ML20151Q141
| ML20151Q141 | |
| Person / Time | |
|---|---|
| Site: | South Texas |
| Issue date: | 08/02/1988 |
| From: | BECHTEL GROUP, INC. |
| To: | |
| Shared Package | |
| ML20151Q144 | List: |
| References | |
| ST-HL-AE-2734, NUDOCS 8808110053 | |
| Download: ML20151Q141 (12) | |
Text
_. _.
ATTACHMENT
..ST HL AE. /7 54 i
PAGE / OF M
. ATTACHMENT I
SUMMARY
OF UNIT 1 VOLTAGE VERIFICATION TEST RESULTS (PSB-1)
SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION P
BY BECHTEL ENERGY CORPORATION 1
INDEX Sumary of Results Pages 1 thru 3 Test Results Sumar.y Appendix A Simplified One Line Diagrams Appendix B 8808110053 880802 l
POR ADOCK 05000498 P
-05181/00191 l
l
, _ _ _ _, _ _ ~., _.., _ _.,.,, _.,...,.. _. _ _,., _ _, _,
ATTACHMENT
. ST HL AE 3734 PAGf.g.0F AP Summary Of Results Unit i Voltage Verification Test Results (PSB-1)
South Texas Project Electric Generating 5tation As required by Branch Technical Position (BTP) PSB-1, section B.4, the project has completed a voltage verification test to confirm the adequacy of the mathematical model used for analyzing plant auxiliary power systein voltages under various plant operating conditions.
The project coninitted to this effort in response to FSAR question 430.20N.
This section of the BTP requires that actual measurements of bus voltages and loads be performed under the following conditions:
A.
Safety related buses down to the 120 volt level are loaded to a minimum of 30 percent.
B.
The existing grid and safety related bus voltages and bus loads be recorded during steady state conditions and during transient conditions with the non-concurrent starting of a large class lE motor and a large non-class lE nietor.
C.
A new set of bus voltages be calculated for the voltage and load conditions measured in B above.
D.
The measured ana calculated voltages be compared.
The mathematical model will have been verified if good correlation exists between the measured values and the calculated values and if the actual voltages measured are not lower than 3% below the calculated values.
Voltage analyses have been performed using computer modeling techniques that studied various plant operating conditions as required by section B.3 of BTP PSB-1.
These analyses have determined the steady state bus voltages under heavily loaded conditions coincident with the switchyard at a minimum anticipated voltage. Steady state light load conditions during plant shutdown and normal operating conditions were evaluated coincident with the switchyard at maximuni anticipated voltage.
Transient loading conditions (e.g. during automatic load sequencing) were evaluated to confirm that adequate voltage was available to ensure the pmper starting of motor loads.
The degraded voltage trip setpoint was also established in these voltage analyses.
Verification of the mathematical model substantiates the validity of these other analyses.
The voltage verification test program was established in accordance with the requirements of BTP PSB-1, section B.4.
Minimum required bus loads of thirty percent of the steady state bus loads evaluated in the original voltage analysis were determined and provided to the nuclear operations department. 05181/00191
ATTACHMENT
. ST HL AE #73V
&%.3.OF /J Separate tests were perfornied on train A, train B, and train C.
During the tests all buses were loaded to a minimum of 30% of the maximum calculated loading, with the following exceptions; l) 480 volt motor control center E1A1 load was 28.7% (Maximum Obtainable) 2)
120/208 volt distribution panel DPB435 load was 26.3%. (space heaters)
In addition, during retesting of some voltage points the following two buses were less than 30% loaded.
These were retests to verify results obtained during a previous test during which these buses were loaded to a minimum of 30%.
1) 4.16XV Bus ElB load was 20%. (Maximum available load at time of retest) 2)
120/208 volt distribution panel LPA435 load was 28.9% (space heaters)
Steady state voltages and loading at the necessary buses were recorded. As soon as practical, the motors selected for the transient start tests were energized, first by starting a non class lE circulating water pump motor (3500 hp) followed by (within a short period of time and after steady state conditions were again reached) a class lE high head safety injection pump motor (1000 hp) for each train.
Transient voltages during these motor starts were monitored on all safety related buses except regulated 120V panels.
The measured values were then analyzed using the same mathematical model used during the original voltage analysis.
The Test Results Suneary is provided in Appendix A and Simplified One Line Diagrams for the associated buses are provided in Appendix B.
