used to measure the verification leakage rate.

O SU-089/003 6

m IV.

ANALYSIS AND INTERPRETATION O

The Integrated Leakage Rate Test resialts at the upper 9'5% confidence level are 0.60%/ day (Mass Point analysis) and 0.104%/ day (Total Time analysis). The local leakage rate for penetrations not in postLOCA lineup is 0.001%/ day.

The sums of the ILRT upper 95% confidence level and LLRT leakage rates, 0.061%/ day (Mass Point analysis) and 0.105%/ day (Total Time analysis), satisfy the acceptance criterion that the. sum must be less than 0.75 La = 0.150%/ day.

Local Leakage Rate Test, repair, and adjustments of containment isolation valves were performed prior to the ILRT. The minimum pathway leakage improvement due to repairs and adjustments is 140,591.24 seem or 0.081%/ day. The as found containment leakage rat e s, the sum of the minimum pathway leakage improvement and ILRT upper 95% confidence levels, 0.185%/ day (Mass Point analysis) and 0.186%/ day (Total Time analyste), satisfy the as found acceptance

- criterion. that the sum must be less than La = 0.200%/ day.

l.N O

SU-089/003 7

TABLE 1 DRYBULB AND' DEWPOINT TEMPERATURE SENSOR LOCATIONS Volume Volume Elevation Azimuths Distance Fractions Fractions l

No.

Tag No.

(ft)

(degrees) From Center Original Reassigned 1 0-TE-5500 165 0

0

.081

.100

  • 2 0-TE-5501 147 90 33

.081

.000

'3 0-TE-5502 147 270 33

.081

.000 4 0-TE-13465 120 0

45

.072

.100 5 0-TE-5508 50 270 45

.021

.021

  • 6 0-TE-5513 50 110 45

.043

.000 7 0-TE-5514 115 0

0

.073

.100 8 0-TE-5505 125 90 40

.072

.100 9 0-TE-5506 104 180 30

.073

.100 10 0-TE-5517 30 160 45

.042

.056 11 0-TE-5507 75 210 40

.064

.0805 12 0-TE-5509 65 0

0

.042

.042 13 0-TE-5510 75 150 45

.064

.0805 14 0-TE-5512 50 210 50

.043

.086

.15 0-TE-5514 30 210 45

.042

.056 16 0-TE-5516 16 340 30

.042

.056

  • 17 0-TE-5515 20 90 30

.042

.000 0

18 o-rz-5511 so

'o

'O

.022

.022 DEWCELLS Volume Volume Elevation Azimuths Distance Fractions Fractions No.

Tag No.

(ft)

(degrees) From Center Original Reassigned 1 0-AE-5518 119 60 55

.220

'220 2 0-AE-5520 140 270 35

.220

.220 3 0-AE-5521 69 180 40

.086

.086 4 0-AE-5522 47 180 30

.086

.086 5 0-AE-5523 16 160 45

.168

.168 6 0-AE-5519 119 170 55.

.220

.'220

  • Malfunctioning sensors - not used for leakage rate' calculations.

4 0

SU-089/003 8

~

.1 1

V.

RE FERE NCES (m:

%)

1.

Calvert Clif fs, Unit 2, Plant Technical Specifications.

2.

Calvert Clif fs Procedure STP M-662-2, Integrated Leakage Rate Test, Unit 2 Containment.

3.

10CFR50, Appendix J, " Reactor Containnent Leakage Testing for Water Cooled Power Reactors."

4 ANSI N45.4-1972, " Leakage Rate Testing of Containment Structures

. for Nuclear Reactors."

5.

ANSI /ANS 56.8-1981, " Containment System Leakage Testing Re quireme nt s."

6.

Bechtel Topical Report BN-TOP-1, " Testing Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plant s.",

Rev. 1, February 1972.

l 4

O SU-089/003 9

A L-.AA.w4

-a.

-m.

A J

4-.--

.a a4-e-A m

m aLa.44ueah+#-i_.

--.--%.a__.

u,m 4

5 4-=a 5

4 1

4 APPENDIX A DESCRIPTION OF BECHTEL ILRT COMPUTER PROGRAM r

l I

i I

l

'l i

6 l

\\

l l

t i

f 6

e i

I l

l SU-089/005/1

,n-

--,nww.--ya_m-m,-

-,-------,,,w..

--. w..-.--w w

APPENDIX A DESCRIPTION OF BECHTEL ILRT COMPUTER PROGRAM A.

Program and Report Description 1.

The Bechtel ILRT computer program is used to determi.4e the inte-grated leakage rate of a nuclear primary containment structure.

The program is used to compute leakage rate based on input values of time, free air volume, containment atmosphere total pressure, drybulb temperature, and dewpoint temperature (water vapor pressure).

Leakage rate is computed using the Absolute Method as defined in ANSI /ANS 56.8-1981, " Containment System Leakage Testing Requirements" and BN-TOP-1, Rev 1, " Testing Criteria for Integrated Leakage Race Testing of Primary Containment Structures for Nuclear Power Plants".

The program is designed to allow the user to evaluate containment leakage race test results at the jobsite during containment leakage testing. Current leakage rate values may be obtained at any time during the testing period using one of two computational methods, yieldfng three different report printouts.

2.

In the first printout, the Total Time Report, leakage rate is coa-puted from initial values of free air volume, containment atmosphere fs x i

(

)

drybulb temperature and partial pressure of dry air, the latest values of the same parameters, and elapsed time.

These individually computed leakage races are statistically averaged using linear re-gression by the method of least squares.

The Total Time Method is the computational technique upon which the short duration test criteria of BN-TOP-1, Rev 1, " Testing. Criteria for Integrated Leakage Rate Testing of Primary Containment Structures for Nuclear Power Plant," are based.

3.

The second printout is the Mass Point Report and is based on the Mass Point Analysis Technique described in ANSI /ANS 56.8-L981,

" Containment System Leakage Testing Requirements." The mass of dry air in the containment is computed at each data point (ti=e) using the Equation of State, from current values of containment atmosphere drybulb temperature and partial pressure of dry air.

Contained mass is " plotted" versus time and a regression line is fit to the data using the method of least squares.

Leakage rate is determined from the statistically derived slope and intercept of the regression line.

4 The third printout, the Trend Report, is a summary of leakage rate values based on Total time and Mass Point computations presented i

as a function of number of data points and elapsed ti=e (test dura-t io n ). The Trend Report provides all leakage rate values required for comparision to the acceptance criteria of BN-TOP-1 for conduct of a short duration test.

5.

The program is written in a high level language and is designed for use on a micro-computer with direct data input from the data acquisition system.

Brief descriptions of program use, formulae A-1

g

(

used for leakage rate computations, and program logic are provided in the following paragraphs.

B.

Explanation of Program 1.

The Bechtel ILRT computer program is written, for use by experi-i enced ILRT personnel, to determine containment integrated leakage rates based on the Absolute Method described in ANSI /ANS 56.8-1981 and SN-TOP-1.

2.

Information loaded into the program prior to or at the start of the test:

a.

Number of containment atmosphere drybulb temperature sensors, dewpoint temperature (water vapor pressure) sensors and pressure gages to be used in leakage rate computations for the specific test b.

Volume f ractions assigned to each of the above sensors c.

Calibration data for above sensors d.

Test title e.

Test pressure g.

Maximum allowable leakage race at test pressure 3.

Data received from the data acquistion system during the test, and used to compute leakage rates:

a.

Time and date b.

Containment atmosphere drybulb temperatures c.

