ML20151Q577

From kanterella
Jump to navigation Jump to search
Forwards Info Notice 88-046 Re Potentially Defective Refurbished Circuit Breakers Supplied to Power Plants. Encl Invoice Identifies That Recipient as Customer.Addl Info Will Be Provided as Other Records Are Reviewed
ML20151Q577
Person / Time
Issue date: 08/01/1988
From: Grimes B
Office of Nuclear Reactor Regulation
To:
GOVERNMENT PRINTING OFFICE
References
IEIN-88-046, IEIN-88-46, NUDOCS 8808110215
Download: ML20151Q577 (3)


Text

s

.F-

  1. pa ua

'o E'

'g UNITED STATES NUCLEAR REGULATORY COMMISSION n

WASHING TON, D. C. 20555

%...../

AUG 01 1998 Procurement Officer Bureau of Engraving and Printing "D" Street Between 13th & 14th Street, S.W.

Washington, D.C.

20228

Dear Sir:

SUBJECT:

POTENTIALLY DEFECTIVE REFURBISHED CIRCUIT BREAKERS 4

The enclosed Nuclear Regulatory Commission (NRC) Information Notice (IN) 88-46 describes the circumstances under which defective refurbished electrical equip-ment may have been supplieo to nuclear power plants. Our continuing investiga-tion of the five circuit breaker companies identified in the IN shows that the companies have shipped breakers to a number of government facilities and agencies.

Our review of a sample of invoices indicates that generally the breakers are sold to a distributor, and it was only the occasional shipment direct to the end user that permitted us to identify the final government destination.

I have enclosed a copy of an invoice that identifies your agency as the customer. These documents represent our review of a selection of records spanning the last two or three years from all of the companies. As other records are reviewed, we will provide any additional information that comes to light.

However, since some of the companies have been in business for as many as 30 years, a full historical records search will not be possible.

The five California companies appear to sell surplus new as well as refurbished breakers. However, their refurbished equipment may be shipped in containers resembling original manufacturer containers.

If there is any additional information you require, please call me or Mr. Walter Haass at (301) 492-3219.

Sincerely,

)

.O drian K. Grimes, Director Division of Reactor Inspection and Safeguards Office of Nuclear Reactor Regulation Ofo?

Enclosures:

/

1.

NRC Bulletin (IN) 88-46 I i f

2.

Invoices / Orders 8800110215 % 01 PDR ORG PNV

+

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C.

20555 July 8, 198B NRC INFORMATION NOTICE NO. 88-46:

LICENSEE REPORT OF DEFECTIVE REFURBISHED CIRCUIT BREAVERS Addressees:

All holders of operating licenses or construction permits for nuclear power reactors.

Purpose:

This information notice is being provided to alert addressees of licensee reported information that defective refurbished electrical equipment, such as circuit breakers (CBs), may have been supplied to nuclear power plants.

It is expected that recipients will review this information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems.

However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required.

Description of Circumstances:

Pacific Gas and Electric Company (PG&E) has infortned NRC that it placed a purchase order for 30 new, non-safety-related, molded-case, KHL 36125-t.vpe CBs manufactured by the Square D Company (Square D) with a local electrical distributor.

These CBs were intended for use in non-safety-related applica-tions at PG&E's Diablo Canyon Nuclear Power Plant.

According to PG&E, the distributor in turn placed the order with a local sup-plier who bid the lowest price and promised the quickest delivery. The CBs were delivered directly to the Diablo Canyon plant by the supplier; the dis-tributor did not have an opportunity to inspect the CBs.

Square D, aware of the purchase order, questioned its failure to receive an order for the unique vintage KHL 36125-type CBs.

With PG&E's petrmission, Square D inspected the CBs and deterinined that PG&E had been given refurbished, rather than new, CBs.

Square D tested and performed detailed examinations of the CBs, and the results reported by PGtE follow.

A.

Physical Examination The yellow side labels used on the CBs were suspect in that the CB model numbers were typed on the labels whereas authentic labels are preprinted.

The CBs departed from normal appearance in other respects as well.

