Text
i I
TOLE 00 EDISON s enew en crcr..
OCNALD C, 3"ELTCN
.cen, m - u ev Docket No. 50-346 License No. SPF-3 Serial No. 1-781 February 16, 1988 Mr. A. B. Davis Regional Administrator U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137
Subject:
Response to NRC Compliance Bulletin No. 87-02
Dear Mr. Davis:
Toledo Edison (TED) hereby submits the information requested by NRC Compliance Bulletin No. 87-02, "Fastener Testing to Determine Conformance with Applicable Material Specifications", dated November 6, 1987 (Log 1-1699).
The subject hulletin required that licensees review fastener receipt inspection requirements, and internal material controls; determine through testing, whether stock fasteners meet required specifications and evaluate the safety Fignificance of those fasteners which did not teet the applicable specifications.
TED made a initial response on December 21, 1987, Serial 1-771, indicating that a final response would be submitted by February 15, 1988.
TED hereby submits the information necessary to close this bulletin.
TED's evaluation found 45 of the 51 fasteners tested met the applicable specifications.
The 6 fasteners which did not meet the required speci-fication were evaluated based on the overall test results and their use in the plant.
TED's evaluation determined those fasteners to be acceptable for their intended use.
Sincerely
- t. r s,
!'V\\.
~
({
J S:bam cc:
Document Control Desk DB-1 Resident Inspector
\\
l A. W. DeAgazio NRR Project Manager i
k EDISON PLAZA 3M MAD! SON AVENUE
- 0LEDO OHFO 43652 C
b-A=-
La
~
C'-
++-
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Page 2 RESPONSE TO NRC BULI.ETIN 87-02 FOR DAVIS-BF.SSE NUCLEAR POWER STATION UNIT NO. 1 This letter is submitted in conformance with Atemic Energy Act of 1954 Section 182a. in response to NRC Bulletin 87-02 (Log No. 1-1699) "Fastener Testine to Decemine Confor=ance with Applicabic Material Specifications".
! N s,
D.'C.
Shelton, Vice President. Nuclear i
l Sworn and subscribed before ce this 16thday of February,1988.
bWh
(
'l Notary Public, State of Ohio My Commission expires
/f
/
4
/
1
..c.__,
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Enclosure Page 1 RESPONSE TO NRC COMPLIANCE BULLETIN NO. 87-02 The following sections provide Toledo Edison's response for each of the Bulletin 87-02 action items:
NRC ACTION 1r Describe a) the characteristics currently examined during eceipt inspection of fasteners (i.e., head markings for grade and manufacturer symbols, review of certified material test report or certificate of conformance), and b) internal controls utilized during storage and issuance from stock to assure the appropriate use of fasteners.
TED Response Receipt inspection and internal controls prerent at Davis-Besse to ensure appropriate fastener use are:
Receipt inspections of safety-related fasteners are performed in accordance with TED procedure QA-VQ-01301.07, Receipt Inspection, Vendor Documentation Review and Purchase Order Closure.
QA-V0-01301.07 contains guidance for receipt inspection and describes how those attributes are to be inspected when required by the General Material Inspection Checklist (GMIC).
These documents provide assurance that the following characteristics are inspected upon material receipt:
manufacturer's symbol, grade designation earking, fasteners identification and material certification.
Davis-Besse Nuclear Group Procedure NG-NP-00400, Materials Management, governs the receipt, storage, and issuance of fasteners.
Upon arrival fasteners are inspected for physical damage and to verify description and quantity.
Discrepancies are recorded and resolved prior to issuance for installation or use.
Safety-related mate' rials are segregated and controlled to prevent mixing with nonsafety-related eaterial.
Stock material including safety-related items are identified and stored by stock number.
Materials with the same stock number are purchased to the same requirements (e.g. material grade, material) or similar requirements which have been evaluated as being acceptable.
l
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Enclosure Page 2 Storage of material with different stock numbers in the same location is not permitted.
It is the responsibility of the end user to identify from design documents the correct bolting material for the appliention and its corresponding stock number.
Materials Control personnel ensure that the stock number issued is the stock number requested.
NRC ACTION 2:
Select a minimum sample of ten (10) non-safety related fasteners (studs, bolts, and/or cap screws), and ten (10) safety-related fasteners (studs, bolts, and/or cap screws) from current. in use, stock.
The sample is to be obtained by the licensee with the participation of an NRC inspector.
Fasteners procured to meet the following chemical and mechanical properties are of interest: A-193 graces B7, B8, and B16; SAE J429 grades 5 and 8; A-449; A-235 Types 1, 2 or 3; A-354 grades BB, BC, BD; A-490; A-320 LTM; A-307; A-563; or equivalent.
TED Resnonse Refer to response for NRC Action 3.
NRC ACTION 3:
For the selected sample of fasteners in item 2 include a j
sample of typical nuts that would be used with each fas:ener (one-for-one).
In particular, nuts purchased to the chemical and mechanical specifications of A-194 are of interest.
TED Resoonse A total of 51 fasteners (nuts, bolts and studs) were sampled. The majority of these fasteners were selected from the fasteners of particular interest per the bulletin.
The NRC Resident Inspectors participated in the sampling.
A sample of typical nuts that would be used with each f astener (one-for-one sampling) proved impractical due to the unavailability of items in stock.
NRC ACTION 4:
Chemical testing shall be performed on all samples.
Mechanical testing shall be performed on each safety-related fastener. Hardness testing shall be performed on each nut and non-safety-related fastener. All testing shall be performed by a laboratory which the licensee has cualified for this type of testing and appears on the licensae's approved vendor list. Testing performed shall be done in accordance with the requirements of the fastener's specification, grade, and class, and the test shall evaluate the ultimate tensile strength, hardness and chemical properties as required by the fastener's speci-fication, grade, and class.
