ML20151V190

From kanterella
Jump to navigation Jump to search
Deficiency Rept Re non-water Tight Penetration Seals.Test Rig Constructed to Simulate Typical Upper Cable Spreading Room Configuration & Sealants Verified to Provide Waterproof Seal.Next Rept Will Be Submitted by 881020
ML20151V190
Person / Time
Site: Vogtle 
Issue date: 08/16/1988
From: Rice P
GEORGIA POWER CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
GN-1478, NUDOCS 8808220179
Download: ML20151V190 (1)


Text

Mn?a%"

Waynesboro Ge/g a 30830 Telephone 404 N404L E. tens.on 3413 434 724 H14. Evers m 3413 L

Gwrgia Power R (1 Ric.

gp"j'jt August 16, 1988 c, a, g,,.. m,s a United States Nuclear Regulatory Commission ATTN:

Document Control Desk File:

X7BG03-M145 Washington, D. C.

20555 Log: GN-1478

Reference:

Vogtle Electric Generating Plant - Unit 2 Non-Water Tight Penetration Seals (M145)

GPC letter GN-1468 dated July 6, 1988 In previous correspondence Georgia Power Company notified the NRC of a potentially reportable condition under 10CFR50.55(e) involving Unit 2 penetration seals which were found to be not watertight.

Our investigation into this concern is not yet complete.

The penetrations which must be sealed have been identified and procedures and drawings are being prepared for the repair of these penetrations.

Two materials have been selected to fill the small leak paths between the foam seal and the structure, and between the cables in a bundle.

A test rig was constructed to simulate a typical upper cable spreading room configuration and these sealants were verified to provide a waterproof seal.

A second test rig was corstructed to simulate a typical plant configuration.

Testing in this rig is scheduled to be complete by the end of August.

A final report on this issue for Unit 2 is scheduled to be submitted by October 20, 1988.

This condition was reported for Unit 1 via Licensee Event Report (LER)88-016.

This correspondence contains no proprietary infonnation and may be placed in the NRC Public Document Room.

, s '%

P. D. Rice POR/sem xc:

USNRC - Region II Suite 2900 l

101 Phrietta Street, N. W.

Atlanta, GA 30323 i

H. G. Baker, Jr.

D. R. Altman C. W. Hayes J. P. Kane J. A. Bailey R. W. McManus R. H. Pinson G. Bockhold, Jr.

Sr. Resident (NRC)

E. D. Groover G. R. Frederick D. H. Smith (OPC)

C. T. Moo-e J. E. Swartzwelder J. E. Joiner (TSLA) l R. A. Thoeis A. B. Gallant NORMS 8008220179 800816O l

1 0 ADOCK050g44 PDR S

i