ML20151Q860
| ML20151Q860 | |
| Person / Time | |
|---|---|
| Issue date: | 08/01/1988 |
| From: | Grimes B Office of Nuclear Reactor Regulation |
| To: | TEXAS, STATE OF |
| References | |
| IEIN-88-046, IEIN-88-46, NUDOCS 8808110313 | |
| Download: ML20151Q860 (2) | |
Text
'
A*"4 9[o, UNITED STATES 3 "., j y
NUCLEAR REGULATORY COMMISSION 3 v, 5.'-
C WASHINGTON, D. C. 20555 g
%.% y
...+
g 01 M Texas Department of Corrections Coffiel Metal Fab.
Route 1, Box 150 Tennessee Colony, TX 75861
Dear Sir:
SUBJECT:
POTENTIALLY DEFECTIVE REFURBISHED CIRCUIT BREAKERS The enclosed Nuclear Regulatory Comission (NRC) Information Notice (IN) 88-46 describes the circumstances under whien defective refurbished electrical equip-ment may have been supplied to nuclear power plants.
Our continuing investiga-tion of the five circuit breaker companies identified in the IN shows that the companies have shipped breakers to a number of government facilities and agencies.
Our review of a sample of invoices indicates that generally the breakers are sold to a distributor, and it was only the occasional shipment direct to the end user that permitted us to identify the final government destination.
I have enclosed a copy of an invoice that identifies your agency as the customer.
These documents represent our review of a selection of records spanning the last two or three years from all of the companies.
As other records are reviewed, we will provide any additional information that comes to light.
However, since some of the companies have been in business for as many as 30 years, a full historical records search will not be possible.
The five California companies appear to sell surplus new as well as refurbished brea kers. However, their refurbished equipment may be shipped in containers resembling original manufacturer containers.
If there is any additional information you require, please call me or Mr. Walter Haass at (301) 492-3219.
Si nce' rely,
s
^
w d-~
Brian K. Grines, Director Division of Redctor Inspection and Safeguards Office of Nuclear keactor Regulation
Enclosures:
h
,9 l ;
1.
NRC Bulletin (IN) 88-46
)ss 2.
Invoices /Ordetrs 40 i
e
./
8808110313 880801 '
PDR DRG NRRB PNU l
4
k 4
ji
- g' o
Texas Department of Corrections AUG 01.1988 i
DISTRIBUTION:w/o Enclosures JTaylor JSniezek-TMartin BGrimes JStone PDR
- Centra 15 Files'
- 1,
- DRIS^Redding ~(w/ Enclosures)
.~
4 1
1 1
i i
i 4
4
- See previous page f r o urrences.
DRIS:hRR r
JStone:tt*
ad
- 1 07/22/88
/23/88 i
d'E I; l
i i
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C.
20555 July 8, 1988 NRC INFORMATICN NOTICE NO. 88-46: LICENSEE REPORT OF DEFECT!YE REFURBISH CIRCUIT BREAVERS Addressees:
All holders of operating licenses or construction permits for nuclear power reactors.
Puroose:
This information notice is being provided to alert addressees of licensee reported information that defective refurbished electrical equipment, such as circuit breakers (CBs), may have been supplied to nuclear power plants.
It is expected that recipients will review this information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems.
However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required.
Description of Circumstances:
Pacific Gas and Electric Compan purchase order for 30 new, non y (PG&E) has informed NRC that it placed a safety-related, molded-case, KHL 36125-type i
CBs manufactured by the Square D Company (Square D) with a local electrical distributor.
These CBs were intended for use in non-safety-related applica-tions at PG&E's Diablo Canyon Nuclear Power Plant.
According to PG&E, the distributor in turn placed the order with a local sup-plier who bid the lowest price and promised the quickest delivery.
The CBs were delivered directly to the Diablo Canyon plant by the supplier; the dis-tributor did not have an opportunity to inspect the CBs. Square D, aware of f
i the purchase order, questioned its failure to receive an order for the unique i
l vintage KHL 36125-type CBs.