Each s.smple shall be tagged with the sample's ID number.
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Enclosure Psqe 3 TED Response Chemical, mechanical and hardness testing were performed on all of the samplea, both safety-related and nonsafety-related fasteners. The testing was performed by a TED approved laboratory qualified for this type of testing.
The testing was performed in accordance with ASTM-approved methods required by the fasecner's specificatien, grade and class.
Each sample was provided with a unique identification number.
NRC ACTION 5:
The results of all tests, together with supporting information, are to be reported to the HRC utilizing the format shown in Attach 7ents 1 and 2 of this bulletin.
Include the names and adcresses of suppliers and manufacturers of safety-related fasteners and, to the extent possible, of non-safety-related fasteners.
For any fastener found out of specification, provide an evaluation of the safety rignificance including j
consideration of the most limiting application.
TED Response Results of TED's Bulletin 87-02 testing are presented in, using the format suggested by the bulletin.
Results which do not neet the applicable specification requirement are denoted by an asterisk (*).
Attachment I contains the Fastener Testing Data Sheets along with a list of the fastener supplier and manufacturer names and addresses.
i Two fasteners of stock number DB-15-1793 and four nuts of j
stock numbers DB-15-4170 and DB-15-4197 did not meet i
required specifications. A brief description of each and an evaluation of the safety significance is provided below.
1.
Sample DB-15-4197 (17 A & B) - consisted of two 1/4"-20 hex nuts made of SA 194 Grade 2H material.
The nuts were procured as safety-related fasteners.
j The Rockwell Hardness test results indicate that the i
hardness of the nuts was slightly above specification (39 HRC and 40 HRC, specification is 24-38 HRC).
All other properties tested met the chemical and physical specification requirements. A review indicates that 51 of these nuts were irsued to the field. One nut was issued in a nonsafety-related pipe hanger install-ation and fifty were used in a non-pressure boundary structural application (grating). Considering the use of the nuts and since all other parameters were in specification, there is no nuclear safety sigr.ificance to the discrepancy.
Docket Ne. 50-346 License No. KPF-3 Serial No. 1-781 Enclosure Page 4 2.
Sample DB-15-1793 (15 A 6 B) - consisted of two 9/16" x 1-1/4" bolts made of SAE J429 Grade 5 material.
These bolts were procured as nonsafety-related fasteners and it has been verified that none of these bolts were used in a safety application. The Rockwell test results indicate that the hardness was sightly below the specification (both~ samples were 21 HRC, specifi-cation is 25-34 HRC).
All other properties tested met the specification requirements.
Since these bolts were not used in any safety application, and all other parameters were in specification, there is no nuclear safety significance to the discrepancy.
3.
Sample DB-15-4170 (27, 28) - consisted of two 1-1/4" hex nuts, one made of ASTM A194 Grade 2H and the other believed to be SAE J995C Grade 2 material-These nute were procured as nonsafety-related fasteners and none of these nuts were used in a safety application. The Rockwell test results' indicate that the nardness of the ASTM A194 Grade 7H nut was slightly below the specification (23 HRC, specification is 24-38 FRC).
The SAE J995C Grade 2 nut, although in specification, had a considerably low hardness (53 HRB, specification is 30 HRC max (108 HRB equivalent)).
All other properties tested were in specification.
Since there nuts were not used in any safety application, there is l
no nuclear safety significance to the discrepancy.
The fasteners and nuts from the stock number of the above discrepancies (i.e. DB-15-4170, DB-15-4197, and DB-15-1793) have been removed from the-stock system j
and placed in a QA hold area to be dispositioned as non-conforming items.
NRC ACTION 6:
Based on the results of the testing and review of current procedures, described any further actions being taken to assure that fasteners used in the plant meet the requisite specifications and requirerents and that the operability of safety-related plant components is not affected.
TED Response Toledo Edison has revised the receipt inspection procedure to provide for further examination of fasteners to ensure that manufacturer's symbols and grade designations are present on nominal diaceters of 1/4" or larger, where specifically required by the material specific: Lion or International Fastener Institute (IFI)-122.
Based on reviews of current procedures for receipt inspection /
material handling, and the bulletin testing program, TED considers no further actions are necessary.
. ~ _ -
Docket No. 50-346 i
License No. NPF-3 Serial No. 1-781 Enclosure Page 5 APPENDIX
- 1. - Fastener Testing Data Sheets
- Listing of Suppliers / Manufacturers SAMPLE IDENTIFICATION NO.
Safety-related Fasteners Nonsafety-related Fasteners DB-15-1220 DB-15-1790 DB-15-4302 DB-15-1784 DB-15-4533 DB-15-1797 DB-15-4540 DB-15-1219 DB-15-4314 DB-15-1789 DB-15-4306 DB-15-1242 DB-15-4273 DB-15-1221 DB-15-4256 DB-15-1225 DB-1-87-1182-00 DB-15-1604 DB-15-4197 DB-15-1793 DB-15-4201 DB-15-4170 DB-15-4204 DB-15-4206 DB-15-4214 DB-15-4016 DB-15-4208 DB-15-4017 DB-15-4195 DB-15-4019 DB-15-4199 DB-15-4209 DB-15-4259 2.