Delta (A) is defined as Measured Voltage Calculated Voltage in % - 100%
The worst case (most negative) A 's for the two steady state and two transient tests for each train are shown in Appendix A.
The results in Appendix A are the worst case of the three supply sources to the 13.8XV bus which feeds each train (See Appendix B).
When the supply source to the 13.8XV bus is a standby transformer (#1 or #2), the 362.25XV switchyard bus voltage was monitored and used as the reference bus for the A 's.
When the supply source is the unit auxiliary transformer, the 23XV generator bus was monitored and used as the reference bus for the A's, since the voltage drop thru the main step up transformers NT001A and NT001B is compensated for by the automatic load tap changer on the unit auxiliary transformer.
As indicated in Appendix A, good correlation exists between the measured values and the calculated values for the steady state and transient portions of the test program for all trains.
The differences between the steady state measured and calculated values range from a maximum negative A of - 2.23 percent difference on bus DPB 235 and a maximum positive A of + 1.42 percent on MCC bus ElC2.
Therefore, the comparison of the measured and calculated steady state values is acceptable per the criteria in BTP PSB-1. 05181/0019i
ATTACHMENT
. ST-HL AE.2739 26C4.V 0F G For the transient voltage conditions, the measured values differed from calculated values by a maximum negative 21 of - 2.99 percent on load center bus ElB2 and a maximum positive 21 of +.64 percent on 4.16KV bus EIA. This data shows good correlation between the measured and calculated values and the comparisen of the measured and calculated transient values, and is acceptable per the criteria in BTP PSB-1.
In summary, on the basis of the results of the Voltage Verification Test steady state and transient analysis, the mathematical model used in the voltage analysis is considered to have been verified as being acceptable and the original analysis did satisfactorily predict plant distribution system conditions under the various analyzed operating modes.
. i 05181/00191
.~.-. -
i ATTACHMENT
. ST HL AE #73V PAGE 6 0F /?
Test Results Sunenary Appendix A Page 1 of 3 Train A I
J Worst Case Worst Case Bus l
Steady State A (%)
Transient A (%)
13.8KV Bus IF l
-.68 i
- 1.18 1
I 4.16KV Bus El A
+.18
+.64
.97
.49 l Load Center (LC) ElAl i (480V)
Load Center (LC) ElA2
-.21
+.33 (480V) i I
.62 l
.17 Notor Control Center 1
(NCC) ElAl (480V)
.38 Notor Control Center
+.48 (NCC) El A3 (480V)
.36
+
.25 Notor Control Center (MCC) ElA2 (480V)
.41
+.15 Notor Control Center (NCC) E1 A4 (480V) l Distribution Panel
- 1.87 N/A DPA 135 (120/208V)
I Distribution Panel l
- 1.28 N/A l
DPA 335 (120/208V)
I
.68 N/A Distribution Panel DPA 235 (120/208V)
Distribution Panel
- 1.96 N/A l DPA 435 (120/208V) l l
l N/A Denotes that transient volta 9es on 120/208 volt distribution panels are not calculated and are therefore not applicable to A calculations.
05181/0019i
ATTACHMENT ST.HL.AE 913Y PAGE 6 OF /A Test Results Summary Appendix A Page 2 of 3 1 rain B Worst Case Worst Case r,u s Steady State li (%)
Transient 21 (%)
.72
.72 13.8KV Bus 1G l
l 4.16KY Bus ElB
- 1.02
- 1.06 i
.07
- 1.70 Load Center (LC) E181 i Load Center (LC) ElS2
- 1.76
- 2.59
.52
- 2.14 Motor Control Center (MCC) ElB1 Motor Control Center
.67
- 2.28 (MCC) ElB3 l
l
. 61
- 2.11 Motor Control Center (NCC) E182
. 61
- 1.24 Motor Control Center (NCC) ElB4 l
Distribution Panel
- 2.12 N/A DPB 135 Distribution Panel
- 2.23 N/A DPB 335 1
Distribution Panel
- 1.70 I
h/A DPB 235 l
l Distribution Panel
- 1.97 N/A l
l DPB 435 l
05181/00191
.,~
' 1 I
ATTACHMENT l
. ST HL AE #7W
. PAGE 7 OF / R Test Results Sunnary Appendix A Page 3 of 3 Train C Worst Case Worst Case j
Bus Steady State A (%)
Transient A(%)
.68
- 1.18 13.8KV Bus lH
.25
.79 4.16KV Bus Elc Load Center (LC) ElCl 1.24
- 1.72 i
.54
- 1.08 Load Center (LC) ElC2 Motor Control Center 1
- 1.19
- 1.66 (NCC) ElCl Motor Control Center
+.63
.21-(NCC) ElC3 Motor Control Center
+ 1.42
+.16 (MCC) ElC2 Motor Control Center
- 1.07
- 1.42 (NCC) ElC4
(
1 Distribution Panel
- 1.09 N/A j
DPC 135 l
Distribution Panel
.28 N/A DPC 335
[ Distribution Panel
.60 h/A l DPC 235 l
l Distribution Panel
. 61 N/A l DPC 435 05181/00191
_,. u._
_.,, _ _ ~
..-._._._._.__._.-,s.._,_.-.__-._,_.._.,_._..._._...
