1 d

e'

(

= """

F7 Log # TXX-88459 1

C File # 10110 r

C 909.2 7UELECTRIC Ref. # 10CFR50.55(e) y]**,'" j*41, May 13, 1988 J

U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION DOCKET NOS. 50-445 AND 50-446 SERVICE WATER SYSTEM WATER HAMMER SDAR: CP-87-130 (SUPPLEMENTAL REPCRT)

Gentlemen:

On January 6, 1988, we notified you via our report logged TXX-88034 of a reportable deficiency involving Service Water System water hammer and column separation at the inlet and outlet of the emergency diesel generator jacket water coolers which can occur subsequent to a service water pump trip.

Our last report logged TXX-88159, dated February 4,1988, provided a schedule for the completion of the corrective action for Units 1 and 2.

The purpose of this supplemental report is to status the implementation of corrective actions for this deficiency.

The installation of vacuum breakers in the Unit 1 emergency diesel generator jacket water coolers has been rescheduled for completion by September 2, 1988.

The completion schedule for Unit 2 will be prior to the start of the primary system cold hydrostatic test.

Very truly yours, b.b-W. G. Counsil By:

D. R. Woodlan Docket Licensing Manager MCP/grr c-Mr. R. C. Martin, Region IV Resident Inspectors, CPSES (3) 8805180099 880513 PDR ADOCK 05000445 h

S DCD d

i o 400 North ouve street LB81 Dallas, Texas 73201

- - - - - - - - - - - - - - - - - - -