Attacheent 2 - Fastener Data Summary Safety-related Fasteners Nonsafety-related Fasteners
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet OSample ID#
DB-15-1220 Fastener
Description:
Bolt, Mach 5/8" x 3 3/4" Dascription of Sample Stock Location:
U-053-C Material Specification as Documented by Licensee Records:
SA193 GR B7 Head Marking (Specification and Manufacturer)- K B 7, A'a'N Grade & Manufacture ID
- 0 Class / Procurement Level:
Q, Safety Related G3neral Plant Application (e.g., Pressure Boundary, Structural) *1 ant Safety Relate Systems / Pressure Boundary Vendor: chicago Tube 6 Iron Q0005'.0 i
QA Requirements Imposed on Vendor:
ASME Sect. III 71ED. No Add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature N
Date
/
- The sample ID# shall have a prefix that contains the licensee facility initiale
- elf applicable, please provide an explanation for your classification system
Docket No. 50-346 License No, h7F-3 Serial No. 1-781
)
Attachment i Fastener Testing Data Sheet eSample ids DB 15-4302 Fastener
Description:
Stud, 5/8" x 6 1/4" Description of Sample Stock Location: UH-019 Material Specification as Documented by Licensee Records:
SA193 GR E7 Hoad Marking (Specification and Manufacturer):
B7, T Grade & Manufacture
- Class / Procurement Level:
0, Safety Related General Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Related Systems / Pressure Boundary Vendor: Hub, Inc.
096267 QA Requirements I:oposed on Vendor:
ASME Sect. III 71ED No Add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date 88
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachment i Fastener Testing Data Sheet CSample ID#
DB-15-4533 Fastener
Description:
Stud, 1/2" x 4" Dascription of Sample Stock Location: UG-053 Material Specification as Documented by Licensee Records:
SA 193 GR B7 Head Marking (Specification and Manufacturer):
KB7, XXZ Grade 6 Manufacture ccClass/ Procurement Level:
n, Safety Related GGneral Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Relatei Systems / Pressure Soundary Vendor:
Kilbourne Engineering n00t.267ST QA Requirements Imposed on Vendor:
ASME Sect. III 71ED. So add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date
- /5)If
/
- The sample ID# shall have a prefix that contains the licensee facility initials acIf applicabic, please provide an explanation for your classification system
, Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSemple ID#
DB-15-4540 Fcatener
Description:
stud, 3/4" x 2" Description of Sample Stock Location:
UG-057 Material Specification as Documented by Licensee Records:
SA193 GR B7 Head Marking (Specification and Manufacturer):
C, B7 crade & Manuf acture ID CCClass/ Procurement Level:
Q, Safety Related Ganoral Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Relatec Systems /cressure Vendor:
Boundarv 4 alter C a el Company 033945 QA Raquirements Imposed on Vendor:
AsME sect. III Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Precurement Signature Date 4/6/8f
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
, Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachmer.t 1 Fastener Testing Data Sheet CSample ID#
DB-15-4314 Fastener
Description:
stud, 5/8" x 3 3/4" Dascription of Sample Stock Location:
Uc-027 Material Specification as Documented by Licensee Records:
SM 93 GR 38 Head Marking (Specification and Manufacturer):
AXM, KB8 Grade 6 Manufacture
- Class / Procurement Level:
o, sat 2 y Related Ganeral Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Related Systems / Pressure Boundary Vendor:
Y.ilbourne Engineering 0005542sT QA Requirements Imposed on Vendor:
ASME Sect. III 71ED
.No Add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature M,. i i Date 7
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 i
License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSample ID#
DB-15-4306 Fastener
Description:
Stud, 3/4" x 5 3/4" Descriptic:. of Sample Stock Location:
UJ-019 Material Specification as Documented by Licensee Records:
SA193 GR B8 Head Marking (Specification and Manufacturer)- AXM, KB8 Grade & Manufacture ID CCClass/ Procurement Level:
0, Safety Related i
Ganoral Plant Application (e.g., Pressure Boundary, S +.ru c tu ra l ) Plant Safety Relate Systens/ Pressure Boundary Vendor: Kilbourne Engineering 0005930 QA Requirements Imposed on Vendor:
ASME Sect. III 71ED.
No Add.
Licensee Representative:
M. C. Beier Enginaering /.saurance Supervisor, Procurement Signature Dcte A/6/8F
- The sample ID# shall have a prefix that cc,atains the licensee facility initials
- cIf applicable, please provide an explanation for your classification system
1 Docket No. 50-346 i
License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSomple ID# DB-15-4273 Fastener
Description:
7/8" x 5" Hex Head Cap Screw Description of Sample Stock Location:
L'-05 3 D Material Specification as Documented by Licensee Records:
ASD! A-307 Cr. B Head Marking (Specification and Manufacturer):
st ecClass/ Procurement Level:
Q, Safety Related General Plant Application (e.g., Pressure Boundary, Structural) Safety Related use/
Non Pressure Boundary Vendor: Chicago Tube 6 Iren ^000540ST QA Requirements Imposed on Vendor:
Procured per ASD! A-307 Gr. B Licensee Representative:
