Text

[,,,jo UNITED STATES g

'g g

NUCLEAR REGULATORY COMMISSION 5,,

WASHING TO N, D. C. 20555 E

%...../

AUG 0 I tggg Drug Enforcement Administration 1725 Industrial Way Sparks, NV 89431

Dear Sir:

SUBJECT:

POTENTIALLY DEFECTIVE REFURBISHED CIRCUIT BREAKERS The enclosed Nuclear Regulatory Commission (NRC) Information Notice (IN) 88-46 describes the circumstances under which defective refurbished electrical equip-ment may have been supplied to nuclear power plants. Our continuing investiga-tion of the five circuit breaker companies identified in the IN shows that the companies have shipped breakers to o number of government facilities and agencies.

Our review of a sample of invoices indicates that generally the breakers are sold to a distributor, and it was only the occasional shipment direct to the end user that permitted us to identify the final government destination.

I have enclosed a copy of an invoice that identifies your agency as the customer. These documents represent our review of a selection of records spanning the last two or three years from all of the companies. As other records are reviewed, we will provide any additional information that comes to light.

However, since some of the companies have been in business for as m j as 30 years, a full historical records search will not be possible.

The five California companies appear to sell surplus new as well as refurbished breakers. However, their refurbished equipment may be shipped in containers resembling original manufacturer containers.

If there is any additional information you require, please call me or Mr. Walter Haass at (301) 492-3219.

Sincerely, O

l + ~ ~~

l m-Brian K. Grimes, Director Division of Reactor Inspection and Safeguards Office of huclear Reactor Regulation pp03

Enclosures:

1.

NRC Bulletin (IN) 88-46 I j';

2.

Invoices / Orders I

i Qf 8808110178 880801 PDR ORO NRRB PNU

+

AUG 01 1983 c.

Drug Enfercement' Administration

- 2'-

l

-DISTRIBUTION:w/o Enclosures i

JTaylor-J$niezek TMartin BGrimes

.1 Stone PDR,.,..., _ _ _

ICetttralJ11esiM "DRISReading(w/ Enclosures) i J

a 1

i i

1

  • See previous page f 4x urrences.

i DRIS:NRR i

JStone:tt*

07/22/88 7/ 3/88 1

f/r P/;

rq 1

1

- +,

-,... - - - ~,,,,. -,,,,,,,,

.,,.,,.,_,_.,.,-,,,.,_,,,.m...-,n.,,.,__,,,m,

..,,,,,.-,,,,,,,.,,,,-ny-,,,,w,,,.-.,,,,,,--n,r,,

., -,J

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C.

20555 July 8, 1988 NRC INFORMATION NOTICE NO. 88-46: LICENSEE REPORT OF DEFECTIVE REFURBISH CIRCUIT BREAVERS Addressees:

All holders of operating licenses or construction permits for nuclear power reactors.

Puroese:

This information notice is being provided to alert addressees of licensee reported information that defective refurbished electrical equipment, such as circuit breakers (CBs), may have been supplied to nuclear power plants.

It is expected that recipients will review this information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems.

However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required.

Description of Circumstances:

Pacific Gas and Electric Compan purchase order for 30 new, non y (PG&E) has informed NRC that it placed a safety-related, molded-case, KHL 36125-type CBs manufactured by the Square D Company ISquare 0) with a local electrical distributor.

These CBs were intended for use in non-safety-related applica-tions at PG&E's Diablo Canyon Nuclear Power Plant.

j According to PG&E, the distributor in turn placed the order with a local sup-plier who bid the lowest price and promised the quickest delivery. The CBs were delivered directly to the Diablo Canyon plant by the supplier; the dis-tributor did not have an opportunity to inspect the CBs. Square D, aware of the purchase order, questioned its failure to receive an order for the unique vintage KHL 36125-type CBs.

With PG&E's permission, square D inspected the CBs and determined that PG8E had been given refurbished, rather than new, CBs.

Square D tested and performed detailed examinations of the CBs, and the results 1

reported by PGtE follow.

A.

Physicel Examination The yellow side labels used on the CBS were suspect in that the CB model numbers were typed on the labels whereas tuthentic labels are preprinted.

The CBs departed from normal appearance in other respects as well.

nmeseor 4/-

IN 88-46 July 8, 1980 Page 2 of 3 The individual CB cases and each of the CB components appeared to be Square D products; however, the individual CBs incorporated components of different years of manufacture.

Each CB bore evidence of having been opened and reassenbled.

B.

Electric Testing i

Square D subjected the CBs to five electrical tests.

None of the CBs complied with Square D or Underwriters' Laboratory (UL) specifications for all of the tests, and several Of the CBs were out of tolerance on each of the tests.

At least four of the CBs failed to trip under circum-stances in which they are designed to trip.

Discussion:

.In the past, there have been instances in which licensees purchased comercial-grade components, such as CBs, relays, trip units, and other electrical compo-nents, from electrical distributors and have received components that did not meet the ariginal purchase order requirements.