With PG&E's permission, Square D inspected the l
CBs and determined that PG&E had been given refurbished, rather than new, CBs.
Souare D tested and performed detailed examinations of the CBs, and the results reported by PGIE follow.
A.
Physical Examination The yellow side labels used on the CBs were suspect in that the CB model numbers were typed on the labels whereas authentic labels are preprinted.
The CBs departed from normal appearance in other respects as well.
b f'
--CB070sDuut f
IN 88-46 July B, 1980 Page 2 of 3 The individual CB cases and each of the CB components appeared to be Square D products; however, the individual CBs incorporated components of different years of manufacture.
Each CB bore evidence of having been opened and reassembled.
B.
Electric Testing Square D subjected the CBs to five electrical tests.
None of the CBs complied with Square D or Underwriters' Laboratory (UL) specifications for all of the tests, and several of the CBs were out of tolerance on each of the tests. At least four of the CBs failed to trip under circum-stances in which they are designed to trip.
Discussion:
In the past, there have been instances in which licensees purchased comercial-grade components, such as CRs, relays, trip units, and other electrical compo-ntnts, from electrical distributors and have received components that did not meet the original purchase order requirements.
NRC has received additional information indicating that the problem of surplus or defective refurbished CBs may also apply to CBs sold under other manufacturers' names (e.g., General Electric, Westinghouse, ITE, Cutler Hamer, and Sylvania).
The electrical suppliers involved in refurbishing and sales of circuit breakers, including the Diablo Canyon, Square D circuit breakers, apparently include five California corporations.
These companies are (1) General Circuit Breaker &
Electric Supply, Inc., (2) HLC Electric Supply Co., Inc., (3) Pencon Inter-national, Inc., doin California Breakers,g business as General Magnetics / Electric Wholesale, (4)
Inc., and (5) Anti-Theft Systens, Inc., doing business as ATS Circuit Breakers and as AC Circuit Breaker-Electrical Supply.
NRC has an investigation and vendor inspection in progress at the above compa-On the basis of the information developed to date, a preliminary list nies.
of customers of the five companies including a list of nuclear utilities (where available) is provided in Attachment 1.
equipment nanufacturers whose names may have been used on surplus or ref equipment sold as new equipment.
The information included in Attachments 1 and 2 is only prelininary and is provided to assist licensees in reviewing the potential of having procured suspect electrical equipment at their facilities.
Licensees are reminded of the requirements to ensure that procured itens meet the relevant specificatiens and codes and are suitable for the intended appli-l cation.
Licensees should consider, as a matter of prudence, the need to inquire n' and to verify with their authorized distributors the sources of procured materials, equipment, and components.
Licensees may meet these re by effectively implementing their quality assurance (QA) programs,quirements particularly in the areas of vendor evaluations, vendor surveillances, receipt inspection, bench tests, and post-installation tests.
IN 88-46 July 8, 193P Page 3 of 3 NRC is gathering additional information to detemine what further actions are necessary. The primary purpose of this infomation notice is to alert addressees of the situation as soon as possible.
The NRC is considering issuing a bulletin to followup on this infomation notice when the NRC has sufficient information to define requirements, ho specific action or written response is required by this infomation notice.
If you have any questions about this matter, please contact one of the techni-cal contacts listed below or the Regional Administrator of the appropriate regional office.
b 4*
CharTes F., Rossi, Director Division of Operational Events Assessment Office of Nuclear Reactor Regulation Technical Contacts:
K. R. Naidu, NRR (301) 492-0980 Jaime Guillen, NRR (301) 492-1170 Attachments:
1.
Preliminary List of Custoners (Intermediate Suppliers) of Suspect Electrical Equipment 2.
Preliminary List of Original Equipment Manufacturers Yhose Names May Have Beer Used on Surplus or Pefurbished Equioment Sold as New Equipment 3.