M. C.
Beier Engineering Assurance Supervisor, Procurement Signature Date I
-~
/
0The sample ID# shall have a prefix that contains the licensee facility initials ccIf applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial ho. 1-781 Fastener Testing Data Sheet
- Sample IDW DB-15-4256 Fastener
Description:
3/8" x 1 1/2" Head, Hex Description of Sample Stock Location:
t-H02-1 Material Specification as Documented by Licencee Records:
ASD! A-307 GR. B Hoad Marking (Specification and Manufacturer):
B S
a
- Class / Procurement Level:
0, safety Related Gsneral Plant Application (e.g.,
Pressure Boundary, Structural) Safety Related use/
Non-Pressure Boundary Vendor:
All State Fastener Q009885ST QA Requirements Imposed on Vendor:
Procured per ASDt A-307 Cr. 5 Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement I
Signature i!88 Date
/
- The sample ID# shall have a prefix that contains the licensee facility initials 1
- If applicable, please provide an explanation for your classification system
1 Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachment i Fastener Testing Data Sheet
- Sample IDy DB-1-87-ll82 BOM #0008, Sample Quantity - 2 each Fastener
Description:
Hex HD cap Screw 1/2" - 13 x 1 1/4" Description of Sample Stock Location:
Non-stock Material Specification as Documented by Licensee Records:
\\
Head Marking (Specification and Manufacturer):
KS
/\\
- Class / Procurement Level:
0, Scfety Related General Plant Application (e.g.,
Pressure Boundary, St ruc tu ral ) Rela t S, s t e. /
Son Dressure Boundary Vendor: All State Fasteners 00ll454ST QA Requirements Imposed on Vendor:
Meets requirements of SAE CR.5 Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date *1N/59
/
i
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classific.ation system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ids DB-15-4197, sample Ouantity - 2 each Fastener
Description:
Nut, Hex 1/4"-20 Dascription of Sample Stock Location:
UH-023 i
i Material Specification as Documented by Licensee Records:
SA194 GR 2R i
Head Marking (Specification and Manufacturer):
2H, T Manufacture, Grade, Process
- Class / Procurement Level:
Q, Safet:. Related Gsneral Plant Application (e.g., Pressure Boundary, Structural) Plant safety Related Systems / Pressure Boundary Vendor: Hub, :nc. n011:05 1
QA Requirements Imposed on Vendor: ASME Sect. III 71Ed., No Add.
)
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement l
Signature Date If
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system i
, Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachment i Fastener Testing Data Sheet
- Semple ID#
DB-15-4201 Fastener
Description:
Nut, Hex, 5/8" Description of Sample Stock Location:
UG-029 Material Specification as Documented by Licensee Records:
ASDi A-307, Gr. B Head Marking (Specification and Manuf acturer)-
T e* Class / Procurement Level:
0, Safety Related General Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Related Systems /Non-pressure Boundary Vendor: REC Corp.
044476 QA Requirements Imposed on Vendor: Asn! A-307 Gr. B Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature
,28[F Date
/
- The sample IDW shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system i
1 Docket No. 50-346 i
License No h7F-3 Serial No. 1-781 Fastener Testing Data Sheet
- Somple ids DB-15-4204 Fastener Descriptior.: Nut, Hex, 3/4" - 10 Description of Sample Stock Location:
UJ-029 Material Specification as Documented by Licensee Records:
SA307 GR. B Head Marking (Specification and Maucfacturer)'
JAC T Manufacture ID
- Class / Procurement Level:
Q, Safety Related Generai. Plant Application (e.g., Pressure Boundary, St ructural) Plant safety Related Systems /Fressure Boundary Vendor: REC Corp.
063687 QA Requirements Imposed on Vender:
ASME Sect. III 1971 ED S. Add., SA307 e. B Licensee Representative:
M.
C. Beier Engineering Assurance Supervisor, Procurement Signature Date F I
/
- The sample ID3 shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSample ID# DB-15-4214 Fastener
Description:
Nut, Hex - 1" Dascription of Sample Stock Location:
t-053-D Material Specification as Documented by Licensee Records:
SA 194 GR6 Head Marking (Specification and Manufacturer):
6B, JSH, SAS Manufacture, Grade, Proce ceClass/ Procurement Level:
0, Safety Related General Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Relate Systems / Pressure Boundary Vendor:
Power & Ens;ineered Products Company 0 7579 QA Requirements Imposed on Vendor:
ASME Sect. III CL. 2 1971 Ed. No Add.
l Licensee Representative:
M. C. Beier Engineering Aesurance Supervisor, Procurement
)
Signature
/
D,te
- The sample ID# shall have a prefix thet contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSample ids DB 15-4208 Fastener
Description:
Nut, He.x 3/010 Description of Sample Stock T.ocation:
UJ-027 Material Specification as Documented by Licensee Records:
SA194 1R6 Hood Marking (Specification and Manufacturer;-
A1, 6CF Manufacture Grade. Process CCClaas/Procurecent Level:
Q, Sa fety Related General Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Relater Systems / Pressure Boundary Vendor: Hub 096267 QA Rcquirements Imposed on Vendor:
ASME Sect. III 71ED, : o add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date a
N
/
/
- Tho sample ID# shall have a prefix that contains the licensee facility initials
{
- elf applicable, please provide an explanation for your classification system l
~.
\\
Docket No. 50-346 License No. NPF-3 Serial No, 1-781 Fastener Testing Data Sheet Seaple ID#
DB-15-4195, Sample Quantity - 2 each Fastener
Description:
Nut. Hex 3/8"-16 l
Dascription of Sample Stock Location:
UH-023 Material Specification as Documented by Licensee Records:
SA 194 Gr. 2H i
Head Marking (Specification and Manufacturer):
K, 2HB M.anufacture, Grade, Process
)
CClass/ Procurement Level:
Q, Safety Related Ganoral Plant Application (e.g., Pressure Boundary, Structural) Plant Safety Relate l
Systems / Pressure Boundary Vendor: Kilbourne Engineering 0004267sT QA Requirements Imposed on Vendor: ASME Sect. III 71ED, So Add.
Licensee Representative:
M. C. Beier i
Engineering Assurance Supervisor, Procurement Signature b
/
Date
- The sample ids shall have a prefix that contains the licensee facility initials
- If applicable, please provide an exp"anation for your classification system
Docket No. 50-346 License No. h7T-3 Serial No. 1-781 Attachment I l
t Attachment i Fastener Testing Data Sheet
- Sample ID#
DB-15-4199, Sample Quantity - 2 each Fastener
Description:
Nut, Hex lh" - 13 Doncription of Sample Stock Location:
UH-055 daterial Specification as Documented by Licensee Records:
SA194 GR 2H Head Marking (Specification and Manufacturer):
2HB, art., K Manufacture, Grade Proces
- Class / Procurement Level: e, Safety Related Gonoral Plant Application (e.g.,
Pressure Boundary, St ructural ) Plant Safety Related Systems / Pressure Boundary Vendor: Kilbourne Enzineering A99970A QA Requirements Imposed on Vendor:
ASME Sect. III 71ED "o Add.