Containment atmosphere pressure (s) d.

Containment atmosphere dewpoint temperatures e.

Containment free air volume.

4.

After all data at a given time are received, a Summary of Measured Data report (refer to " Program Logic," Paragraph D, " Data" option command) is printed.

5.

If drybulb and dewpoint temperature sensors should fail during the i

test, the data from the sensor (s) are not used. The volume frac-tions for the remaining sensors are recomputed and reloaded into the program for use in ensuing Leakage rate c'omputations.

O l

A-2

l p

't i

V C.

Leakage Rate Formulae 1.

Computation using the Total Time Method:

a.

Measured leakage rate, from data:

pvt i = W RTt (1) 1 pvt i = W RTi (2) i 2400 (W1-W) i Li (3)'

=

Solving for Wt and Wt and substituting equations (1) and (2) into (3) yields:

2400 [1 - TPVtti)

L l

(4)

=

g Ati

(

IPVtti)

where, W,Wi = Weight of contained mass of dry air at times et and t

et respectively, lbs.

T,Ti = Containment atmosphere drybulb temperature at times 1

et and ti respectively, 'R.

P1, Pt = Partial pressure of the dry air component of the con-tainment atmosphere at times et and et respectively, psia.

't,Vt = Containment free air volume at times tt and et respec-tively, (constant or variable during the test), fee.

et, et = Time at 1st and ich data' points respectively, hours.

Aet = Elapsed time from et to ti, hours.

R = Specific gas constant for air = 53.35 f:.lbf/lbm.*R.

Lt = Measured leakage rate computed during time interval et to,ei, we../ day.

In order to reduce truncation error, the computer program uses the following equivalent formulation:

-2400 aWi O

Lt=

a et W1 A-3

1 5

where, Wi-W1 AWt W1 W1 APaVi ATi apt aVi t

+

+

PVti Tt Pt V1 g, a 'i It apt =Pt-Pt AVt = Vg - Vt j

ATt=Ti-Tt b.

Calculated leakage rate from regression analysis, I=a+ bat (5)

N where:

O L = Calculated leakage rate, we.%/ day, as determined from the regressian line.

a = (I Lt - bm et)/N (6)

N(IL a et) - (Et )(a et) i t

b=

(7)

A N(El et ) - (2 e )J t

N = Number of data points l

'N i

I=I l

i=1 l

l c.

Calculated leakage rate at the 95% confidence level.

L95 - a + b a tg + S_

(a)

L where:

E95 = calculated leakage rate at the 957. confidence level, we.*/ day, at l

elapsed timeaty.

O A-4 I

_ _ _ _. ~. _ -

p i

For a CN < 24 2 - AIL - BEL a c )/(N-2)l l/2 x [1, t, (3 g _g)2j (9,)

0 025;N-2 [(ILg t

S_

=t i t L

N (Qe 2 (g3 gi)2f3)j W g

where, to.025;N-2 = 1.95996 + 2.37226 + 2.82250 ;

N-2 (N-2)4 For aCN > 24 2 - aILt - BEL sti)/(N-2)]l/2 x[

,(3 g _ g) 2/

(9b) s_ = c.025;N-2 [(ILg o

i L

N (at 2 _ (g e )2f3)jl/2 t

i 1.6449(N-2)2 + 3.5283(N-2) + 0.85602 where, t0 025;N-2 =

(N-2)2 + 1.2209(N-2) - 1.5162 Ea ti O

at=

N 2.

Computation using the Mass Point Method a.

Contained mass of dry air from data:

Wg = 144 P,V, RTt (10) where:

All symbols as previously defined.

b.

Calculated leakage rate frors regression analysis W = a + b a t b

L = -2400 -

(11) a where:

L

= Calculated leakage race, we.*./ day, as determined f rom the regression line.

O i.

A-5

1 O

= (IW -bIatt)/N (12) a i

N(IWga t ) - (Wg)(Eict) t 2

N(Ia tg ) - (Iatg)Z ch atg = Total elapsed time at time of i data point, hours N = Number of data points Wg = Contained mass of dry air at ich data point, Iba, as computed from equation (10).

N I=I i=1 Inorder to reduce truncation error, the computer program uses the following equivalent formulation:

aWg b

a=

W i + (I

- I at )/N g

t W1 W1 4

~

~

aWg aWg N (I att) - I Iat t W

W 1

1 b=

W 2

N(Ia tt ).. ( g3 g )2 aWi

where, is as previously defined.

W1 c.

Calculated leakage race at the 95% confidence level.

-2400 I95 "

(D-S)

Cl')

b a

t where:

E95 - Calculated leakage rate at the 95% confidence level, we.%/ day.

i A-6

l f

O 1/2 SN 2 _ (g3 g )2) U 2 (g3)

Sb"E0 025@2 [Ntacg i

i where, t0 025;N-2. 1.6449(N-2)2 + 3.5283 (N-2)2 + 0.85602 (N-2)2 + 1.2209 (N-2) - 1.5162 f

S=<(t[Wg - (a + b a tt)]2 1/2 N-2 e

E6 W /W )2 _ [gg g fy ))2/N -

=Wg<

g g i 1 N-2 i,

t - IB W /W )(Eiti)/N]2 1/2

[ECAW/W)at t L i 1 Z

Imeg ).- (I att)Z/N O

i O

A-7 J-__

)

D.

Program Logic 1.

The Bechtel ILRT computer program logic flow is controlled by a set '

of user options.

The user options and a brief description of their associated function are presented below.

OPTION COMMAND FUNCTION Af ter starting the program execution, the user either enters the name of the file containing previously entered data or initializes a new data file.

DATA Enables user to enter raw data. When the system requests values of time, volume, temperature, pressure and vapor pressure, the user enters the appropriate-data. After completing the data entry, a summary is printed out.

The user then verifies that the data were entered correctly.

If errors are detected, the user will then be given the opportunity to correct the erro rs.

Af ter the user verifies that the data were entered correctly, a Corrected Data Summary.Repo t of time, data, average temperature, partial pressure of dry air, and water vapor pressure is printed.

()

TREND A Trend Report is printed.

TOTAL A Total Time Report is printed.

MASS A Mass Point Repo rt is printed.

TERM Enables user to sign-of f temporarily or permanently.

All data is saved on a file for restarting.

CORR Enables user to correct previously entered data.

LIST A Summary Data Report is printed.

READ Enable the computer to receive the next set of data from the data acquisition system directly.

PLOT Enables user to plot summary data, individual sensor data or air mass versus time.

DELETE Enables user to delete a data point.

INSERT Enables user to reinstate a previously deleted data point.

O VOLFRA Enable user to change volume f ractions.

A-8 1

t"~

k OPTION s

COMMAND FUNCTION TIME Enable the user to specify the time interval for a report or plot.

VERF Enable the user to input imposed leakage race and calcaluted ILRT leakage rates at start of verification test.

E.

COMPUTER REPORT AND DATA PRINTOUT MASS POINT REPORT The Mass Point Report presents leakage rate data (wt%/ day) as deter-eined by the Mass Point Method. The " Calculated Leakage Race" is the value determined from the regression analysis. The " Containment Air Mass" values are the masses of dry air in the containment (Iba).

These air masses, determined from the Equation of State, are used in the regression analysis.

TOTAL TIME REPORT f

The Total Time Report presents data leakage rate (wt%/ day) as deter-

\\

mined by the Total Time Method. The " Calculated Leakage Rate" is the value determined from the regression analysis.