880 M

{

IN 88-46 July 8, 1988 Page 2 of 3 The individual CB cases and each of the CB components appeared to be Square D products; however, the individual CBs incorporated components of di#ferent years of manufacture.

Each CB bore evidence of having been opened and reassembled.

B.

_ Electric Testing Square D subjected the CBs to five electrical tests.

None of the CBs complied with Square D or Underwriters' Laboratory (UL) specifications for all of the tests, and several of the CBs were out of tolerance on each of the tests. At least four of the CBs failed to trip under circum-stances in which they are designed to trip.

Discussion:

In the past, there have been instances in which licensees purchased comercial-grade components, such as CBs, relays, trip units, and other electrical compo-nents, from electrical distributors and have received components that did not meet the original purchase order requirements.

NRC has received additional information indicating that the problem of surplus or defective refurbished CBs may also apply to CBs sold under other manufacturers' names (e.g., General Electric, Westinghouse, ITE, Cutler Hamer, and Sylvania).

The electrical suppliers involved in refurbishing and sales of circuit breakers, including the Diablo Canyon, Square D circuit breakers, apparently include five California corporations.

These companies are (1) General Circuit Breaker &

Electric Supply, Inc., (2) HLC Electric Supply Co., Inc., (3) Pencon Inter-national, Inc., doing business as General Magnetics / Electric Wholesale, (4)

California Breakers, Inc., and (5) Anti-Theft Systens, Inc., doing business as ATS Circuit Breakers and as AC Circuit Breaker-Electrical Supply.

NRC has an investigation and vendor inspection in progress at the above compa-nies.

On the basis of the information developed to date, a preliminary list of customers of the five companies including a list of nuclear utilities (where available) is provided in Attachment 1. contains a list of original equipment manufacturers whose nanes may have been used on surplus or refurbished equipment sold as new equipment.

The information included in Attachments 1 and 2 is only preliminary and is provided to assist licensees in reviewing the potential of having procured suspect electrical equipment at their facilities.

Licensees are reminded of the requirements to ensure that procured items meet the relevant specifications and codes and are suitable for the intended appli-cation.

Licensees should consider, as a matter of prudence, the need to inquire of and to verify with their authorized distributors the sources of procured materials, equipment, and components.

Licensees may meet these re by effectively implementing their quality assurance (QA) programs,quirements particularly in the areas of vendor evaluations, vendor surveillances, receipt inspection, bench tests, and post-installation tests.

IN 88-46 July 8, 198P Page 3 of 3 NRC is gathering additional inforwation to determine what further actions are necessary. The primary purpose of this information notice is to alert addressees of the situation as soon as possible.

The NRC is considering issuing a bulletin to followup on this information notice when the NRC has sufficient information to define requirements.

No specific action or written response is required by this information notice, if you t3ve any questions about this matter, please contact one of the techni-cal contacts listed below or the Regional Administrator of the appropriate regional office.

%bh Charles F., Rossi, Director Division of Operational Events Assessment Office of Nuclear Reactor Regulation Technical Contacts:

K. R. Naidu, NRR (301) 492-0980 Jaime Guillen, NRR (301)492-1170 Attachments:

1.

Preliminary List of Customers (Intermediate Suppliers) of Suspect Electrical Equipment 2.

Preliminary List of Original Equipment Manufacturers Phose Names May Have Been Used on Surplus or Refurbished Equipment Sold as New Equipment 3.

List of Recently Issued NRC Information Notices l

l l

l t

IN 88-46 July 8, 19PP Page 1 of ?

PREllMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utility (if available)

Westinghouse Electric St. Louis, M0; Boston, MA; Supply Co. (WESCO)

