s

==

F7 Log # TXX-88457 1

=

File # 10110 r

C 910.4 7t/ ELECTRIC Ref. # 10CFR50.55(e)

[f'*,'",t,J*d, May 13, 1988 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION DOCKET NOS. 50-445 AND 50-446 CONDENSATE STORAGE TANK OVERPPESSURIZATION SDAR: CP-87-28 (SUPPLEMENTAL REPORT)

Gentlemen:

On December 2,1987, we notified you by our letter logged TXX-6992 of a deficiency involving the ca)acity of the condensate storage tank CST),which we determined to be reporta)le under the orovisions of 10CFR50.55 e). Our most recent report on this issue, logged TXX-88272, was submitted on March 4,1988. This report is submitted to update the corrective action completion schedule for this issue.

Actions taken to resolve this deficiency (described in TXX-6992) consist of adding a safety-related control feature for the CST level transmitters which isolates CST makeup using redundant safety grade valves when the CST high level setpoint is reached.

Corrective actions for Unit I have been rescheduled for completion by July 25, 1988.

The completion schedule for Unit 2 will be prior to Unit 2 hot functional testing.

Very truly yours, d{oM W. G. Counsil By:

D. R. Woodlan Docket Licensing flanager MCP/grr c-Mr. R. D. Martin, Region IV Resident inspectors, CPSES (3) 8805180091 880513 PDR ADOCK 05000445 i D S

DCD 400 Nottit Olist Street LB 81 Dallas, Teses 73201 1