The " Measured Leakage Rates" are the leakage rate values determined using Total Time calcu-lat ions. These values of leakage rate are used in the regression analysis.

TREND REPORT l

The Trend Report presents leakage rates as determined by the Mass Point and Total Time methods in percent of the initial contained mass of dry air per day (wt%/ day), versus elapsed time (hours) and number of' data points.

SUMMARY

DATA REPORT The Summary Data report presents the actual data used to calculate leakage rates by the various methods described in the " Computer Program" section of this report. The six column headings are TINE, DATE, TEMP, PRESSURE, VPRS, and VOLUME and cantain data defined as follows:

1.

TIME:

Time in 24-hour notations (hours and minutes).

2.

DATE:

Calendar date (month and day).

3.

TEMP:

Containment weighted-average drybulb temperature in absolute units, degrees Rankine (*R).

A-9

l)T 4

PRESSURE:

Partial pressure of the dry air component of the con-

\\--

tainment accosphere in absolute units (psia).

5.

VPRS:

Partial pressure of water vapor of the containment atmosphere in absolute units (psia).

6.

VOLUME:

Containment free air volume (cu. ft.).

F.

SUMMARY

OF MEASURED DATA AND

SUMMARY

OF CORRECTED DATA The Summary of Measured Data presents the individual containment atmosphere drybulb temperatures, dewpoint temperatures, absolute total pressure and free air volume measured at the time and date.

1.

TEMP 1 through TEMP N are the drybulb temperatures, where N = No. of RID's.

The values in the right-hand column are temperatures (*F), cultiplied by 100, as read from the data acquisition system (DAS).

The values in the lef:-hard column are the corrected temperatures expressed in absolute units

(*K).

2.

PRES 1 through PRES N are the total pressures, absolute, were N = No.

of pressure sensors. The right-hand value, in parentheses, is a number in counts as read from the DAS. This count value is converted

(N to a value in psia by the computer via the instrument's calibration

\\_sl table, counts versus psia.

The left-hand column is the absolute total pressure, psia.

3.

VPRS 1 through VPRS N are the dewpoint temceratures (water vapor pressures), where N = No. of dewpoint sensors.

The values in the right-hand colu=n are te=peratures (*F), multi-plied by 100 as read from the DAS.

The values in the left-hand column are the water vapor pressures (psta) from the steam tables for saturated steam corresponcing to the dewpoint

( s a tu ra t io n) temperatures in the center column.

The Sum =ary of Corrected Data presents corrected temperature and pressure values and calculated air mass determined as follows:

1.

TEMPERATURE (*R) is the volume weighted average containment atmosphere drybulb temperature derived f rom TEMP 1 through TEMP N.

2.

CORRECTED PdESSURE (psia) is the partial pressure of the dry air cocconent of the containment atmosphere, absolute.

The volume weighted average containment atmosphere water vapor pressure is subtracted from the volume weighted average total pressure, yielding the partial pressure of the dry air.

O

3.

VAPOR PRESSURE (psia) is the volume weighted average contain-ment atmosphere water vapor pressure, absolute derived f rom VPRS 1 through VPRS N.

A-10

4 VOLUME (cu. ft.) is the containment free air volume.

5.

CONTAINMENT AIR MASS (lba) is the calculated mass of dry air in the containment. The mass of dry air is calculated using the containment free air volume and the above TEMPERATURE and CORRRECTED PRESSURE of the dry air.

O f

O A-ll

O APPENDIX B STABILIZATION

SUMMARY

DATA O

O SU-089/005/2

i CALVERT CLIFFS - UNIT 2 ILRT

SUMMARY

DATA ALMAX

=

.200 VOLUME =

2000000.

VRATET =

.250 VRATEM =.252 TIME DATE TEMP PRESSURE VPRS VOLUME 1300 1123 534.062 64.5922

.3640 2000000.

1315 1123 534.094 64.5621

.'A 84 2000000.

1330 1123 534.134 64.5526

.3720 2000000.

1345 1123 534.213 64.5470

.3756 2000000.

1400 1123 534.289 64.5441

.3/96 2000000.

1415 1123 534.346 64.5453

.3833 2000000.

1430 1123 534.397 64.5522

.3848 2000000.

1445 1123 534.493 64.5603

.3855 2000000.

1500 1123 534.580 64.5679

.3863 2000000.

1515 1123 534.637 64.5766

.3870 2000000.

1530 1123 534.708 64.5837

.3878 2000000.

1545 1123 534.789 64.5910

.3884 2000000.

1600 1123 534.853 64.5973

.3890 2000000.

)

1615 1123 534.924 64.6040

.3897. 2000000.

1630 1123 534.969 64.6094

.3902 2000000.

1645 1123 535.027 64.6156

.3909 2000000.

1700 1123 535.092 64.6210

.3914 2000000.

1715 1123 535.119 64.6270

.3918 2000000.

1730 1123 535.175 64.6309

.3924 2000000.

O 1745 1123 535.192 64.6362

.3930 2000000.

1800 1123 535.255 64.6412

.3934 2000000.

1815 1123 535.294 64.6447

.3938 2000000.

1830 1123 535.323 64.6487

.3942 2000000.

1845 1123 535.391 64.6523

.3946 2000000.

1900 1123 535.400 64.6557

.3952 2000000.

1915 1123 535.434 64.6598

.3955 2000000.

1930 1123 535.486 64.6634

.3958 2000000.

1945 1123 535.524 64.6652

.3960 2000000.

2000 1123 535.551 64.6686

.3966 2000000.

2015 1123 535.554 64.6718

.3969 2000000.

2030 1123 535.599 64.6754

.3972 2000000.

2045 1123 535.628 64.67SO

.3975 2000000.

2100 1123 535.646 64.6805

.3979 2000000.

2115 1123 535.697 64.6838

.3982 2000000.

2130 1123 535.738 64.6879

.3985 2000000.

2145 1123 535.758 64.6919

.3989 2000000.

i

{

2200 1123 535.780 64.6945

.3993 2000000.

1 2215 1123 535.428 64.6986

.3996 2000000.

2230 1123 535.875 64.7027

.3999 2000000.

2245 1123 535.900 64.7057

.4003 2000000.

2300 1123 535.934 64.7103

.4007 2000000.

7 2315 1123 535.962 64.7144

.4010 2000000.

2330 1123 536.024 64.7178

.4015 2000000.

1 2345 1123 536.035 64.7219

.4019 2000000.

I 1

l

--,__-,-_,n__--._

CALVERT CLIFFS - UNIT 2 ILRT

SUMMARY

DATA

.200 VOLUME =

2000000.

ALMAX

=

VRATET =

.250 VRATEM =.252 TIME DATE TEMP PRESSURE VPRS VOLUME 0 1124 536.105 64.8591

.2726 2000000.

15 1124 536.264 64.8768

.2726 2000000.

30 1124 536.437 64.8944

.2723 2000000.

45 1124 536.525' 64.9060

.2725 2000000.

100 1124 536.640 64.9163

.2725 2000000.

115 1124 536.698 64.9250

.2723 2000000.

130 1124 536.758 64.9340

.2726 2000000.

145 1124 536.838 64.9414

.2726 2000000.

200 1124 536.878 64.9480

.2729 2000000.

215 1124 536.946 64.9538

.2730 2000000.

230 1124 536.993 64.9607

.2730 2000000.

245 1124 537.029 64.9653

.2733 2000000.

300 1124 537.079 64.9728

.2733 2000000.

315 1124 537.132 64.9780

.2735 2000000.

