ML20153H092

From kanterella
Jump to navigation Jump to search
Suggests That Region IV Handle Problems W/Station Svc Water Sys.Problems Involve Isolated Bubbling of Placite Internal Liner & Pipe Erosion in Piping to Component Cooling Water HXs as Result of Water Turbulence
ML20153H092
Person / Time
Site: Comanche Peak 
Issue date: 02/19/1986
From: Noonan V
Office of Nuclear Reactor Regulation
To: Westerman T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
NUDOCS 8602280608
Download: ML20153H092 (2)


Text

-

YY r/

y FEU 19 M l

MEMORANDUM FOR:

T. Westerman, Chief Comanche Peak Group, RIV 7

y FROM:

Vincent S. Noonan, Directoe PWR Project Directorate #5 Division of PWR Licensing-A

/

SUBJECT:

COMANCHE PEAK - STATION SERVICE SYSTEM Yb Texas Utilities Generating Company management has notified us that they are experiencing problems associated with the Station Service Water System.

Since this system has been turned over to operations for approximately six years and has been operational for this interval of time, we believe that it should be dispositioned by your group rather than be handled as a CPRT issue.

The problems identified to date with this system involve:

1.

Isolated " bubbling" of the Placite internal piping liner.

2.

Pipe erosion in the piping to the Corponent Cooling Water Heat Exchangers as a result of water turbulence.

3.

Instrument pipe weld failure at the pump discharge.

4.

Diesel Generator jacket cooler erosion. -

5.

Diesel Generator jacket cooler piping water henr.er.

~

6.

Pinhole leak on service water inlet piping to Safety Injection Pump leak oil cooler.

7.

Other problems currently being identified by TUGC0 personnel.

Please let us know if you will need any assistance from NRR, and please keep us informed on this matter.

.y p% 2] o M So g 45 Vincent S. floonan, Director A

PDM PWR Project Directorate #5 Division of PWR Licensing-A cc:

C. Trannell, NRP A. Vietti-Cook R. Martin, RIV J. Barnes, RIV Distribution:

Docke or Gntral File PDd5 Reading File P. Keshishian NRC R

T. Novak L c 1 PDR M. Rushbrook m

P J5 PD#5 ramell VSNo tan AkfrL A n

paasegk UNITED STATES

+

8 NUCLEAR REGULATORY COMMISSION o

t a

wasHiNotom. o. c. 20sss

  • s

/

b 19 y MEMORANDUM FOR:

T. Westerman, Chief Comanche Peak Group, RIV FROM:

Vincent S. Noonan, Director PWR Project Directorate #5 Division of PWR Licensing-A

SUBJECT:

COMANCHE PEAK - STATION SERVICE SYSTEM Texas Utilities Generating Company management has notified us that they are experiencing problems associated ith the Station Service Water System.

Since this system has been turned over to operations for approximately six years and has been operational for this interval of time, we believe

  • hat it should be dispositioned by your group rather than be handled as a t

CPRT issue.

The problems identified to date with this system involve:

1.

Isolated " bubbling" of the Placite internal piping liner.

2.

Pipe erosion in the piping to the Component Cooling Water Heat Exchangers as a result of water turbulence.

l 3.

Instrument pipe weld failure at the pump discharge.

4.

Diesel Generator jacket cooler erosion.

5.

Diesel Generator jacket cooler piping water hamer.

6.

Pinhole leak on service water inlet piping to Safety Injectiol Pump leak oil cooler.

7.

Other problems currently being identified by TUGC0 personnel.

Please let us know if you will need any assistance from NRR, and please keep

~

us informed on this matter.

l m

ff M.

o an. Director WR Proje t Directorate #5 Division of PWR Licensing-A cc:

C. Tramell, NRR A. Vietti-Cook R. Martin, RIV

3. Barnes, RIV

__