Licensee Representative:
M. C. Beier Engineering Assurance Supervise.r, Procurement Signature Date M* N
"^^
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system l
j
Docket No. 50-346 License No. b7F-3 Serial No. 1-781 9
Fastener Testing Data Sheet OSample ids DB-15-4209 Fastener
Description:
Nut, Hex, 7/8"-9 Description of Sample Stock Location:
UJ-029 Material Specification as Documented by Licensee Records:
A563 CR C or D Head Marking (Specification and Manufacturer): Three Circumferential Lir.es, T, JAU
- Class / Procurement Level:
- 0. Safety Related Ganoral Plant Application (e.g., Pressure Boundary, Structural) Plant safety Relate i
Systems / Pressure Boundar
)
Vender: REC Corporation
'63687A QA Requirements Imposed on Vendor:
AsME Sect. III 71ED, S. Add.
Licensee Representative:
M. C. Beler Engineering Assurance Supervisor, Procurement Signature
/
f8 i Date
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 g
License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet aSaaple ids DB-15-4259 Fastener
Description:
1/2" x 2" HH Cap Screw Description of Sample Stock Location:
U-053-E Material Specification as Documented by Licensee Records: Asn! A-3C7 Cr. B Head Marking (Specification and Manufacturer):
R eoClass/ Procurement Level: Q, safety Related General Plant Application (e.g., Pressure Boundary, Structural) Safety Related use, Son-Pressure 3oundary Vendor:
REC Corp.
A71354A QA Requirements Imposed on Vendor:
Procured per Asnt A-307 Gr. B Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature
~
Date
[
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- elf applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachment I Fastener Testing Data Sheet
- Sample ids DB-15-1790 Fastener
Description:
7/16"NT x 2" Hex Bolt Dascription of Sample Stock Location:
FO-20E Material Specification as Documented by Licensee Records:
Not specified Head Marking (Specification and Manufacturer):
l
/\\
c8 Class / Procurement Level: Non-Q/Non-safety General Plant Application (e.g.,
Pressure Boundary Structural)
Plant Son-Safety Syste.s, General Use/Non-pressure, Boundary Vendor: Non-Safety Supplier per attached list QA Requirements Imposed on Vendor:
Nene Licensee Representative:
M. C. Beier Engineering Assur.ance Supervisor, Procurement Signsture Date E 8I
- The sample ID# shall have a prefix that contains the licensee facility initials
- cIf applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. b7F-3 Serial No. 1-781 Fastener Testing Data Sheet OSample ids DB-15-1784 Fastener
Description:
7/16"NF x 3/4" Hex Bolt Description of Sample Stock Location:
F-020-F Material Specification as Documented by Licencee Records:
Not specified Haad Marking (Specification and Manufacturer)-
b
/\\
- Class / Procurement Level: Non-0/Non-safety General Plant Application (e.g., Pressure Boundary, Structural)
Plant Non-Safety Systers, General Use/Non-pressure Boundary i
Vendor: Non-Saf ety supplier per attached list QA Requirements Imposed on Ver' dor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement i
Signature Date O
f
- The sample ID# shall have a prefix that contains the licenace facility initials
- If applicable, please provide an explanation for your classification system l
1
Docket No. 50-346 1,1 cense No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet CSample ids DB-15-1797 Fastener
Description:
9/16"NC x 2 1/4" Hex soit Description of Sample Stock Location: F-020-C Material Specification as Documented by Licensee Records:
Not specified Hoad Marking (Specification and Manufacturer)-
/s N ceClass/ Procurement Level: Non-0/Non-safety General Plant Application (e.g., Pressure Boundary Structural)
Plant Non-Safety Systems, General Use/Non-pressure, Boundary Vendor: ':en-safety supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature ___
Date D E
/
CThe sample ID# shall have a prefix that contains the licensee facility initialt
- If applicable, please provide an explanation for your classification system
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Attachment i Fastener Testing Data Sheet cSemple ids DB-15-1219 Fastener
Description:
5/8" x 3 1/2" Machine Bol Z/P with Hex Nut Description of Sample Stock Location:
F-018-E Material Specification as Documented by Licensee Records:
Not specified Head Marking (Specification and Manufacturer).
