Extends Invitation to Attend 880523 Meeting in Rockville,Md to Discuss Hilti,Inc 10CFR21 Rept Re Insufficient Recommendation for kwik-bolt Anchor Capacity.Brief Presentation Re Subjs on Encl Meeting Agenda Requested
ML20154F622
Person / Time
Issue date: 05/06/1988
From: Berlinger C
Office of Nuclear Reactor Regulation
To: Hollenbach P
ITW
References
REF-PT21-88 NUDOCS 8805240001
Download: ML20154F622 (3)


Text

v

$ '\\%0 Mr. Paul Hollsnbach MAY 6 1988 ITW/Ramset/ Red Head

-8 P. O. Box 594 Chester, New Jersey 07930 Gentlemen:

The Nuclear Regulatory Commission (NRC) was informed by Hilti, Inc., in accor-dance with 10 CFR Part 21, of recent tests of Hilti Kwik-Bolts that indicate that the previously reconinended minimum edge distance from an anchor bolt to an unsupported concrete edge may be insufficient to develop 100% of the recem-mended anchor capacity. The Hilti test results indicate that Hilti Kwik-Bolts placed at a distance of five anchor bolt diameters from an unsupported edge, as recommended by the Expansion Anchor Manufacturers Institute (EAMI) guidelines, have only 30% of the recommended anchor shear capacity and 78% of the recom-mended tensile capacity. Hilti further indicated, at a meeting with the NRC staff, that the test results are believed to be applicable to other expansion anchor bolts that use the same type of anchor mechanism as Hilti Kwik-Dolts.

The NRC staff feels that the test results indicating a 70% reduction in shear capacity are significant and indicate that there is a potential safety concern that will require further NRC review.

In view of the foregoing, the NRC would i

like to invite representatives of companies that supply bolts or provide bolt installation services to the nuclear industry, such as your company, to attend a meeting where pertinent information could be freely exchanged between meeting participants. The meeting is scheduled for May 23, 1988, at 1:00 p.m. in Conference Room 12-B-11 at the NRC's White Flint Building which is located at 11555 Rockville Pike in Rockville, MD. We are requesting that attendees present a brief presentation, approximately 15 mint'tes, that addresses the subjects listed in the meeting agenda and any other aspects related to this issue which you consider important.

If you plan to attend, or if you have any questions or concerns (such as how to present proprietary information), please contact Jaime Guillen at (301) 492-1153 or Rom Lipinski at (301) 492-0844 before May 16, 1988 Your cooperation on this matter would be greatly appreciated.

Sincerely.

Original Signed By

( arl H. Berlinger Carl H. Berlinger, Chief 8e05240001 e805 g Generic Communications Branch PDR PT21 EMVH Division of Operational Events Assessnent PDR ee Office of Nuclear Reactor Regulation

Enclosures:

1.

Meeting Agenda l

2.

Subjects of Presentations DISTRIBUTION w/ enclosures CERossi, NRR CHBerlinger, NRR JGuillen, NRR A

EJButcher, NRR WDLanning, NRR RLipinski, NRR jv n jl!(1 l

PDR Central Files DCS OGCB R/F. w. n JGuillen R/F DOEA R/F m$EfiT:NRR ESGB C/0GCB:DOEA:NRR OGCR. EA:NRR JGuit en RLipinski CHBerlinger i /s 05/(,,/88 05/ G/88 05/N/88 V

I

D

-MAY 6 588 May 23, 1988 Meeting Agenda Item Speaker Time I.

Introduction NRC 1:00 - 1:15 p.m.

II. Presentations by Manufacturers 1:15 - 3:00 p.m.

Manufacturers

  • III. Discussion / Forum Attendees 3:00 - 4:00 p.m.
  • Invited Manufacturers

~

l Hilti Inc.

Molly Bolt Co.

Ramset/ITW/ Red Head Richmond Screw Anchor Co., Inc.

Tech. Services - Nuclear, Ramset Division - OLIN TRW Assemblies and Fasteners Group, Nelson Stud Division

MAY 61988 c

O Principal Sub.iects of Presentations I.

Describe your anchor products, their use, and the design recommendations provided to your customers.

II. Does the "five diameters" or other edge distance criterion apply to your anchor products? Provide justification for your answer.

III. Describe any tests conducted by your organization that provides additional information regarding shear capacity reduction as a function of edge distance.

IV.

Provide a list of known nuclear power facilities that use your anchor

products, t

V.

Describe your company's fatest recannendations regarding edge distance control and their bases.

VI. Approximately what percentage of your type of anchors are possibly affect-ed by the "edge distance" issue?

VII. Present your perspective of the "edge distance" issue.

.