330 1124 537.189 64.9833

.2736 2000000.

345 1124 537.215 64.9870

.2738 2000000.

400 1124 537.259 64.9913

.2740 2000000.

O 1

O

CALVERT CLIFFS - UNIT 2 ILRT TEMPERATURS STABILIZATION FROM A STARTING TIME AND DATE OF:

0 1124 1985 TIME TEMP ANSI BN-TOP-1 (HOURS)

C'R)

AVE A T AVE A T DIFF AVE A T (4 HRS)

(1HR)

(2 HRS)

.00 536.10

.25 536.26

.50 536.44

.75 536.52 1.00 536.64 1.25 536.70 1.50 536.76 1.75 536.84 2.00 536.98

.387*

2.25 536.95

.341*

2.50 536.99

.278*

2.75 537.03

.252*

3.00 537.08

.220*

3.25 537.13

.217*

3.50 537.19

.215*

3.75 537.21

.189=

4.00 537.26

.268

.179

.11e

.095*

)

  • INDICATES TEMPERATURE STABILIZATION HAS BEEN SATISFIED 1

1 O

a e-

+ =

-.wa 4 M

...----_m 4

i l

APPENDIX C ILRT TREND REPORT f

1 A

r I

l 4

i e

l SU-089/005/3 4

CALVERT CLIFFS - UNIT 2 ILRT TREND REPORT TIME AND DATE AT START OF TEST:

400 1124 1985 No.

END TOTAL TIME ANALYSIS NASS POINT ANALYSIS PTS TIME NEAS. CALCULATED UCL CALCULATED UCL 4

445

.011

.025

.869

.011

.165 5

500

.056

.050

.362

.045

.130 6

515

.019

.038

.246

.030

.084 7

530

.076

.061

.222

.060

.110 8

545

.015

.032

.191

.021

.077 9

600

.005

.022

.161

.011

.055 10 615

.021

.006

.133

.007

.032 11 630

.014

.007

.122

.002

.030 12 645

.001

.003

.109

.004

.023 13 700

.002

.001

.099

.004

.018 14 715

.016

.003

.095

.001

.020 15 730

.003

.000

.087

.002

.015 16 745

.035

.007

.092

.008

.027 17 800

.007

.006

.087

.007

.024 18 815

.033

.011

.090

.014

.030 19 830

.032

.015

.091

.019

.034 20 845

.057

.023

.099

.030

.047 21 900

.045

.027

.102

.035

.051 22 915

.025

.028

.099

.034

.049 0

23 930

.028

.028

.098

.034

.047 24 945

.048

.032

.100

.038

.051 25 1000

.051

.036

.102

.042

.055 26 1015

.057

.040

.105

.047

.060 27 1030

.029

.039

.103

.045

.057 28 1045

.051

.042

.104

.048

.059 29 1100

.041

.043

.104

.048

.058 30 1115

.040

.044

.103

.048

.058 j

31 1130

.040

.044

.103

.048

.057 32 1145

.040

.045

.102

.048

.056 33 1200

.060

.048

.104

.051

.060 34 1215

.051

.049

.104

.052

.061 35 1230

.045

.050

.104

.052

.060 I

1

O APPENDIX D ILRT

SUMMARY

DATA, MASS POINT, AND TOTAL TIME REPORTS O

O SU-009/005/4

CALVERT CLIFFS - UNIT 2 ILRT O

SUMMARY

DATA j

ALMAX

=

.200 VOLUME =

2000000.

VRATET =

.250 VRATEM =.252 TIME DATE TEMP PRESSURE VPRS VOLUME 400 1124 537.259 64.9913

.2740 2000000.

415 1124 537.302 64.9967

.2740 2000000.

430 1124 537.357 65.0020

.2741 2000000.

445 1124 537.379 65.0061

.2745 2000000.

500 1124 537.439 65.0116

.2744 2000000.

515 1124 537.464 65.0155

.2745 2000000.

530 1124 537.511 65.0188

.2746 2000000.

545 1124 537.511 65.0225

.2749 2000000.

600 1124 537.543 65.0254

.2749 2000000.

615 1124 537.556 65.0285

.2752 2000000.

630 1124 537.589 65.0303

.2754 2000000.

645 1124 537.601 65.0326

.2756 2000000.

700 1124 537.630 65.0361

.2755 2000000.

715 1124 537.656 65.0380

.2756 2000000.

730 1124 537.663 65.0405

.2756 2000000.

745 1124 537.706 65.0419

.2757 2000000.

800 1124 537.704 65.0443

.2757 2000000.

815 1124 537.745 65.0464

.2760 2000000.

830 1124 537.762 65.0483

.2761 2000000.

O 845 1124 537.802 65.0497

.2762 2000000.

900 1124 537.814 65.0524

.2764 2000000.

915 1124 537.810 65.0545

.2763 2000000.

930 1124 537.825 65.0556

.2767 2000000.

945 1124 537.870 65.0578

.2770 2000000.

1000 1124 537.898 65.0603

.2769 2000000.

1015 1124 537.924 65.0621

.2771 2000000.

1030 1124 537.902 65.0641

.2771 2000000.

i 1045 1124 537.940 65.0644

.2773 2000000.

l 1100 1124 537.940 65.0659

.2773 2000000.

1115 1124 537.957 65.0679

.2777 2000000.

1130 1124.

537.974 65.0696

.2775 2000000.

1145 1124 537.991 65.0715

.2776 2000000.

1200 1124 538.035 65.0721

.2780 2000000.

1215 1124 538.030 60.0732

.2779 2000000.

1230 1124 538.028 65.0740

.2780 2000000.

O

CALVERT CLIFFS - UNIT 2 ILRT LEAMAGE RATE (WEIGHT PERCENT / DAY)

()

MASS POINT ANALYSIS i

TIME AND DATE AT START OF TEST:

400 1124 1985 TEST DURATION:

8.50 HOURS I

TIME TEMP PRESSURE CTNT. AIR NASS LOSS AVERAGE MASS (R)

(PSIA)

NASS (LRN)

(LBN)

LOSS (LBM/HR) 400,537.259 64.9913 653026.

415 537.302 64.9967 653028.

-2.2

-S.S 430 537.357 65.0020 653014.

13.8 23.1 445 537.379 65.0061 653028.

-13.8

-2.9 500 537.439 65.0116 653010.

17.5 15.3 515 537.464 65.0155 653019.

-9.0 5.1 530 537.511 65.0184 652995.

24.6 20.6 545 537.511 65.0225 653033.

-37.9

-4.0 600 537.543 65.0254 653023.

9.7 1.4-615 537.556 65.0245 653039.

-15.5

-5.7 630 537.589 65.0303 653016.

22.3 3.4 645 537.601 65.0326 653025.

-S.4

.4 700 537.630 65.0361 653025.

.2

.4 715 537.656 65.0340 653012.

12.7 4.3 730 537.663 65.0405 653028.

-16.4

.7 745 537.706 65.0419 652990.

34.3 9.6 800 537.704 65.0443 653018.

-27.4 2.0 0

815 537.745 65.0464 652944.

29.5 8.8 830 537.762 65.04S3 652987.

1.2 S.6 845 537.802 65.0497 652952.

35.1 15.6 i

900 537.814 65.0524 652965.

-12.8 12.2 I

915 537.410 65.0545 652990.

-25.6 6.8 930 537.825 65.0556 652944.

6.1 7.6 945 537.870 65.0578 652951.

33.6 13.1 1000 537.898 65.0603 652943.