None
- Class / Procurement Level: Nen-Q/Non-safety General Plant Application (e.g., Pressure Boundary, Structural) non-Safety syster.s General Use/Non-Pressure Vendor: Non-safety supplier per attached list Boundary QA Requirements Imposed on Vendor: None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature IN Date
- I
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
l Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ID#
DB-15-1789 Fastener
Description:
7/16"Nc x ! 1/2"Hex Bolt Dascription of Sample Stock Location:
F-020-E Material Specification as Documented by Licencee Records:
Not specified i
Head Marking (Specification and Manufacturer):
D
/\\
- Class / Procurement Level: Non-q/Non-safety General Plant Application (e.g., Pressure Boundary Structural)
Plant Non-Safety Systems, General Use/Non-pressure, Boundary Vendor: Non-Safety supplier per attached list QA Roquirements Imposed on Vendor: None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date A/5!II
- The sample ID# shall have a prefix that contains the licensee facility initials
- 1f applicable, please provide an explanation for your classification system
. Docket No. 50-346 i
License No. NPF-3 Serial No. 1-781 Attachment i Fastener Testing Data Sheet
- Sample ID#
DB-15-1242, Sample Quantity - 2 each Festener
Description:
Machine Bolt, 3/4"x 1 1/2" w/ Nut Description of Sample Stock Location:
F-018-C t'aterial Specification as Documented by Licensee Records:
Not specified Head Marking (Specification and Manufacturer). K on Bolt - So markines on nuts seClaes/ Procurement Level: Son-o/ Son-safety I
General Plant Applicatien (e.g., Pressure Boundary, Structural)
Plant Non-Safety Systems, General Use/Non-pressure Boundary Vendor:
Sen-Saf ety supplier per at tached list QA Requirements Imposed on Vendor:
Sone Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Ab-2/fd 5 Date
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system i
,-Docket No. 50-346
' License No. NPF-3 Serial No. 1-781 Attach =ent 1 Attachment'l Fastener Testing Data Sheet cSample ids DB-15-1221. Sample Quantity - 2 each Fastener
Description:
Machine Bolt, 3/8" x 4" w/ Nut Description of Sample Stock Location:
F-018-D Material Specification as Documented by Licensee Records:
Not specified
\\
Head Marking (Specification and Manufacturer):
KS
/\\
- Class / Procurement Level: Non-0/Non-safety General Plant Application (e.g., Pressure Boundary, Struc tu ral ) Plant Non-safety Systets ' General L*se, Non-pressure Boundary Vendor:
Non-sa f e t:. Supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement i
Signature
?
Date I
/
i
- The sample ID# shall have a prefix that contains the licensee facility initialt
- If applicable, please provide an explanation for your classification system
, Docket No. 50-346 License No, NPF-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ids DB-15-1225, Sample cuantity - 2.each Fastener
Description:
Machine Bolt, 5/8" x 5" v/ Nut Description of Sample Stock Location:
F-018-D Material Specification as Documented by Licensee Records:
Not specified
\\
Head Marking (Specification and Manufacturer):
KS
/N
- Class / Procurement Level:
Son-Q/Non-safety General Plant Application (e.g.,
Pressure Boundary, Structural)
Plant Non-Safety Systems, General Use/Non-pressure Ecundary Vendor: Son-safety supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature U -
Date A/D if j
i
- The sample IDW shall have a prefix that contains the licensee facility initials
)
- cIf applicable, please provide an explanation for your classification system i
l
)
~~
. Docket No. 50-346 License No. NPF-3 Serial No. 1-781
' Attachment 1 Fastener Testing Data Sheet CSample ID#
DB-15-1604 Sample Quantity - 2 each Fastener
Description:
Bolt, 1 1/4" x 7" Description of Sa=ple Stock Location: f 020 F Material Specification as Documented by Licensee Records:
Asnt A490 Head Marking (Specification and Manufacturer): A 490, C
- Class / Procurement Level:
Non-Q/Non-safety Gsneral Plant Application (e.g.,
Pressure Boundary, Structural) Plant 'en-safety Systems / General Use. Non-pressure Boundar-Vendor:
Non-safety supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M.
C. Beier Engineering Assurance Supervisor, Procurement Signature Date
/
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
. Docket No. 50-346 License No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet
~8 Sample ID#
DB-13-1793. Sample Ouantity - 2 each Fastener
Description:
Hex Bolt, 9/16"NC x 1 1/4" Dascription of Sample Stock Location F-020-D Material Specification as Documented by Licensee Records:
Not specified i
Head Marking (Specification and Manufacturer). Rockford N/
I
- Class / Procurement Level: Non-0/Non-safety General Plant Application (e.g., Pressure Boundary, Structural)
Plant non-Safety Systems / General IJse, Non-pressure Boundary Vendor:
Non-safety supplier per attached list
)
QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement
- 1gnature
-=
Date
/
- The sample ID# shall have a prefix that contains the licensee facility initials celf applicable, please provide an er.planation for your classification system
Docket No. 50-346 License No, h7F-3 Serial No. 1-781 Fastener Testing Data Sheet CSample IDW DB-15-4170, Sample Ouantity - 2 each Fastener
Description:
Nut, Hex 1 1/4" Description of Sample Stock Location:
F-022-F Material Specification as Documented by Licensee Records:
Not specified Hoed Marking (Specification and Manufacturer)-
1 ea. 2H, S. J l ea. g
- Class / Procurement Level:
Non-0/Non-safety General Plant Application (e.g., Pressure Boundary, Structural) l Plant Non-Safety Systems / General Use, Non-pressure Boundary Vondor: Non-Safety Supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature W
+Mse Date
/
4 cThe sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system i
Docket No. 50-346
' License No. NPF-3 Serial No. 1-781 At'achment 1 Attachment'1 Fastener Testing Data Sheet CScmple ids DB-15-4206. Sample Ouantity - 2 each Fostener
Description:
Nut, Max, 1 1/4" Description of Sample Stock Location:
FK-018 Material Specification as Documented by Licensee Records:
Asn! A194 Gr. 2H Head Marking (Specification and Manufacturer): >!anufacture, Grade. Process 2H. J. S
- Class / Procurement Level:
Non-Q/Non-safety General Plant Application (e.g., Pressure Boundary, Structural) Plant ::en-saf ety
- Systems, General Use. Non-pressure Boundary Vendcr:
- en-Safety Supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurarce Supervisor, Procurement Signature Ib Date 7
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system i
_y._
. Docket No. 50-346 License No. S'PF-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ID#
DB-15-4017 Fastener
Description:
7/16"Sc Hex Sut Description of Sample Stock Location:
F-020-B Material Specification as Documented by Licensee Records:
carbon Steel Head Marking (Specification and Manufacturer):
Sone
- Claes/Frecurement Level:
Non a/Nen-safety General Plant Application (e.g., Pressure Boundary, Structural)
Plant Non-Safety systems, General 'Jse/Non-pressure Scundary
end c r : Son-safety supplier per attseed list QA Requirements I= posed on Vendor:
Sene Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature b
Date 58
/
\\
- The sample ID# shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system I
Docket No. 50-346 1.icense No. NPF-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ids DB-15-.016 Fastener
Description:
7/16SF" Hex Sut Description of Sample Stock Location: F-020-B Material Specification as Documented by Licencee Records: carbon Steel Hoad Marking (Specification and Manufacturer): None
- Class / Procurement Level: Son-0/5on-safety General Plant Applicatien (e.g., Pressure Boundary, Structural)
Flan Son-Safety Systems, General Use/Nea-pressure Boundary Vv ndo r !_ ':en-Sa f et:. Sueplier per a:: ached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C.
