3lQ 6MiAjatA l '/
4 lsQq.s
~ ' T -
O 4
PRELIMINARY NOTIFICATION June 15, 1977 PRELIMINARY NOTIFICATION cQF EVENT OR UNUSUAL' OCCURRENCE--PNO-77-10 This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest sienificance. The infor: nation
' presented is as initially received without ver_ification or evaluation
_and is basically all that is known by IE staff on t.his date.
Facility: Millstone Point Unit No. 1 (50-245)
Northeast Nuclear Energy Company Waterford, Connecticut Subj ect:
THROUGHW ALL CRACK, RECIRCULATION LOOP DRAIN LINE Ddring a drywell inspection on June 14, with the reactor pressure a.t 500 psig, a through-wall crack was visually observed on a two-inch recirculation loop drain line. The drain line is located on the suction side of the A recirculation pump. The crack was located in the heat affected zone of the pipe at a socket weld to a 90 elbow. Prior to shutdown, unidentified drywell leakage was below that allowed by the Technical Specifications.
Repairs are in progress. The licensee plans to conduct metallographic analysis'of the crack.
Media interest' is expected because of a high sensitivity to events at this plant. The State of Connecticut is informed. A press release is not ' planned.
NRC, Region I, (Philadelphia) received notification of this occurrence by phone from the licensee at 2:00 PM, 6/15.
C$ntact: GKlinglar, IE x27451 FNolan, IE x27451 JSniezek, IE x27451 TransmittedHStk.'.Kammerer,CA Distribution:
Chairman Rowden C. C G. F. Murphy, JCAE
' Commissioner Kennedy S. J. Chilk, SECY H. H. Whiteside, SCNR Comm!.esioner Gilinsky H. R. Myers, HC,E,E Transmitted: MNBBt/!l.d P Bldg 3W SS Bldg Y/.If L. V. Gossick, EDO '
E. G. Case, NRR C. V. Smith, NMSS S. H. Hanauer, EDO J. A. Harris, PA W. G. Mcdonald, MIPC Luge (MAIL)
E. Vol Region [genau,JE'f/3 27[
3 R. G. Ryan, OSP T. J. McTiernan, OIA H. K. Shapar, ELD PRELIMINARY OTIFICATION o
1 2
_. m I
9009110099 770615 PDR 18cE
{.
PNO-77-103 PDR k
j.
-