ML20151X710

From kanterella
Jump to navigation Jump to search
Forwards Implementation Repts on Reactor Vessel Level Monitoring Sys & Core Exit Thermocouples,Per 870501 Commitment
ML20151X710
Person / Time
Site: Calvert Cliffs 
Issue date: 04/27/1988
From: Tiernan J
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.F.2, TASK-TM NUDOCS 8805040229
Download: ML20151X710 (3)


Text

, _ _ _

..-i p N

p' l

B ALTIMORE CAS AND ELECTRIC CHARLES CENTER + P. O. BOX 1475 BALTIMORE. MARYLAND 21203 JostPH A.TitRNAN VH:t Passiotat NucktAn eNtmov April 27,1988 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

Document Control Desk

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit No.1; Docket No. 50-317 Implementation Reports on inadequate Core Cooling Instrumentation for Unit 1. NUREG-0737. ftem II.F.2

REFERENCE:

(a) Letter from Mr, J. A. Tiernan (BG&E) to NRC Document Control Desk, i

dated May 1,

1987, Reactor Vessel Level Monitoring System

!m*plementation of inadequate Core Cooling Instrumentation Gentlemen:

I Reference (a) provided the implementation Report for the reactor vessel level monitoring system (RVLMS) on Calvert Cliffs Unit 2. It also contained a commitment to provide Unit i RVLMS and core exit thermocouples (CETs) Implementation Reports by Mar 1,1988. Those implementation Reports are Attachments A and B.

i Should you have any further questions regarding this matter, we will be pleased to discuss them with you.

Very truly yours, JAT/DBO/ dim l

Attachments l.$ p cc:

D. A, Brune, Esquire l

O i

J. E.

Silberg, Esquire R. A.Capra, NRC l j i

S. A.McNeil, NRC i

W. T. Russell, NRC l

D. C, Trimb!(, NRC 8805040229 880417 PDR ADOCK 05000317 P

DCD l

... - 'i e

l A1TACHMENT A IMPLEMENTATION REPORT REACTOR VESSEL LEVEL MONITORING SYSTEM, UNIT 1 Status The system was installed during the fall 1986 refueling outage. Functional testing and calibration are complete. Test results are available for inspection.

Functional Test Results The system performs in accordance with design expectations and within design error tolerances.

Deviations of As-Built System From Desian None Technical Soecifications 10,1987.gd the RVLMS to UnitI and 2 Technical Specifications was An amendment request to a submitted on July Procedures The Emergency Operating Procedures (EOPs) have been revised and now include the ItVLMS.

The EOPs were revised using CEN-152, Combustion Engineering Emergency Procedure Guidelines, and our Procedures Generations Package. Operators have been trained on the system and EOPs.

i I

Letter from J. A. Tiernan (BG&E) to NRC Document Control Desk, dated July 10,1987, Request for Amendment

e*

ATTAC11 MENT B IMPLEMENTATION REPORT CORE EXIT TIIERMOCOUPLES, UNIT I Status The system was installed during the fall 1986 refueling outage. Functional testing and calibration are complete. Test results are available for inspection. The installation of fully qualified Incore Instrumentation (ICI) strings is to begin with the spring 1988, cycle 10 reload of Unit 1. Sufficient ICI's will V replaced to ensure a minimum of four completely qualified CET channels per core quadrant. Testing will take place during startup. Future replacement of ICI strings with fully qualified strings will result ultimately in the full qualification of all 45 CET channels.

Functional Test Results The system performs in accordance with design expectations and within design error tolerances.

peviations of As-Built System From Desian None Technical Soecifications An amendment request to add the CETs to Unit i Technical Specifications will be submitted shortly after startup from the current refuelin;; outage.

Procedures The Emergency Operating Procedures (EOPs) have been revised and now include the CETs.

The EOPs were revised using CEN-152, Combustion Engineering Emergency Procedure Guidelines, and our Procedures Generations Package. Operators have been trained on the system and EOPs.