NRC has received additional information indicating that the problem of surplus or defective refurbished CBs may also apply to CBs sold under other manufacturers' names (e.g., General Electric, Westinghouse, ITE, Cutler Hamer, and Sylvania).

The electrical suppliers involved in refurbishing and sales of circuit breakers, including the Diablo Canyon, Square D circuit breakers, apparently include five California corporations.

These companies are (1) General Circuit Breaker &

Electric Supply, Inc., (2) HLC Electric Supply Co., Inc., (3) Pencon Inter-national, Inc., doing business as General Magnetics / Electric Wholesale, (4) s California Breakers, Inc., and (5) Anti-Thef t Systens, Inc., doing business as ATS Circuit Breakers and as AC Circuit Breaker-Electrical Supply.

NRC has an investigation and vendor inspection in progress at the above compa-nies.

On the basis of the information developed to date, a preliminary list of customers of the five companies including a list of nuclear utilities (where available) is provided in Attachment 1.

i equipment nanufacturers whose names may have been used on surplus or refu eavipmer.t sold as new equipment.

The information included in Attachments 1 and 2 is only prelininary and is provided to assist licensees in reviewing the potential of having orocured suspect electrical equipment at their facilities.

Licensees are reminded of the requirements to ensure that procured items rseet the relevant specifications and codes and are suitable for the intended appli-cation.

Licensees should consider, as a matter of prudence, the need to inquire nf and to verify with their authorized distributors the sources of procured raterials, equipment, and components.

Licensees may meet these re by effectively implementing their quality assurance (OA) programs,quirements particularly in the areas of vendor evaluations, vendor surveillances, receipt inspection, bench tests, and post-installation tests.

w

IN 88-46 July 8, 198P Page 3 of 3 l

NRC is gathering additieaal infomation to detemine what further actions are necessary. The primary purpose of this infomation notice is to alert addressees of the situation as soon as possible.

The NRC is considering issuing a bulletin to followup on this infomation notice when the NRC has sufficient inforntion to define requirements.

No specific action or written response is required by this infomation notice.

If you have any questions about this matter, please contact one of the techni-cal contacts listed below or the Regional Administrator of the appropriate regional office.

b 44 CharTes F..

Rossi, Director i

Division of Operational Events Assessment Office of Nuclear Reactor Regulation Technical Contacts:

K. R. Naidu, NRR (301) 492-0980 t

t Jaime Guillen, NRR (301) 492-1170 Attachments:

1.

Preliminary List of Customers (Intermediate Suppliers) of Suspect Electrical Equipment 2.

Preliminary List of Original Equipment Manufacturers j

Phose Names May Have Beer Used on Surplus or Pefurbished Equipment Sold as New Equipment j

3.

List of Recently Issued NRC Infomation Notices

)

]

1 Attachmeat 1 IN 88 46 July 8, 19PP Page 1 of 2 PREllMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utility (if available)

Westinghouse Electric St. Louis, M0; Boston, NA; Supply Co. (WESCO)

Boise, ID; Atlar,ta, GA; Charleston, SC; Panama, FLt Santa Clara, CA; Fresno, CA; Sacramento, CA; Shreveport, LA; Green Bay, Wl; Elk Creek, IL; Albuquerque, NM; Mobile, AL; Ft. Worth, TX; Baton Rouge, L A; Biriningham, AL; East Hartford, CT; Kokomo, IN; Jackson, MS; Milwaukee, WI; Beaumont TX; Nashville, TN; Skelton, WV; Albany, NY; Hartford, CT; Portland, ME; St. Paul, MN; Minneapolis, MN; other locations Power Conversion Huntington Beach, CA Rockwell International Los Angeles, CA Arkansas Power and Light Little Rock, AP AND Southern California San Clemerte, CA; SONGS Edison other locations Phoenix Electric Phoenix, AZ Rensenhouse Electric Topeka, KS Breaker and Control Houston, TX

, General Electrie Company Baltimore, MD; Houston, TX; Landover, mci; Chantilly, YA; Emeryville, CA; Elmhust IL Southern El.ctric Alexandria, LA Suppiy Company

\\

Cleveland Electric Company i

i l

l

\\

IN 88-46 July 8, 1988 Page 2 of 2 PRELIMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) i 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utility (if _a va ila ble)

Stokley triterprises Norfolk, YA Tajler Electric Company

+tland, OR Graybar ntura, CA; Atlanta, GA bughesAircraft El Segundo, CA Houston Electric Houston, TX Distribution Company i

, ITE Electrical Products Atlanta, GA; Knoxville, TN

, Knudson Corporation Los Angeles, CA Georgia Power Company Milledgeville, GA l

IN 88-46 July 8, 1988 Page 1 of 2 PRELIMINARY LIST OF GPIGINAL EQUIPMENT MANUFACTURERS WF^SE NAMES MAY HAVE BEEN USED Oh SURPLUS OR REFURDISHED EOUIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number

_ Equipment Descriptior Square D B19.5; B22 Heater for overload relay General Electric 12HGA11552 Auxiliary relay Exide Company NX400 Spectro Inc.