Boise, ID; Atlanta, GA; Charleston, SC; Panama, FL; Santa Clara, CA; Fresno, CA; Sacramento, CA; Shreveport, LA; Green Bay, Wl; Elk Creek, IL; Albuquerque, NM; Mobile, AL; Ft. Worth, TX; Baton Rouge, LA; Birmingham, AL; East Hartford, CT; Kokomo, IN; Jackson, MS; Milwaukee, WI; Beaumont, TX; Nashville, TN; Skelton, WV; Albany, NY; Hartford, CT; Portland, ME; St. Paul, MN; Minneapolis, MN; other locations Power Conversion Huntington Beach, CA Rockwell In':ernational Los Angeles, CA Arkansas Power and Light Little Rock, AP ANO Southern California San Clemente, CA; SONGS Edit;n other locations Phoenir. Electric Phoenix, A2 Rensenhouse Electric Topeka, V.S Breaker a1d Control Houston, TX General Electric Company Baltimore, MD Houston, TX; Landover, MD';)Chantilly, VA; Emeryville, CA; Elmhust, IL Southern Electric Alexandria, LA l

Supply Company Cleveland Electric Company l

l l

l

IN 88-46 July 8, 1988 Page 2 of ?

PRELIMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utilit (if available Stokley tnterprises Norfolk, VA Taylor Electric Company Portland, OR

, Graybar Ventura, CA; Atlanta, GA Hughes Aircraft El Segundo, CA Houston Electric Houston, TX Distribution Company i

l

,, ITE Electrical Products Atlanta, GA; knoxville, TN

,, Knudson Corporation Los Angeles, CA i

Georgia Power Company Milledgeville, GA l

l l

{

t I

l

!}.

IN 88-46 l

July 8, 1988 Page 1 of 2 I

1 PRELIMINARY LIST OF ORIGINAL EQUIPMENT MANUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SURPLUS OR REFURBISHED EQUIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number Equipment Descriptior.

Square 0 B19.5; B22 Heater for overload relay General Electric 12HGA11552 Auxiliary relay E,xide Company NX400 Spectro Inc.

V00014 Mercury lamps Bussman Company REN15 15-amp 250-V fuse Bussman Company N05-30 30-amp 600-Y fuse (unknown)

FSN 5925-628-0641 Circuit breaker Westinghouse DB-50 Trip unit Westinghouse DB-25 400-amp circuit breaker Westinghouse HKB3150T Trip unit Westinghouse KB3250F Frame Westinghouse FB3020 Circuit breaker l

Westinghouse FB3070 Circuit breaker Westinghcuse FB3050 Circuit breaker Westinghouse EMP3040 Circuit breaker Westinghouse EHB3025 Circuit breaker Vestinghouse LBB3125 Circuit breaker Westinghouse HKA31250 Trip unit Vestinghouse JA3200 Circuit breaker Westinghouse EHS2100 Circuit breaker i

Westinghouse CAH3200 Circuit breaker

Attachment ?

IN 88-46 July 8, 198P Page 2 of 2 PRELIMINARY LIST OF ORIGINAL EQUIPMENT MANUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SURPLUS OR REFURBISHED E0VIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number Equipment Description Westinghouse 225N Navy trip units ITE EF-3B100 100-amp circuit breaker General Electric AK-2-75-3 Circuit breaker General Electric AK-2 Circuit breaker General Electric AK-1-50 Circuit breaker General Electric AK-1-75 Circuit breaker General Electric B; TD0; TFJ Circuit breakers General Electric TCYVFS Circuit breaker ITE ET; KA Circuit breakers Cutler Harrer Circuit breakers Zinsco/Sylvania Circuit breakers Bryant Circuit breakers Murry Circuit breakers Federal Pacific Electric Circuit breakers Company I

l

IN 80-46 July 8, 1988 Page 1 of 1 LIST OF RECENTLY ISSUED NRC INFORMATION NOTICES Wrm tion Date of Notice No.

Subject issuance issued to 88-45 Problems in Protective 7/7/88 All holders of OLs Relay and Circuit or cps for nuclear Breaker Coordination power reactors.

83-44 Mechanical Binding of 6/24/88 All holders of OLs Spring Release Device or cps for nuclear in Westinghouse Type power reactors.

DS-416 Circuit Breakers 8'8-43 Solenoid Valve Problems 6/23/88 All holders of OLs or cps for nuclear power reactors.

88-42 Circuit Breaker Failures 6/23/88 All holders of OLs Due to Loose Charging or cps for nuclear Spring Motor Founting Bolts power reactors.