List of Recently Issued NRC Infomation Notices i
1 l
i Attachment I IN 88-46 July 8, 19PP Page 1 of 2 PREllMINARY LIST OF CUSTOMERS (INTERMEDIATE SL'PPLIERS) 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utility fif available_1 Westinghouse Electric St. Louis, M0; Boston, MA; Supply Co. (WESCO)
Boise, ID; Atlanta, GA; Charleston, SC; Panama FL; Santa Clara, CA; Fresno, CA; Sacramento, CA; Shreveport. LA; Green Bay, WI; Elk Creek, iL; Albuquerque, NM; Mobile, AL; Ft. Worth, TX; Baton Rouge, LA; Binningham, AL; East Hartford, CT; Kokomo, IN; Jackson, MS; Milwaukee, W1; Beaumont, TX; Nashville, TN; Skelton, WV; Albany, Ni; Hartford, CT; Portland, ME; St. Paul, MN; Minneapolis, MN; other locations Power Conversion Huntington Beach, CA Rockwell International Los Angeles, CA Arkansas Power and Light little Rock, AP AND Southern California San Clemente, CA; SONGS Edison other locations Phoenix Electric Phoenix, A2 Rensenhouse Electric Topeka, r,5 Breaker and Control Houston, TX
, General Electric Company Baltimore, MD; Houston, TX; Landover, MD; Chantilly, VA; Emeryville, CA; Elmhust, IL Southern Electric Alexandria, LA Supply Company Cleveland Electric Company
= - - - -. _
4 IN 88-46 July 8, 1988 Page 2 of ?
PREllMINARY LIST OF CUSTDMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL E0lllPMENT Organization Location Nuclear Utility (if available)
Stokley Enterprises Norfolk, VA Taylor Elart-d
'ompany Portland, OR Graybar Ventura, CA; Atlanta, GA Hughes Aircre't El Segundo, CA Houstor. Electric Houston, TX Distribution Company i
ITE Electrical Products Atlanta, GA; Knoxville, TN Knudson Corporation Los Angeles, CA i
Georgia Power Company Milledgeville, GA l
1
- ~ ~ ~ ~ -
~ ~
IN 88-46 July 8, 1988 Page 1 of 2 PRELIMINARY LIST OF ORIGINAL EQUIPMENT M/NUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SL'RPLUS OR REFURBISHED E0VIPMENT SOLD AS NEW EQUIPMENT Manufacturer Mecel Number Equipment Descriptior.
Square 0 B19.5; B22 Heater for ove-load relay General Electric 12HGA11552 Auxiliary rolay Exide Company NX400 Spectro Inc.
V00014 Mercury lamps Bussman Company REN15 15-amp 250-V fuse Bussman Conpany N05-30 30-amp 600-V fuse (unknown)
FSN 5925-628-0641 Circuit breaker Westinghcuse 0B-50 Trip unit Westinghouse DB-25 400-amp circuit breaker Westinghouse HKB315GT Trip unit Westinghouse KB3250F Freme Westinghouse FB3020 Circuit breaker Westinghouse FB3070 Circuit breaker Westinghouse FB3050 Circuit breaker Westinghouse EHo3040 Circuit breaker Westinghouse EHB3025 Circuit breaker l
Vestinghouse LBB3125 Circuit breaker Bestinchcuse HKA31250 Trip unit Vestinghouso JA3200 Circuit breaker Wutinghouse EHB2100 Circuit breaker i
Uestinchouse CAH3200 Circuit breaker
IN 88-46 July 8, 198P Page 2 of 2 PREllMINARY LIST OF ORIGINAL EQUIPMENT MANUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SURPLUS OR REFURBISHED E0VIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number Equipment Description Westinghouse 225h Navy trip units ITE EF-3B100 100-amp circuit breaker General Electric AK-2-75-3 Circuit breaker General Electric AK-2 Circuit brsaker General Electric AK-1-50 Circuit breaker General Electric AK-1-75 Circuit breaker General Electric B; TD0; TFJ Circuit breakers General Electric TCVVFS Circuit breaker ITE ET; KA Circuit breakers Cutler Hanmer Circuit breakers Zinsco/Sylvania Circuit breakers Bryant Circuit breakers
~
Murry Circuit breakers Federal Pacific Electric Circuit breakers Company
IN 88-46 July 8, 1988 Page 1 of 1 LIST OF RECENTLY IS$UED N1C INFOR!!ATION NOTICES Inforr:a t ion Date of Notice No.