V00014 Mercury lamps Bussman Company REN15 15-amp 250-V fuse Bussman Company N05-30 30-amp 600-V fuse (unknown)

FSN 5925-628-0641 Circuit breaker Westinghcuse 08-50 Trip unit Westinghouse DB-25 400-amp circuit breaker Westinghouse HKB3150T Trip unit Westinghouse KB3250F Frame Westinghouse FB3020 Circuit breaker Westinghouse FB3070 Circuit breaker Westinghouse FB3050 Circuit breaker Westinghouse EHP3040 Circuit breaker Westinghouse EHB3025 Circuit breaker Pestinghouse LBB3125 Circuit breaker Vestinghouse H/,A312Ef Trip unit Westinghouse JA3200 Circuit breaker Westinghcuse EHB2100 Circuit breaker Westinghouse CAH3200 Circuit b eaker

At%achment 2 IN 88-46 July 8, 198P Page 2 of 2 PRELIMINARY LIST OF ORf CINAL EQUIPMENT KANUFACTURERS WHOSE NAMES itxY HAVE BEEN USED Ofi SURPLUS OR REFURBISHED E001PMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number Equipment Description Westinghouse 225N Navy trip units

~

Murry Circuit breakers Federal Pacific Electric Circuit breakers Company

IN 88-46 July 8, 1988 Page 1 of 1 LIST OF RECENTLY ISSUED NRC INFORMATION NOTICES 1

Infomation Date of j

Notice No.

Subject Issuance issued to t

88-45 Problerrs In Protective 7/7/88 All holders of OLs Relay and Circuit or cps for nuclear Breaker Coordination power reactors.

88-44 Mechanical Binding of 6/24/88 All holders of OLs Spring Release Device of cps for nuclear in Westinghouse Type power reactors.05-416 Circuit Breakers 88-43 Solenoid Valve Problem:,

6/23/88 All holders of OLs or cps for nuclear power reactors.

88-42 Circuit Breaker Failures 6/?3/88 All holders of OLs Due tn loose Charging or cps for r.uclear Spring Motor Founting Bolts power reactors.

88-41 Physical Protection 6/22/88 All holders of OLs Weaknesses identified or cps for neclear Through Regulatory Ef-power reactors, fectiveness Reviews (RERs1 88-40 Examiners' Handbook for 6/22/88 All holders of OLs Developing Operator or cps for nuclear Licensing Examinations power reactors.

88-29 LaSalle Unit 2 Loss of 6/15/88 All holders of OLs Recirculation Pumps With or cps for BWRs.

Power Oscillation Event 88-38 Failure of Undervoltage 6/15/88 All holders of OLs Trip Attachment on General or cps for nuclear Electric Circuit Breakers power reactors.

88-37 Flow Blockage of Cooling 6/14/88 All holders of OLs Water to Safety System or cps for nuclear Components power reactors.

88-30 Pos:ible Sudden Loss of RCS 6/8/88 All holders of OLs inventory During low Coolant or cps for PWRs.

Level Operation OL = Operating License CP = Construction Pemit

r 1

[. <- = _-

~

k 8

INVOICE E

3

. -E Elcetric Supply Co.

3?

11312

,O Circurt Breakers & Motor Control cessi coes:

,y (818) 9?O 4 646 g

I (800) 423-8540 m

~

13329 Garvey Avenue g

Baldwin Park, CA 91706 g

Ardae T.loctric D.E.A.

t-S S

'-~

r.o. sox 337 H

1725 Industrial way O

~

l L

D' 3FI'

!N 831 P

Sparks, W $9431

"* S OI O

~

j,,

y j}

ORDERED BY.

PO e PHONti

  • INvotCE DATE Mike D236022235
702) 359-8330 5-13-67 SALESMAN DATE SHIPPED vlA O BACK ORDER INV. NO

!s 7 /*

-)

CTS Today 0 ORIGINAL INVOICE NO C y *g.

U*

SH:P EL'O DESCRfM3ON p

1 I

2inaco QB 2430-40 59 00

\\'/

O l

1 4

O BACK ORDERS WILL BE SHIPkED ON INVOICE NOTED ABOVE.

SUBTOTAL I qf c,. 0 ss,pp,og tH s (,,s u a i. y.

C "'

a t 4'*1 l 4

De C M A GE,5 INS 3

I

.-4 TAX NOT A1.ON S l

FREIGHT

)

V CHARGES

/

"5 ClivtO Bf

)

L4 TOTAL %/,'.

,M 2

TE-NET 30 DAYS: NO C/.SH DISCOUNT MAC, HECKS PAYA5LE TO: HLC ELECTRIC SUPPLY CO.

I MASTER COPY S