Simplified One Line Diagrams Appendix B ATTACHMENT Page 1 of 5
. ST HL AE s273Y PAGE.S.0F /A o
I
$i I
H i wSo' o
W N
lI y *,'
CE w
D uc m
x o
a-s5a 2
cc
~
xm maw e l
g u
>e h.
l O
O t
s x
$Q X
8
~
en e
w a
^
p H f I
i 2 bl D
- 2 "E I E
T B
?
i
..F i
o Ex g
w; W
m x
- --*?fc
-( @-.@
e h ::
8 V
l Q
0 0
~
d b
n I e 6-s l
Ki s
se Ai Ss E
e b-W ggI 2"-
^
^
i i
o s
.a-a 25
@ @ g( @ @
M:
F ee s,
~
g.
7
~
x e
0 j
u l h-i g
=,
l 1
Ob 3
I g
"W p
? 'b h
C C
N i
i u
h h
l h
I m
o so s.
]
U w.
c w
2 SL) M O
y 3
--3 O
n( (vv{
o alb 1 "
"t-s.
e Es
/
? ii 3
~
i m
R_ l p 1r se s=
l A6 2
e c
I"*
{ ', #
01 i
m --
g M
@Br' i
c
- n.
.s, e
v
.---e e w
- e=*
e-O emune e
+
6 eh, e
a esw-.
e
Simplified One Line Diagrams Appendix B ATTACHMENT Page 2 of 5 ST HL AE a?3'/
PAGE 9 OF /a N
I 1 ~
Es.
I H
g wo o, o
w i>
V ".'
W T
u.e S
-)
in OgN w
o o
D h
- I
.J g
>-e k
l 0.
u.
- O
- W I
C M
-.a 8
x
@m 4
a W
^
[
>= g*
l
'2llll*
I ( @N b
h g
e '
q-8 I
go g
g A
m W
-*?ft
@@!(@@
e n
I O
I I I 4
t i
A k
m te 1
o 'k r
O e.
i e
2 I
V v@
y 3
1 Wi
+
w de A!
a e es-
.eg Oi-
,-o g.2 e
845 IOI b
3 o
-(
at ::
p c
rI t,
z JL
- F aj
- .4:
l h" rg @
sE e
t m-e o
o '2 e
I :
-A x
.o R..
U*
o 2
~
m e~ 0'
-~
- $\\
w rd u
.-r a
m wa
__ ;g e
.J
@@a O@
- ~ s
- -
e, um 3
k v
2.J Ow
~
i w
g
)
tt c
t
~87 Dh M
{D 1a
~
n
( ip
'W w
I h
8 1
M
AUX ESF XFMR EAB fg,_o ULJJ EI A HdR ROOM ITm 13.0-4.1 W
@ 22
)
u 4.16KV EIA
- 23 @ g
- 2 @
- 2 4@
- 26 6 LOAD CENTER XFMR LOAD CENTER XFMR
'J EI A2 LJ EIAf r3 4.16-0.40KV 07 4.16-0.40KV 1000 HP
)@
@ " " " " - 'd
)@
if,
&2 *
& 27 1
480V t2 E1Al I
480V CC EIA2
[
' )@
' )@
)@
@g )ggw, O5 D:
@#27 @30&3f
@32 @ *33 @ 3y
@ 35 gg@*y7 080v MCC EIAI 480V MCC EIA3 480V MCC EI A2 480V MCC El At*
EN[
)@
)@
)@
)@
~~?
