NPDES Noncompliance Notification:On 880725,total Residual Chlorine/Total Residual Halogen of 485 Lb/Day Observed. Caused by Mechanical Failure of Oxident Feed Pump.Oxident Feed Pump Will Be Repaired to Correct Check Valve Problem
ML20151X030
Person / Time
Site: Quad Cities  Constellation icon.png
Issue date: 08/12/1988
From: Bax R
COMMONWEALTH EDISON CO.
To:
ENVIRONMENTAL PROTECTION AGENCY, ILLINOIS, STATE OF
References
RLB-88-269, NUDOCS 8808250200
Download: ML20151X030 (2)


Text

_ _ _ . . _ _ _

o PRIORITY ROUTIigg lim um ,

l Quad Cities Nuclear Power Station r- [--

'O Commonwealth Edison M'-

22710 206 Avenue North . ,7 -

Corcova, Illinole $1242 f- A -

~Y ~

To'ophone 309/65+2241 (

gZ ma , _

?

RLB-88-269

)

August 12, 1988 Illinois Environmental Protection Agency Division of Water Pollution Control Compliance Management Unit 2200 Churchill Road Springfield, IL 62706 U.S. Environmental Protection Agency Region V, Enforcement Division Attention: Chief, Compliance Unit 230 South Dearborn Street Chicago, IL 60604

SUBJECT:

NPDES Non-Compliances for Quad-Citiec Generating Station IL-0005037 Dear Sirst In accordance with Standard Condition 12 we wish to submit the following notice of non-compliances:

DISCIIARGE: 006 & 007 Open Cycle Diffusers PARAMETER AND PERMIT LIMIT: Total Residual Chlorine / Total Residual Halogen Lead Limits Daily Max 400.5 lbs/ day.

NON-COMPLIANCE AND DATE: Total Residual Chlorine / Total Residual Halogen was 485 lbs/ day on 7/25/88.

CAUSE: The cause of the problem has been attributed to a mechanical failure of the oxident feed pump.

An internal check valve in the pump failed and allowed the oxident to be injected at ebout three times the normal dosage.

CORRECTIVE ACTION: The sodium hypochlorite tank was isolated as soon as the increased flow was discovered. The maximum time at the increased flow was 3 1/2 hours or a loss of an additional 1350 gallons of sodium hypochlorite. g p

SOS $ SS 84 A'J G 15 194 lg

{SO

_-g - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - -

j!'

,.u .
k. -

The oxident feed pump will be repaired to correct the check valve problem. After the pump has been repaired, the pump feed rate will be measured to ensure the correct oxident flow rate.

The system is shut down and-will not be operated until the check valve is repaired and tested.

If_there are any questions, please call Ray Moore of my

~

staff at'309-654-2241, extension 2731.

Sincerely, T

R.' L. Bax Station Manager Quad-Cities

-RLB/RM/psb cca B. Davis, NRC Director of Water Quality, Environmental Affairs l