Subject issuance
Sued to 88-45 Problems In Protective 7/7/88 All holders of OLs Relay ~and Circui+
or cps for nuclear Breaker Coordination power reactors.
88-44 Mechanical Binding of 6/24/88 All holders of OLs Spring Release Device or cps for nuclear in Westinghouse Type power reactors.
D5-416 Circuit Breakers 88-43 Solenoid Yalve Problems 6/23/88 All holders of OLs or cps for nuclear power reactors.
88-42 Circuit Breaker Failures 6/23/88 All holders of OLs Due to Loose Charging or cps for nuclear Spring Motor Founting Bcits power reactors.
88-41 Physical Protection 6/22/88 All holders of OLs Weaknesses identified or cps for nuclear Through Regulatory Ef-power reactors.
fectiveness Reviews (RERsl 88-40 Examiners' Handbook for 6/22/88 All holders of OLs Developing Operator or cps for nuclear Licensing Examinations power reactors.
88-39 LaSalle Unit 2 Loss of 6/15/8P All holders of Ols Recirculation Pumps With or cps for BWRs.
Power Oscillation Event 88-38 Failure of Undervoltage 6/15/88 All holders of OLs Trip Attachment on General or cps for nuclear Electric Circuit Breakers power reactors.
88-37 Flow Blockage of Cooling 6/14/88 All holders of Ots Water to Safety System or cps for nuclear Components power reactors.
88-3C Possible Sudden Loss of RCS 6/8/88 All holders of OLs Inventory During Low Coolant or cps for PWRs.
Level Operation 1
OL = Operating License CP = Construction Pemit
=r:.=r.==.====,=:_=~--,.e-e-----------------..
B INVOICE i
4 W --, ;,, ".7,.**2 CALIFORNIA BREAKERS INC.
6 A..-
^
am W 57651UJUNGA AVE 5
costowe= ~o 9
lDREAKERSj
",.",' y A P C^ "* '
lPicso
- ?;,53
. oce carc_
l l1 537?3 06/20,08 01491 F
0 woax oaoe., o eo A
29077
'O g
O s
CIRCLC W S'lPPt.( (JACK 50NVILLC) s TEXAS DLPT. OF C0fnWCTIONS i
Y COFFIEL r'.ETAL FAB 2
E P.
O.
FOX 5*,1 P
ROUTL 1, 00X 1SO 3
JACNSONVILLC. TX 15766 j
j TENN. COLONEY, TX 7b861 MARN4 696-0-43033 Fo8 SMiP VIA cart $w+ ppt 0 PU.CNA$( oaCEa hio DarE a(QU($rtD
,g...-
OS/17/88 981690012 s'.6 /17 / OD Ur S/HD N.
HOLLYWOOD reaus satasuma vtaa
$ rats suvia caer GARY 7
2. 10 - NFT 30 CHLRIE G.
14 TX
".7 s,...,, o f
U" '"'c8
*
- o ""ov"'
0"ca*'**
o.e,.i o
'" " "o (WH) CHB 3090 3 POC 90 AMP 1
1 142.00 142.00 W-RECONDITIONCD GUArt.
142.00 SUD-TOTAL 19.60 SHIPPING & IIANDL.ING t,
i 1
1 t
9 l
t 9
4 2
8
' 5% c*'
PLEASE REMIT
- dN 161.60 I
(
Wcsm en st te me aum ol dehen No refwas sheMed amer M daystrom mwng J8'*
ben mest.cu, o on teu on accets PWrem ayees to pay at twemy or teaw aue cow.
THIS AMOUNT e
sen cor roweeg anorre/s tees a
INVOICE NO.
b3773
'. i
[
j
,