7.7 13.8 1015 537.924 65.0621 652929.

14.0 15.5 l

1030 537.902 65.0641 652975.

-46.4 7.8 l

1045 537.940 65.0644 652933.

42.7 13.8 1100 537.940 65.0659 652944.

-15.1 11.1 1115 537.957 65.0679 652947.

.5 10.8 i

1130 537.974 65.0696 652944.

3.5 10.9 i

1145 537.991 65.0715 652942.

1.4 10.8 l

1200 538.035 65.0721 652495.

47.0 16.4 1215 534.030 65.0732 652911.

-16.2 13.9 l

1230 534.028 65.0740 652922.

-10.6 12.2 FREE AIR VOLUME USED (CU. FT.)

=2000000.

REGRESSION LINE i

INTERCEPT (LBM)

= 653044.

j SLOPE (LBM/NR)

=

-14.3

=

.200 i

NAXIMUN ALLOWASLE LEAKAGE RATE 1

752 0F MAXIMUM ALLOWABLE LEAKAGE RATE

=

.150

=

.060 THE UPPER 954 00NFIDEMCE LIMIT

.052 THE cal.CULATED LEAKAGE RATE

=

I,

CALVERT CLIFFS - UNIT 2 ILRT O

LEAKAGE RATE (WEIGHT PERCENT / DAY)

TOTAL TIME ANALYSIS TIME AND DATE AT START OF TEST:

400 1124 1985 TEST DURATION:

8.50 HOURS TIME TEMP PRESSURE MEASURED (R)

(PSIA)

LEAKAGE Rt.TE 400 537.259 64.9913 415 537.302 64.9967

.032 430 537.357 65.0020

.085 445 537.379 65.0061

.011 500 537.439 65.0116

.056 515 537.464 65.0155

.019 530 537.511 65.0188

.076.

545 537.511 65.0225

.015 600 537.543 65.0254

.005 615 537.556 65.0285

.021 630 537.589 65.0303

.014 645 537.601 65.0326

.001 700 537.630 65.0361

.002 715 537.656 65.0340

.016 730 537.663 65.0405

.003 745 537.706 65.0419

.035 800 537.704 65.0443

.007 O

415 537.745 65.0464

.033 430 537.762 65.0483

.032 445 537.402 65.0497

.057 900 537.814 65.0524

.045 915 537.410 65.0545

.025 930 537.825 65.0556

.028 945 537.870 65.0578

.044 1000 537.898 65.0603

.051 1015 537.924 65.0621

.057 1030 537.902 65.0641

.029 1045 537.940 65.0644

.051 1100 537.940 65.0659

.041 l

1115 537.957 65.0679

.040 1130 537.974 65.0696

.040 1145 537.991 65.0715

.040 1200 534.035 65.0721

.060 1215 534.030 65.0732

.051 1230 538.028 65.0740

.045

=

.030 MEAN OF THE MEASURED LEAKAGE RATES

=

.200 MAXIMUM ALLOWABLE LEAMAGE RATE

.150 75k OF MAXIMUM ALLOWABLE LEAKAGE RATE

=

.104 THE UPPER 95m CONFIDENCE LIMIT

=

.050 THE CALCULATED LEAKAGE RATE

=

k i

I P

t t

i Ji f

i

.I f

APPENDIX E i

PLOTS: AIRMASS, TEMPERATURE, PRESSURE, l

i VAPOR PRESSURE, AND LEAKAGE RATE I

i I

1 i

)

i i.

i 4

l i

i 1

i o

?

r f

l I

1 e

i Y

h I

)

I I

r i

1 l

.i I

t I

i su-089/cos/5 l

l i

j i

i

^-

^

AIRMASS LBM X 1000

)

653.10 g3.s., "#^ %g.,,

I LRT-+ 'b.

652.83 t

-.\\^

1

+ST ABILIZAT ION +

. if.,

l 652.56" s

V,.

4

'v's 652.29" UERIFICATION <

r i

h ER 652.02" URE SENSORS

........' h... OPERATIONAL

~

65.1. 75

.300 1123 TIME H0llRS 2315 1124 i

START TIME DATE END TIME DATE

LUERT CLIFFS UNb 2 ILRT O

AIRMASS LBM X 1999 653.29 STABILIZATION

\\ ^^4 i

vb v.g,.% 3 V

653.00 Nq

, g__(

ILRT A

.4 652.80 vg 0.2X/ DAY FLOW

's.

IMPOSED

'./

\\..A, l

652.60

(,,,

s \\.,_

UERIFICATION

'+

652.40

\\g i

1 i,

652.29 0 1124 TIME HOURS 2315 1124 START TIME DATE END TIME DATE l

l

LUERT CLIFFS UN 2 ILRT TEMPERATURE DEGREES F

79.800 l

..s

/-'.r'~~

78.000" r-

/

77.000" j'

_, e s.

76.000" f

/

75.000" /

/

6-74.000

.300 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE

\\

l

LUERT CLIFFS UNb 2

ILRT PRESSURE PSIA (DRV AIR) 65.100

/

64.980

/

/

64.860 i

64.740" l

/

64.620"

/

/

L.,/

64.500

.31313 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE I

C LUl?RT CLIFFS UNb 2 ILRT UAPOR PRESSURE PSIA

.429

.399" <

~ ~

.,1

.369

.330" I

i

.399" l

.279

..........c.,-c

.300 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE

CkUERTCLIFFS-UNIk2ILRT AIRMASS LBM X 1990 AND REGRESSION LINE l

DX5 _.

' '\\v

-A g

f p

r3 652.98

'N,

\\,s b,

j

's/ \\/%

N j

s._

652.91

'\\

\\'/'

~,

/

ss i

O. 7 5 La _ '~s._

l 652.84 N s,

..s.,~,

652.77

'\\,.

w.

652.70 i

400 1124 TIME HOURS 1230 1124

)

START TIME DATE END TIME DATE i

t J

C UERT CLIFFS UNI 2

ILRT l

MASS POINT LEAMAGE RATE AND UCL X/ DAY 1

.200 l

1

\\

.150 O.75 La l

\\

\\s(/t

.100

\\.

95X UCL

.\\

l

. f'gg \\,

\\_

~

~

~

_,{~

.050

].

j l

~

- ~- /, -/ 'i-l

/

s s-

\\

RATE 1

, ggg-u-

.050 400 1124 TIME HOURS 1230 1124 i

START TIME DATE END TIME DATE i

$LUERT CLIFFS UNb 2

ILRT l

TOTAL TIME LEAEAGE RATE AND UCL X/ DAY l

.259 s

\\

\\

.200

\\

\\\\

~

'n i

.159

\\,

0. 75 La l

N.

95x UCL

~

.199 RATE

\\

.959

\\.

f N.

c-t

.999 l

i 400 1124 TIME HOURS 1230 1124 START TIME DATE END TIME DATE I.

$LUERT CLIFFS UNb 2

ILRT AIRMASS LBM X 1999 AND REGRESSION LINE UERIFICATION TEST 652.59 1

)

. -h

.-'. y 1

%')

~ ~ ~,

652.52

%'%._,, ^ ? ~~__

~

LOWER LIMIT

~

i

\\;.

652.45 s.,

'qs.

t

,[

-'s.

\\,,. ^ s.

~

s.

~

652.38"

.s,_

UPPER LIMIT

' -I.

