This table is sutunitted to fusfill requirements of Part I.B.6 and Pcrt !!!.0 fyo Farley Nuclear Plant AL 0024619 us D f>
CO Permit Analytical Cause of Test Period of Noncornpliance OFJ Discharge Point Parameter Limit Value Noncompilance Corrective Measures Date Began Ended O G)
Once Through Total Residual 0.2 mg/l 0.4 mg/l Occurred during a Procedures were 01/06/88 01/06/88 01/06/88 0 0) Cooling Water Chlorine (Daily Average routine, chlorine changed to provide (0825)
(0845)
(D5N 002)
Limit 0.2 mg/1) dioxide (C102) treat-guidance for an ex-
[20 minutes]
ogg ment period. The tended sampling and cots C102 system was testing program to OW inrnediately checked determine the cause U$
after the occurrence should the anornaly and all components recur.
were operating correctly. An ex-tensive evaluation of the C102 system was performed and no definitive causes could be determined.
%A N\\
j
Af atema Power Com,0.7,ny NT-88-0206 0*
'c 600 North 18th Street Post Of fica Box 2641 o
Birmingham. Alabama 35291-0400 Telephone 205 2'0-1835 m
R. P. Mc Donald Ser. or Vece Pres. dent
/Mahama PDWCT ne scuvo escrc s,vem May 6, 1988 Docket Nos. 50-348 50-364 U. S. Nuclear Regulatory Ccmission Attention: Document Control Desk Washington, D. C. 20555 Joseph M. Farley Nuclear Plant - Units 1 and 2 Quarterly NPDES Ncncompliance Report Gentlemen:
Enclosed in accordance with the Joseph M. rarley Nuclear Plant Technical Spacifications, Appendix B, Section 3.2, is a summary of NPDES noncompliances for the first quarter of 1988 as transmitted to the Alabama Department of Environmental Management.
Should you have any questions or comments, please advise, lh Yours ve
,truly, kud t'
R. P. Mcdonald RPVJAM:e:rb Attachment cc:
Mr. W. H. Bradford (w/ attachment)
Dr. J. N. Grace (w/ attachment)
Mr. L. B. Long (w/ attachment)
Mr. E. A. Reeves (w/ attachment) o q
-.