Beier Engineering Assurance Supervisor, Procurement
/
Signature Ab Date MI $
- The sample Its shall have a prefix that contains the licensee facility initials
- If applicable, please provide an explanation for your classification system
, ~.. -.
Docket No. 50-346 License No, h7F-3 Serial No. 1-781 Fastener Testing Data Sheet
- Sample ids DB-15-4019 Fastener
Description:
9/16" NC Hex Nut Dcocription of Sample Stock Location:
F-020-B Material Specification as Documented by Licencee Records:
carben Steel Hoad Marking (Specification and Manufacturer):
None caClass/ Procurement Level:
Non-0/Nen-safety General Plant Application (e.g., Pressure Boundary, Structural)
Plant Non-Safety Systems, General Use/Non-pressure Boundary Vendor-Non-safety supplier per attached list QA Requirements Imposed on Vendor:
None Licensee Representative:
M. C. Beier Engineering Assurance Supervisor, Procurement Signature Date 55
/
- The sample ID# shall have a prefix that contains the licensee facility initials eaIf applicable, please provide an explanation for your classification system I
i,
Docket No. 50-346 License No. NPF-3 Serial No. 1-781 l
Supplement to Bulletin 87-02 Attachment #1 Suppliers / Manufacturers and Addresses "O" /9m f atv Related Non-O/Nnn-Enfa+v REC Corporation Walter Gogel Company 10 Beach Street 1819 13th Street Mount Vernon, NY 10550 Toledo, OH 43624 All State Fastener Bostwick Braun Co.
P.O.
Box 356 P.O. Box 912 14495 Eight Mile Road Toledo, OH 43692 East Detroit, MI 48021 Freedom fasteners Inc.
Chicago Tube & Iron 30311 Clemene Road 2531 W. 48th Street Westlake. OH 44145 Chicago, IL 60632 Kilbourne Engineering P.O. Box 25344 9226 W.
Flagg Avenue Milwaukee, WI 53225 Hub. Inc.
P.O. Box 125 2146 Flintstone Drive Tucker, GA 30084 i
a Docker No. SD-346 NON SAFETY-RELATED FASTENER DATA
SUMMARY
I,frense Na. NPF-3 Serial No. I-781
{
Attarbrent 2 Mechanical Analysis Chemical Analysis ID I HARDNESS UTS 0.2% YS C
Mn P
S Si Mo Cr DB-15-1790 28Rc 0.34 0.73 0.023 0.015 0.25
<0.01 0.02 DB-15-1784 29Rc 0.36 0.71 0.030 0.028 0.23
<0.01 0.02 DB-15-1797 31Rc 0.32 0.87 0.016 0.015 0.18
<0.01 0.07 DB-15-1219 96Rb 0.097 0.44 0.020 0.022 0.32
<0.01 0.01 DB-15-1789 30Rc 0.34 0.78 0.015 0.024 0.24 0.01 0.07 DB-15-1242 (11A) 83Rb 0.12 0.45 0.027 0.019
<0.01
<0.01 0.04 D8-15-1242 (118) 84Rb 0.12 0.44 0.027 0.019 (J.01
<0.01 0.04 DB-15-1221 (12A) 26Rc 0.32 0.82 0.016 0.017 0.25 0.01 0.10 DB-15-1221 (128) 28Rc 0.33 0.82 0.014 0.019 0.25 0.01 0.10 DB-15-1225 (13A) 33Rc 0.34 0.78 0.021 0.039 0.22 0.02 0.09 DB-15-1225 (138) 33Rc 0.33 0.82 0.020 0.024 0.23 0.02 0.10 DB-15-1604 (14A) 33Rc 0.41 0.80 0.011 0.019 0.24 0.21 0.77
~
DB-15-1604 (14B) 33Rc 0.40 0.83 0.011 0.023 0.25 0.22 0.79 DB-15-1793 (15A)
- 21Rc 0.29 0.82 0.011 0.021 0.20
<0.01 0.03 D8-15-1793 (158)
- 21Rc 0.29 0.79 0.011 0.020 0.19
<0.01 0.03 DB-15-4170 (27)
- 23Rc 0.50 0.83 0.015 0.022 0.25
<0.01 0.04 DB-15-4170 (28)
- S3Rb 0.094 0.47 0.013 0.011 0.08 0.02 0.13 DB-15-4206 (29A) 28Rc 0.50 0.81 0.014 0.020 0.24
<0.01 0.04 D8-15-4206 (29B) 27Rc 0.50 0.81 0.016 0.024 0.26
<0.01 0.04 DB-15-1242 (30A) 95Rb 0.031 0.41 0.025 0.018 0.03
<0.01 0.03 DB-15-1242 (308) 93Rb 0.019 0.54 0.017 0.018 0.07
<0.01 0.05 DB-15-1221 (31A) 91Rb 0.11 0.45 0.021 0.011 0.02
<0.01
<0.01 DB-15-$221 (318) 94Rb 0.11 0.45- 0.021 0.010 0.02
<0.01
<0.01 DB-15-1225 (32A) 92Rb 0.062 0.29 0.012 0.005
<0.01
<0.01
<0.01 DB-15-1225 (328) 91Rb 0.11 0.45 0.021 0.010 0.02
<0.01
<0.01 DB-15-1219 94Rb 0.042 0.40 0.017 0.009 0.01
<0.01 0.02 08-15-4016 93Rb 0.15 0.83 0.007 0.024 0.22
<0.02 0.10 DB-15-4017 98Rb 0.071 0.40 0.020 0.018 0.04 0.02 0.04 08-15-4019 92Rb 0.11 0.43 0.006. 0.009
<0.01
<0.01 0.02 Note:
UTS-ultimate tensile strength; YS-yield strength; C-carbon; Mn-Hanganese; P-Phosphorous; S-Sulfur Si-Silicon; Mo-Molybdenum; Cr-Chromium.