N, i

w\\

i j

652.31

\\

s, 652.24

_900 1124 TIME HOU g g M

START TIME DATE 1

l L

CkUERT CLIFFS UNIk 2 ILRT MASS POINT LEAMAGE RATE X/ DAY UERIFICATION TEST

.500 l

.400

,.e'yPPERLIMIT

.300'

/

N._

~

I

  • ~

t RATt.%_

, ~ -

/

l

.200' LOWER LIMIT

.100" i

)

i

.000

.900 1124 TIME H011RS 2315 1124 START TIME DATE END TIME DATE

LUERT CLIFFS

- llNb 2

ILRT TOTAL TIME LEAMAGE RATE X/ DAY i

UERIFICATION TEST

.500

.400

y. llPPER LIMIT

.300

~_.

/'

s

/

RATE

~~~-

l

.200

/

LOWER LIMIT i

1

.100" t

.000

.900 1124 TIME HOLIRS 2315 1124 START TIME DATE END TIME DATE

m

-- +,._

a w-.

m-a a

-o-+

e 4

i

+

i l

APPENDIX F 1

e VERIFICATION FLOW

SUMMARY

AND DATA l

i i

l i

SU-089/005/6 I

,,.,,-c-.-

-,,-.nn-g.-

---n.

CALVERT CLIFFS - UNIT 2 ILRT O

LEAKAGE RATE (WEIGHT PERCENT / DAY)

MASS POINT ANALYSIS TIME AND DATE AT START OF TEST: 1900 1124 1985 TEST DURATION:

4.25 HOURS TIME TEMP PRESSURE CTMT. AIR MASS LOSS AVERAGE MASS (R)

(PSIA)

MASS (LBM)

(LBM)

LOSS (LBM/HR) 1900 538.261 65.0691 652590.

1915 538.262 65.0678 652575.

15.1 60.4 1930 538.254 65.0673 652581.

-5.5 19.3 1945 538.282 65.0672 652545.

35.3 59.8 2000 538.304 65.0653 652500.

45.3 90.2 2015 538.309 65.0654 652494.

6.0 76.9 2030 538.334 65.0649 652455.

39.2 90.3 2045 538.305 65.0643 652488.

-33.3 58.3 2100 538.316 65.0632 652464.

23.8 62.9 2115 538.304 65.0617 652464.

.3 56.1 2130 538.311 65.0615 652454.

10.1 54.5 2145 538.339 65.0613 652418.

36.2 62.7 2200 538.389 65.0614 652357.

60.7 77.7 l

2215 538.351 65.0608 652398.

-41.2 59.1 2230 534.376 65.0602 652361.

36.7 65.3 2245 538.377 65.0601 652359.

2.1 61.6 O

2300 538.395 65.0601 652337.

22.0 63.2 2315 538.442 65.0594 652274.

63.9 74.5 FREE AIR VOLUME USED (CU. FT.)

=2000000.

REGRESSION LINE IMTERCEPT (LBM)

= 652591.

-66.1 SLOPE (LRN/HR)

=

s VERIFICATION TEST LEAKAGE RATE UPPER LIMIT =

.302 VERIFICATION TEST LEAKAGE RATE LOWER LIMIT =

.202

.243 THE CALCULATED LEAKAGE RATE

=

l O

CALVERT CLIFFS - UNIT 2 ILRT

~

LEAKAGE RATE (WEIGHT PERCENT / DAY)

(_}s TOTAL TIME ANALYSIS TIME AND DATE AT START OF TEST: 1900 1124 1985 TEST DURATION:

4.25 HOURS TIME TEMP PRESSURE MEASURED (R)

(PSIA)

LEAKAGE RATE 1900 538.261 65.0691 1915 538.262 65.0678

.222 1930 538.254 65.0673

.071 1945 538.282 65.0672

.220 2000 538.304 65.0653

.332 2015 538.309 65.0654

.283 2030 538.338 65.0649

.332 2045 538.305 65.0643

.215 2100 538.316 65.0632

.232 2115 538.304 65.0617

.206 2130 538.311 65.0615

.200 2145 538.339 65.0613

.231 2200 538.389 65.0614

.286 2215 538.351 65.0608

.217 2230 538.376 65.0602

.240 2245 538.377 65.0601

.226 O

2300 538.395 65.0601

.232 2315 538.442 65.0594

.274

=

236 MEAN OF THE MEASURED LEAKAGE RATES VERIFICATION TEST LEAKAGE RATE UPPER LIMIT =

300 VERIFICATION TEST LEAKAGE RATE LOWER LIMIT =

200 251 THE CALCULATED 1.EAKAGE RATE

=

e 4m..

g

-,,y, y

p-.--..__.-,9.

.,-_p,.,39,m,-_,_,.9,,

,, ~

,,,-,,m-,,_.,,,7

,_..,,yy

,,--_,9

,~_,-.--_y----

CALVERT CLIFFS - UNIT 2 ILRT O

SUMMARY

DATA

.200 VOLUME =

2000000.

ALMAX

=

VRATET =

.250 VRATEM =.252 TIME DATE TEMP PRESSURE VPRS VOLUME 1230 1124 538.028 65.0740

.2740 2000000.

1245 1124 538.031 65.0749

.2781 2000000.

1300 1124 538.050 65.0748

.2742 2000000.

1315 1124 534.081 65.0745

.2785 2000000.

1330 1124 538.077 65.0746

.2784 2000000.

1345 1124-534.100 65.0743

.2784 2000000.

1400 1124 538.110 65.0745

.2785 2000000.

1415 1124 538.097 65.0742

.2788 2000000.

1430 1124 538.134 65.0741

.2789 2000000.

1445 1124 534.145 65.0741

.2789 2000000.

1500 1124 538.122 65.0739

.2791 2000000.

I 1515 1124 534.149 65.0741

.2790 2000000.

1530 1124 538.166 65.0738

.2792 2000000.

1545 1124 538.142 65.0736

.2794 2000000.

1600 1124 538.213 65.0736

.2795 2000000.

1615 1124 534.216 65.0734

. 27M 2000000.

1630 1124 538.236 65.0723

.2797 2000000.

1645 1124 538.215 65.0720

.2796 2000000.

1700 1124 538.199 65.0717

.2799 2000000.

1715 1124 534.228 65.0717

.2794 2000000.

1730 1124 538.246 65.0711

.2000 2000000.

1745 1124 534.242 65.0709

.2402 2000000.

1800 1124 534.227 65.0709

.2802 2000000.

i 1815 1124 538.254 65.0702

.2803 2000000.

1830 1124 538.290 65.0697

.2804 2000000.

1845 1124 538.292 65.0692

.2804 2000000.

1900 1124 538.261 65.0691

.2405 2000000.

1915 1124 534.262 65.0678

.280s 2000000.

1930 1124 538.254 65.0673

.2004 2000000.

1945 1124 538.282 65.0672

.2809 2000000.

2000 1124 538.304 65.0653

.2813 2000000.

2015 1124 534.309 65.0654

.2812 2000000.

2030 1124 534.334 65.0649

.2812 2000000.

2045 1124 534.305 65.0643

.2813 2000000.

2100 1124 534.316 65.0632

.2815 2000000.

2115 1124 538.304 65.0617

.2814 2000000.

2130 1124 538.311 65.0615

.2816 2000000.

2145 1124 534.339 65.0613

.2318 2000000.

2200 1124 538.349 65.0614

.2818 2000000.

2215 1124 534.351 65.0604

.2818 2000000.

2230 1124 534.376 65.0602

.2819 2000000.

I 2245 1124 534.377 65.0601

