Responds to NRC Re Violations Noted in Insp Rept 50-271/88-04.Corrective Actions:Emergency Lights Provided in Control Room on 880209 & Fire Area RB-5 Reviewed & Determined That No Addl Emergency Lighting Required
ML20153H622
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 05/06/1988
From: Murphy W
VERMONT YANKEE NUCLEAR POWER CORP.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
FVY-88-34, NUDOCS 8805130078
Download: ML20153H622 (2)


Text

.

hERMONT YANKEE NUCLEAR POWER CORPORATION FVY 88-34 RD 5, Box 169, Ferry Road, Brattleboro, VT 05301 yo ENGINEERING OFFICE y

1671 WORCESTER ROAD FRAMINGHAM, M ASS ACHUSETTS 01701 a

TELEPHONE 61F-472 4100 May 6, 1988 U.S. Nuclear Regulatory Comairsion Washington, D.C.

20555 Attn:

Document Control Center

References:

a)

License No. DPR-28 (Docket No. 50-271) b)

Letter, USNRC to VYNPC, NVY 88-054, Inspection No.

50-271/88-04), dated 4/6/88 c)

Letter, USNRC to VYNPC, Inspection Report 88-03, dated 4/1/88 d)

Letter, USNRC to VYNPC, Inspection Report 88-22, dated 12/21/84

Dear Sir:

Subject:

Response to Inspection 88-04, Notice of Violation During a NRC inspection the week of February 8, 1988, a violation of NRC requirements was identified (Reference b)].

The following information is in response to that violation.

VIOLATION "As a result of the 10 CFR 50, Appendix R inspection conducted on February 8-11, 1988, and in accordance with the ' General Statement of Policy and Procedure for NRC Enforcement Actions,'

10 CFR Part 2, Appendix C (Enforcement Policy 1987), the following violation was identified:

10 CFR SO, Appendix R,Section III.J, requires that emergency lighting units with at least an eight-hour battery power supply shall be provided in all areas needed for operation of safe shut-down equipment and in access and egress routes thereto.

Contrary to the above, as of February 8, 1988, emergency lighting units with at least an eight-hour battery power supply were not provided in the following safe shutdown areas and access and er,ress routes:

The Control Room The Northeast Section of the Torus Ce.twalk Fire Area RB-5 Section This is a Severity Level IV Violation (Supplement I)."

\\

8805130078 880506

}

PDR ADOCK 05000271 Q

DCD

g-VERMONT YANKEE NUCLEAR POWER CORPORATION U.S. Nuclear Regulatory Commission May 6, 1988 Page 2

RESPONSE

As identified in the inspection report, emergency eight-hour battery supplied lights were provided in the Control Room on February 9, 1988, prior to the inspectors' exit from Vermont Yankee.

The Northeast Section of the Torus Catwalk does contain safe shutdown equipment. However, this equipment is not required or operated until after the Emergeticy Diesel Generator (s) start. Since power for the Torus Catwalk lights is ultimately provided by the Diesel Generators, it was determined that no addi-tional emergency lights are necessary for this area. As indicated in the report, this technical justification was presented to your personnel during the inspec-tion. Vermont Yankee will submit a formal request for relief from the require-ments of 10 CFR 50, Appendix R, Section III.J for this area by June 1988.

Fire Area RB-5 was reviewed, and it was again determined that no additional emergency lighting is required for this area.

This determination was made following a detailed review of our design records and your Inspection Report Nos. 88-03 and 84-22.

As identified in NRC Report No. 84-22, normal lighting in this area was shut off and emergency lighting was demonstrated adequately by Vermont Yankee to NRC personnel.

Subsequent to the inspection, alternate shutdown and emergency lighting design change packages previously installed were reviewed.

In addition, a walk-down of those areas identified as necessary to support safe shutdown activities, including ingress and egress, were also performed. No further areas of concern, other than those identified during the inspection, were identified. Therefore, pending approval of our exemption request to be submitted by June 1988, Vermont Yankee is in full compliance with the issues identified in the subject Notice of Violation.

We trust the above information adequately addresses your concerns.

However, should you have any questions or desire further information, please do not hesitate to contact us.

Very truly yours, VERMONT YANKEE NUCLEAR POWER CORPORATION 1

Warren P. Murphy Vice President and Manager of Operations l

l

/dm l

cc:

W.V. Johnston, Region I USNRC Region I, Regional Administrator USHRC Resident Inspector, VYNPC l

-