IThe elements listed apply to ASTM A193 B7 or SA193 B7 mater'ial. The elements to be reported for other materials tested, shall conform to those reported in the applicable material specification.
- Properties found out of specification.
L
Attachmont 2
- Docket tio. 50-346 I,frense tio. NPF-3 SAFETY-REI.ATED FASTENER DATA
SUMMARY
- Serial fic. I-7HI i
~
Hechanical Analysis Chemical Analysis ID 8 HARDNESS UTS 0.2% YS C
Mn P
S Si Mo Cr Ni DB-15-1220 32Rc 148500 137100 0.42 0.89 0.009 0.032 0.22 0.21 1.01 DB-15 4302 33Rc 151100 115200 0.44 0.90 0.005 0.026 0.22 0.18 0.98 DB-15-4533 34Rc 153800 141900 0.43 0.89 0.011 0.025 0.23 0.15 1.00 DB-15-4540 28Rc 133100 117000 0.39 0.85 0.010 0.021 0.27 0.13 0.94 DB-15-4314 82Rb 87400 41900 0.056 1.58.0.024 0.016 0.41 0.21 18.31 8.8 DB-15-4306 96Rb 86700 42700 0.053 1.64 0.034 0.026 0.46 0.22 18.43 9.3 DB-15-4273 94Rb 86800 83900 0.21 0.73 0.009 0.018 0.19
<0.01 0.02 DB-15-4256 95Rb 92500 80800 0.20 0.86 0.007 0.023 0.06
<0.01 0.06 4
DB-1-87-1182-00 (10A) 26Rc 137400 0.34 0.74 0.013 0.013 0.25 0.02 0.09 DB-1-87-1182-00 (10B) 27Rc 139200 0.33 0.77 0.013 0.015 0.26 0.02' O.09 l
DB-15-4197 (17A)
- 39Rc 0.43 0.82 0.018 0.029 0.24 0.02 0.10 DB-15-4197 (178)
- 40Rc 0.43 0.78 0.020 0.035 0.22 0.02 0.10 DB-15-4201 92Rb 0.057 0.39 0.014 0.011
<0.01
<0.01 0.04
]
DB-15-4204 28Rc 0.48 0.79 0.008 0.023 0.24
<0.01 0.07 DB-15-4214 23Rc 0.10 0.40 0.036 0.004 0.46 0.02 13.06 DB'- 15-4208 26Rc 0.14 0.71 0.034 0.008 0.33 0.08 11.74 DB-15-4195 (22A) 30Rc 0.42 0.95 0.011 0.029 0.29 0.21 1.00 DB-15-4195 (228) 30Rc 0.42 0.95 0.011 0.029 0.29 0.21 1.00 08-15-4199 (24A) 261tc 0.48 0.70 0.011 0.034 0.26
<0.01 0.04 DB-15-4199 (24B) 27Rc 0.48 0.71 0.012 0.032 0.26
<0.01 0.04 DB-15-4209 31Rc 0.42 0.75 0.011 0.020 0.26 0.01 0.02 DB-15-4259 95Rb 99400 0.12 0.71 0.028 0.039 0.22
<0.01 0.06 1
I 1
I 4
Note: UTS-ultimate tensile strength; YS-yield strength; C-carbon; Mn-Manganese; P-Phosphorous; S-Sulfur
- I Si-Silicon; Mo-Molybdenum; Cr-Chromium; Ni-Nickel.
IThe elements listed apply to ASTM A193 B7 or SA193 B7 material. The elements to be reported for other j
materials tested, shall conform to those reported in the applicable material specification.
- Pronerties fnnnd out of specification.
2
NLD-88-05080 Docket No. 50-346 License No. NPF-3 Serial'No. 1-781 February 16, 1988 i
bec: D. C. Shelton 3080
~L.
F. Storz 2103 P. C. Hildebrandt 3095 T. J. Myers 3065 L. O. Ramsett 3387 M. L. Stewart 5175 S. C. Jain 3105 J. K. Wood 1056 G. A. Gibbs 3085 E. M. Salowitz 1045 R. W. Schrauder 3065 J. E. Silberg J. M. Mallernee 3065 STA 2103 SAR-Up 3065 CNRB 3030 D. Amerine (Centerior)
IND-318 Public Relations 3025 Commitment Management 8175 Records Managenent 3220 J. Strudavant G. Honna V. Watson B. Beyer
?
E. Benson J. Moyers i
M. Beier A. Weedman T. Hiss f
i
...