.2820 2000000.

2300 1124 538.395 65.0601

.2821 2000000.

2315 1124 534.442 65.0594

.2823 2000000.

O I

l l

t I

a l

edh_.-

+, - * -*

'--e-

==.-'*-eAh--mm-M,-,Awwwp A--

c.wp a.m

%s

-w..

4

..u-h w.a.._.-_m_

a e

  • --a m.

4_adh--h----J A-h-62,l-s.-4C-h~*-+

e-

-m

=x t

l I

J i

s l

i l

b 4

I 4

I 4

h APPENDIX G ISG CALCULATIONS l

i 1

i

?

I l

l 1

l

~

l I

{

?

I I

l t

l I

l

}

1 i

i i

l l

r l

1 i

[

i 1

4 t

r i

\\

i I

4 I

k l

I i

i l

I l

i 4

5, l

a s

1 1

i i

l SU-089/005/7 I

f i

I 1

t 4

l Os ISC CALCULATION

( ANSI /ANS 56.8 - 1981 )

CALIBRATION DATA

  1. OF SENSORS SENSITIVITY (E)

REPEATABILITY (r)

TEMPERATURE (T) 14 0.0100 deg. F 0.0100 deg. F PR, ESSURE (P) 2 0.0010 paia 0.0010 paia VAPOR PRESS (Pv) 6 0.1000 deg. F 0.1000 deg. F Length of Teat (t) 8.5 hra 1

Test Pressure (P) 50.5 peig

==>

65.5 pela From Steam Table 0.0108 pei/deg. F (at 65 deg. F)

Le 0.2000 wt*/ day

(

INSTRUNENT NEASUREMENT ERRORS 2

2 1/2 1/2 e7

((ET)

+ (rT) 3

/t# of sensore3 e7 0.0038 deg. F 2

2 1/2 1/2 eP = (CEP)

+ (rP) 3

/C# of sensore3 eP.

0.0010 paia 2

2 1/2 1/2 ePv. [(EPv)

+ (rPv) 3

/t# of sensoral i

0.0006 paia ePv.

INSTRUNENT SELECTION GUIDE 2

2 2

1/2 ISG 2400/tt 2(eP/P)

+ 2(ePv/P)

+ 2(eT/T) 3 ISG =

0.0077 wtN/ day 254 of Le 0.0500 wtw/ day G-1

i l

I b

i r

APPENDIX H LOCAL LEAKAGE RATE TEST EVALUATION l

1 l

I 1

l l

i f

I i

k 4

J 4

1 f

f I

i i

i I

f l

I l

i i

i f

t 1

I SU-089/004/1 a

APPENDIX H LOCAL LEAKAGE RATE TESTING EVALUATION During refueling outages, local leakage rate testing (LLRT) is commenced at the beginning of the outage and completed in approximately six to eight weeks. The ILRT, if scheduled for that outage, is conducted after the completion of the LLRT.

During the.LLRT, repairs and adjustments are made to some systems which may change that penetration's leak rate. The term "As Found" indicates the leak rate before repairs and adjustments and the term "As Left" is'the leak rate after repairs and adjustments. An evaluation of the difference between "As Found" and "As Left" can give only some indication of what the ILRT results would be if conducted prior to repairs and adjustments.

Table 1 is a comparison of the "As Found" and "As Left" data for those penetrations which had repairs and adjustments performed during'the LLRT.

Units of measured leak rate are standard cubic centimeters per minute (sces).

O O

su-oe9/oo4/2 H-1

I O

APPENDIX H U

LOCAL LEAKAGE RATE TEST RESULTS REPAIRS AND ADJUSTMElfrS PENETRATION "AS FOUND" "AS LEFT" 1A 215 36.2 1C 8.2 5.4 2A 11.0 11.0 23 1779.2 631.5 7A 9.6 5.3 73 7.3 2.7 8

34.4 640 9

60.8 60.8 10 280 280 13 486.16 2771.11 14 3264.3 833.5

()

20A 503 210 20C 443 33.4 41 36714.85 1716.54 42

.8 72.5 48A 75.1 75.1 50 15.3 239 62 75 32.9 64 104,716.98 462 67 21.8 11.6 68 6806 6806 69 1850 1850 157,377.79 16786.55 TOTAL SYSTEM "AS FOUND".........

161,185.79

" AS LE FT "...........

20,594.55 O

SU-089/004/3 H-2

i a

t 4

i i

i

!' O

)

.j I

i i

l 1

l i

APPENDIX I 1

I i

SENSOR PLOTS i

l i

?

t i

i i

l 1

l l

t i

i i

l i

l I

i l

l i

l I

i l

)

I i

I 1

4 i

}

SU-089/005/8 t

A

l TEMPERATURE SENSOR 1

DEGREES F l

79.000 1

p

+,,,.,_ - + ' '

l 78.900"

,g 1

r/

77.900"

/

/

/

76.000'

/

e' l

/

75.000'

/

J 74.000

.300 1123 TIME HOURS 2315 1124 l

START TIME DATE END TIME DATE I

1

\\

\\

T MPERATURE SENSOR DEGREES F i

85.000 f.

i i

i 83.000 i'

I FAILED SENSOR

,I l

i u ~ -

. s

  • - ~

\\';.s 8.1.

9 0 0

.I

/

<f f

/

i

/

79.900

,t. 3

,f' l

c t

l Li i

i 77.900" l

l t

l 75.000 1

.300 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE

)

i

TEMPERATURE SENSOR 3

DEGREES F

80.800 f

i 75.000 s_

  • s j

70.000 FAILED SENSOR l

-n.__.)

l l

65.900 l

\\

I i

60.000" 55.000 i

.300 1123 TIME HOI. IRS 2315 1124 1

START TIME DATE END TIME DATE i

l

$LUERT CLIFFS llNb 2

ILRT TEMPERATURE SENSOR 4

DEGREES F

80.800 i

]

79.000

_g,

.. r -

,. f j

78.000

/

1 i

.I

/

/

l 77.900

)

/

1

/

76.000"

./

1 I

/

l l

75.000 /..................................

l

.300 1123 TIME HOURS 2315 1124

)

START TIME DATE END TIME DATE i

i i

I

$LUERT CLIFFS UNb 2

ILRT TEMPERATURE SENSOR 5

DEGREES F

1 79.000

" ~ ~ ~ '

~-

i 78.900"

.,\\,,r'~^~

l

./-*

l 77.999"

/

f 1

<C 76.999"

.- r~'

l

/

1 75.900" /.

74.000 ),

.3 30.L.123 TIME HOURS 2315

.1.124 START TIME DATE END TIME DATE 4

l

\\

l i

CkUERTCLIFFS-UNI 2

ILRT TEMPERATURE SENSOR 6

DEGREES F i

86.000 M, _fg-%,.s< <a a-l 84.800 g,f 'f d

_Jt

.i i

83.600

(

/

l

.J'

/s" 82.400

_/'

l

/

FAILED SENSOR 81.200"e/

i

>,5 I

80.000: TOO 1123 TIME HOilRS 2 3.1.5

.1.1 2 4 START TIME DATE END TIME DATE 1

l l

l

CkUERTCLIFFS-llNIk2ILRT TEMPERATURE SENSOR 7

DEGREES F 79.000 I

_.f_dv4^-^

'#~ vr '4 78.900 J'

77.900

/

1

/

,-/

\\

76.000"

-/

/

3 J'

l 75.000",,4/

/

74.000

