ML20154L048

From kanterella
Jump to navigation Jump to search
Application for Amends to Licenses NPF-11 & NPF-18,adding New Fire Detector Location to Unit 1 & Deleting Requirement for Special Rept If Number of Operable Detectors Falls Below Min Specified.Fee Paid
ML20154L048
Person / Time
Site: LaSalle  
Issue date: 03/04/1986
From: Allen C
COMMONWEALTH EDISON CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20154L051 List:
References
NUDOCS 8603110381
Download: ML20154L048 (2)


Text

!

.1 N Commonwealth Edison O ) One First NItional Plaza, Chicago. Hhnois C.? '

Addrsss Riply to. Post Ofhce Box 767 Chicago, Ilknois 60690 March 4, 1986 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Cotanission Washington, DC 20555

Subject:

LaSalle County Station Units 1 and 2 Proposed Amendment to Technical Specification for Facility Operating License NPF-11 and NPF-18 Fire Detection Instrumentation

  • NRC Docket Nos. 50-373 and 50-374

Dear Mr. Denton:

Pursuant to 10 CFR 50.90, Commonwealth Edison proposes to amend Appendix A. Technical Specification, to Facilit'y Operating License NPF-11 and NPF-18.

This amendment change is being submitted ' for your staff's review and approval.

The proposed amendment adds new fire detector locations to Unit 1 to satisfy License Condition (NPF-11) 2.C.(25)(c).

In addition, an administra-tive change is made to both Unit 1 and Unit 2 licenses to delete the requirement for a special report submittal in the event the number of operable detectors falls below the minimum specified. This administrative change is made to restore LaSalle Technical Specifications to conformance with the GE BWR Standard Technical Specifications.

Attachment A provides background and discussion. The proposed change is enclosed in Attachment B.

The attached change has received both On-Site and off-site review and approval. We have reviewed this amendment request and find that no significant hazards consideration exists. Our review is documented in Attachment C.

Conunonwealth Edison is notifying the State of Illinois of our request for this amendment by transmitting a copy of this letter and its attachments to the designated State Official.

In accordance with the requirements of 10 CFR 50.170, a fee remittance in the amount of $150.00 is enclosed, O

hD3h i

8603110381 860304 PDR ADOCK 05000373 P

PDR lj w g.7/50

\\'

i H. R. Denton March 4, 1986 Please direct any questions you may have concerning this matter to this office.

Three (3) signed originals and thirty-seven (37) copies of this transmittal and its attachments are provided for your use.

Very truly yours,

^

C. M. Allen Nuclear Licensing Administrator im Attachments A: Background and Discussion B: Technical Specification Changes to NPF-ll and NPF-18 C:

Evaluation of Significant Hazards Consideration cc: Region III Inspector - LSCS A. Bournia - NRR M. Parker - State of Ill.

SUBSCRIBED AND S to beforpj/r1 loa 1me thfs day of

'H

, 1986 i' b ADJ Notary Public j)

/)

1346K

ATTACHMENT A LASALLE COUNTY STATION UNITS 1 AND 2 TECHNICAL SPECIFICATION CHANGE REQUEST

SUBJECT:

Fire Detection Instrumentation REFERENCES (a): -NPF-11 License Condition 2.C.(25)(c).

(b): UFSAR Appendix H (H.2.3.2.4, H.3.3.4, H.3.4.4, H.3.4.5 and H.3.6.7).

(c): SSER #2 Section 9.5.8.

(d): NUREG-0123, GE-STS 9BWR), Standard Technical Specifications.

BACKGROUND: Reference (a) required additional fire detection be added to fire zones 2C/3C, 4C3 and 6E.

Fire detection was installed in fire zones 3C and 4C3 prior to the licensing of LSCS Unit 2 (NPF-18) and these zones are included in the Unit 2 Technical Specifications. Fire detection was also installed on the north (Unit 2) portion of zone 6E and is also included in the Unit 2 Technical Specifications. There is no Unit I required safe shutdown equipment in fire zones 3C or 4C3.

Installation of fire detection for fire zones 2C, 4C2, and the south (Unit 1) portion of 6E will be completed prior to startup following the Unit 1 first refueling outage.

DISCUSSION: The minimum number of operable fire detectors for zones 2C (1-40), 4C2 (1-39) and 6E (1-38) have been added to Table 3.3.7.9-1 (Attachment A).

The LSCS fire detectors in these zones meet the guidelines and intent of NFPA 72E.

The detector design was reviewed by a fire protection engineering consultant and found to be acceptable.

The requirements ot Specification 3.3.7.9 action b which require submittal of a Special Report if the minimum number of operable detectors is not met for greater than 14 days is unnecessary and no longer required by reference (d).

When compensatory actions are initiated per action a of Specification 3.3.7.9 (i.e., a fire watch established) fire detection integrity is maintained. This change of reporting requirements will reduce an unnecessary reporting burden and is proposed for both Unit 1 and Unit 2.