88-41 Physical Protection 6/22/88 All holders of OLs Weaknesses identified or cps for nuclear Through Regulatory Ef-power reactors, fectiveness Reviews (RERs) 88-40 Examiners' Handbook for 6/22/P.B All holders of OLs Developing Operator or cps for nuclear Licensing Examinations power reactors.

88-39 LaSalle Unit 2 Loss of 6/15/8P All holders of OLs Recirculation Pumps With or cps for BWRs.

Power Oscillation Event 88-38 Failure of Undervoltage 6/15/88 All holders of OLs Trip Attachment on General or cps for nuclear Electric Circuit Breakers power reactors.

88-37 Flow Blockage of Cooling 6/14/88 All holders of OLs Water to Safety System or cps for nuclear Components power reactors.

88-3C Possible Sudden Loss of RCS 6/8/88 All holders of OLs Inventory During Low Coolant or cps for PWRs.

Level Operation OL = Operating License CP = Construction Fentit

4

  • * " 8 2 '"

INV0 ICE D

~

ENERAL. b,d AGNETICS/Electr7c Wholesale E0 ENGINEERED ELECTRICAL CONTROLS AND CWiPONENTS 2201 YATES AVENUE e CObibfERCE. CAUFORNIA 90040

~

(213) 728 8684 O

PROCUREMEhT OFFICER i

O 1

GENERAL ELECTRIC SUPPLY

.;E AURE OF EkC. RATING & PRINTINC O

r e,

3715 WEs? STREET

  • D* STsEET BETWEEME & 14DLEISJI.l f LAnocTER, MD 20785

' WAsHIuctoNmC 20228 o

h 3-25-a3 25010, suo2 niens s

u.

p f.25.g3

! Urs 533-074728sD (3o1) 341-1800

..c ve.v e

...ag g..g:

i

...o fl li O!@

,1 C.E. TE32100 CIRCUIT BREAEEA 90.00 l

l;,

I i

l 3

3 l

e 4

I L

i 1

I I,

i i

I

_.__.______MARKf 71317-00-_ _

.l' _.-._ m k-W..h %

B ACK ORDE R$ WIL L BE SHIPPE 0 0N CONTINts ATION INVOICE NOTED ABOVE.

SUBTOTAL.

= - = = = ~ -

w. rt. r..n;..=

= =j,

. ;.. = - =..... c = =

~ " W ' C ' Y 'l a,,.--

d~'N_M4AL / f 8 'f/ #

M t

inn' c0v.

4l-I

=.m.---] 3 q ;.

u i3:3

~ -

,i REPAIR LABOR y

-t....

7;piggi--

Tickt

.. 'L L O^ L O. g

.'j,L,', D l hh 8

- I i

T O T A L k-_e-------s-a--;- - * - - ' 34 TE AP.*S NE T 33 D AYS NO CA$H Ol5CUONT

93 !C NOTE. a tats taanct os t e rf a m' tM wo cons.*av ei nt tumst o mtHOut e--------

v.%t et aabt c to ALL mataN;ts ovlR 60 Ou6t r. HIT 1( N ay1HQRila tion l

,...<..o eti ase eav o eaati.sL s irus sts I'c,n"a"$t aiio"E"78.'[ c'%IA'c7 '

t.

c

. mm t

i CIR(l 11 liRI % Al R4 A 1 Ril'S l

l cbb i

Ri t g) A

(()NI \\( TORN h il!! - ( \\lll !

'? \\(.\\l ll( ( Oli % \\l IH

\\l'l( l \\l IR \\\\bl OR\\11 !!b ii *:ii R \\1 t I:! t t)N1ROI %

\\M il N R s bl\\1M\\IUCN

  • *I il R A
t. \\l (.l s RINP10RN Nh il' Ifl A m

s __

400 0 ; 7gg Procurement Officer -DISTRIBUTION:w/o Enclosures JTaylor JSniezek-THartin BGrimes JStone

,PDR __ _ __,..,,,,

g' Centra 1 W iesA DRIS Reading (w/ Enclosures) l 1

l I

4 a

/

  • See previous page ncurrences.

DRIS:NRR S

JStone:tt*

B 07/22/88

/23/88 t/t ntq

__