.3013 1123 IIME HOURS 2315 1124 START TIME DATE END TIME DATE l

$LUERT CLIFFS UNb 2

ILRT l

l TEMPERATURE SENSOR 8

DEGREES F.

79.999

_,,.n. &' ~

i l

78.999

/'

/

)

.e l

\\

r

(

1 i

77.999" f

l

'i r

t 76.999"

/

~~

\\

/

l 75.999"./

i r-l r'

\\

I 74.999 l

.300 1123 TIME HOURS 2315 1124 i

START TIME DATE END TIME DATE I

TEMPERATURE SENSOR 9

DEGREES F 89.999 t

~'

l 79.999 i

r-v

.r,7 78.999

/

i

/

\\

/

1 1

77.999 l

,.c i

. ~ ~

r f

l 76.999"

/

l

./

I 75.999 /..................................

.300 1123 TIME HOllRS 2315 1.1.24 START TIME DATE END TIME DATE l

1 i.

j

$LUERT CLIFFS UHb 2

ILRT TEMPERATURE SENSOR 19 DEGREES F l

79.099

, _s - -

i

<s 78.999

/,.-

j

/

/

/

~

/

i 77.999 i

)

./

i

,/

_r i

76.900

/

\\

/

)

/

l

./

75.900"

/

./

74.000 l'.................................

j

.300 1123 TIME HOURS 2315 1124 l

1 START TIME DATE END TIME DATE 4

l i

]

3

$LUERT CLIFFS UNb 2

ILRT TEMPERATURE SENSOR 11 DEGREES F 79.999 w,_.

-vN

,__ _i,'n 'r 78.999

_e r

r-

/

/

77.999 l'

/

_j 76.999

/

./

,/

75.999"./

./

74.999

_300 1123 TIME HOURS 2315 1124 l

START TIME DATE END TIME DATE l

CkUERTCLIFFS-UNIk2ILRT i

TEMPERATURE SENSOR 13 DEGREES F 1

i 89.999

_f *'W

,_, A,)f!vJW~~ "' ' ^' L

e4 k

79.999

. f0,

'I 78.999"

_d

}

74

\\

w 1

l

\\t.1 77.999"

',/

, t. 0

\\

.i 76.999"'f i

l l

.I 75.999j l

.300 1123 TIME HOURS 2315

.1124 i

j START TIME DATE END TIME DATE t

i a

l 1

i i

Ck UERT CLIFFS UN1h 2

ILRT j

TEMPERATURE SENSOR 13 DEGREES F 79.800 I

1 1

78.000 i

/

77.900

/

\\

/

\\

_r'

/

76.900

/

.i

/

75.900"./

l i

?

I 74.000 ',,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

j

300 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE I

l LUERT CLIFFS UHb 2

ILRT l

TEMPERATURE SENSOR 14 DEGREES F f,f,

, Y '

11qj{j,,~,jV"'-l'?'

, (,

f lI)A.

\\c' \\,

78.000" l

fv F

i 77.000"

,.,[,

t

,.,c l

f/

76.900" ro' d

/

r

~l~

75.000" l 1

l'

'I 74.000

1.,

i

.3013 1123 TIME HOilRS 2315 1124 START TIME DATE END TIME DATE I

l l

CkUERTCLIFFS-UNI 2

ILRT TEMPERATURE SENSOR 15 DEGREES F l

78.800 r.,a, gY". d 77.000 v

i r'

{

a 76.900

/'

/

\\

c' I

)

75.800

\\

.A' 74.900" c'J I

.I 73.000 l..................................

.300 1123 IIME HOLIRS 2315 1124 i

START TIME DATE END TIME DATE l

l i

TEMPERATURE SENSOR 16 DEGREES F 78.999

~./r

~

.f -

s^. ~

.aP 77.999

,,_r '

f

,+ /

i 76.999

/

./

75.BO9

/

i

)

l 74.999 l

/

/l,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,

73.999

.300 1123 TIME HOURS 2315 1124 i

START TIME DATE END TIME DATE i

$LUERT CLIFFS UNb 2

ILRT TEMPERATURE SENSOR 17 DEGREES F 4

79.999 l

78.999 l

l 77.900 FAILED SENSOR 76.999 l

i 75.900" i

74.999

.300 1123 TIME HOURS 2315 1124 i

START TIME DATE END TIME DATE

LUERT CLIFFS UNb 2

ILRT i

i TEMPERATURE SENSOR 18 DEGREES F l

78.800

' ~ ~ _ _ ~

l

,.s-j ',,,

77.000"

~

1

/

?

f 76.000" l

-/

/

l

/

~~/-

l 75.000" b_i i

74.000" /

)

'l 73.000 1,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,....

I

.300 1123 TIME H011RS 2315 1124 START TIME DATE END TIME DATE i

i

)

l l

DEWPOINT TEMPERATURE SENSOR

.1. DEG.

F 1'

89.999 76.999

.. f_

72.999 SENSOR OPERATIONAL 68.999" i

64.999" s.

.s 69.999...........".......................

.399 1123 TIME HOURS 2315 1124 i

START TIME DATE END TIME DATE l

CkUERTCLIFFS-UNIk2ILRT DEWPOINT TEMPERATURE SENSOR 2

DEG.

F 4

80.000 76.900" __

.s t

72.000" SENSOR OPERATIONAL i

68.900" 64.000"

's,_

3 I

l 60.000

.300 1123 TIME HOI. IRS 2315 1124 l

START TIME DATE END TIME DATE i

Ck UERT CLIFFS UNIk 2 ILRT DEWPOINT TEMPERATURE SENSOR 3

DEG.

F i

80.800 i

l I

76.000 72.900 SENSOR OPERATIONAL 68.000" 64.000" 60.000

. 31313 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE

LUERT CLIFFS UNb 2

ILRT DEWPOINT TEMPERATURE SENSOR 4 DEG.

F 70.800 66.000" i

62.000"

\\

.t I

i 58.000' '

54.000" i

50.000

.300 1123 TIME HOURS 2315 1124 START TIME DATE END TIME DATE i

l

CkUERTCLIFFS-UNIk2ILRT DEWPOINT TEMPERATURE SENSOR 5

DEG.

F 70.000 l

i 66.000 l

j 62.000" /

I i

l 58.000" i

l 54.000" I

b I

l 50.000

.300.1.123 TIME HOURS 2 3 1 5

.1.1.2 4 START TIME DATE END TIME DATE i

l

CkUERTCLIFFS-UNIk2ILRT DEWPOINT TEMPERATURE SENSOR 6

DEG.

F l

80.900 p

76.900"

~

72.000" SENSOR OPERATIONAL 68.000" l

i 64.900" l

~

60.000 c.......................

. 31313 1123 TIME HOURS 2315

.1.124 i

START TIME DATE END TIME DATE l

l

CkLUERTCLIFFS-UNI 2

ILRT PRESSURE SENSOR 1 PSIA 65.400

/_ -

./ -

65.300" c'g I

e 65.200"

/

I

]

\\

65.100"

/

/

65.000"

/

i

/

,1 w/

64.900

.300 1123 TIME HOI.lRS 2315 1124

]

START TIME DATE END TIME DATE

$ LUERT CLIFFS UNb 2

ILRT PRESSURE SENSOR 2 PSIA 65.400

,s' i

65.300

/

,f 65.200" f

l

[

l

)

65.100"

/.

l f

i

/

i 65.000"

,/

j

64. 900f"313I31.1.23 i

TIME HOURS 2315 1124 START TIME DATE END TIME DATE l

i l

- - - _ - - - -