LJ 400-120/200V LJ 400-120/209V LJ 400-120/209V LJ 400-120/209V E
30KVA 3E341EDTAl70 ra 3E341 EDTA 370 30KVA 30KVA r7 r7 3E341EDT A270 30KVA r3 3E341EDTAV70 l MCC E1A1 I'
MCC EI A2 COMPT M2 COMPT L3 L-3E171EMCE1A1 3E171EMCEIA2
- 11@ $92$93 "9Y0 _$/5&hd
- 47 0 $f8 $ 47 90 fSt $52 y
3E 171EbpA#35 3E171 EbPA 33S 3E171dbPA275 3E171dbPA435 Mh lao /20sv AC PANEL B0 120/200v AC PANEL 90 120/209V AC PANEL 90 120/209V AC PANEL BO BMI MCC EIAi, COMai Q3 MCC El A3, COMPT 03 MCC EIA2. COMPT H3 MCC EIAV, COMPT K/
Qi SOUTH TEXAS PROJECT T
m m.
enmim e.
14926-001 FIGURE - 3
AUX ESF XFMR
{B35'-0 aJL/EIS SH5R ROOM rr m 13.8-4.16KV
@*53 3)O g
7 LOA LOAD CENTER XFMR EIB,D CENTER XFMR g E182 LJ M
r7 4.16-0.40Ky (7 4.16-0.40KV 10 0 HP H HS1 -IB
)Q v,
5
=
0*5T
@*56 m !E" i
0
=
=
' )@
)@
{)@
480V LC EIS/
480v LC E182 g
@%o_ @wqycz
@'o_ @*aD*cs-
@ %7D*cr
&' )@'wD*ri. M i 480v MCC EtBI 480V MCC E183 480V MCC E182 480V MCC EISP
. co
)@
)@
)@
)@
.i s
LJ 400-120/209v LJ 400-120/209V LJ 400-120/209V LJ 4CO-120/209V 3OKvA 3OKVA rq 3E341EDT8170 rq 3E341EDTB370 30KvA e
ra 3E341EDT827o 3OKvAra 3E341EDTSV70 l MCC E18I T
li* COMPT R3 MCC E182 i
COMPT K3
/
/
)
b-3E171EHCE1Bf bJ 3E171EMCE182
. W ii
- 72@
@*73@*79
- 750
@*76 @*77
- 78@ Wi@*go
- 81 @ $82W83 35y 3E171[bP8135 3E17IEbP B335 3E171E'bP8235 3E171dbPSV35 b
120/200V AC PANEL BD 120/209V AC PANEL BD 120/200V AC PANEL 80 120/200V AC PANEL 90
!O hE MCC E181, COMPT S3 MCC E183, COMPT E3 MCC E182, COMPT 53 MCC E189, COMPT-N/
g y" SOUTH TEXAS PROJECT
>= =.
I
-14926-001 FIGURE - &
i
\\
4 J
8
~
v l
i AUX ESF XFMR EAB ULLU E1C o,_o-dR ROOM (T m 13.8-4.16KV e"e* 1)O
$$)@DCENTERXFMR
,)@
- $$ )@
^ " "
LOAD CENTER XFMR LOA
'J Elc2 LJ EICI F7 4.16-0.48KV r7 4.16-0.40KV 1000 HP
)h L)h go'" N HJI-IC @m i
@*89
C E1C 2 '
j tl E1CI
[
480V L
480V
' )@
)@
' )@
)@
Q;.
Erw _ 0y,20yn
@w _ wseru Gfr7 yreD"vr
&/oo. m ir e viO2
- [e,
480v MCC E1CI 480V MCC E1C3 480V MCC E1C2 480V MCC EICV
.E
')@
' )@
)@
)@
j 2
~=
i LJ 400-120/200V LJ 400-120/200V LJ 400-120/209V LJ 490-120/209V 3OKVA 30KVA 3E341EDTC37o 30KvA 3E341EDTC27o ra 3E341EDTCf?p 30KVAr, 3E341EDT C 170 r7 r3 l~l~l MCC E1CI 3 MCC E1C2 kJ)*3E171EMCEIC2
)
COMPT 01 i
COMPT Ji IL 3E171EMCE1Cl l
- /030 $/0&/05
- 4%0 h/07$/08
- 1.60,h//0 $///
- //20
$ft3$//y l
v9>
3E171dbPC135 3E171dbPC335 3E171dbpC235 3E171dhPCVJ5
$gN
-I "C
i 120/208v AC PANEL BO 120/200v AC PANEL Os 120/208v AC PANEL OD 120/208V AC PAEL 80 MCC E1CI, COMPT ny MCC E1C3, COMPT e3 MCC E1C2, COMPT D3 MCC E1Cy, COMPT'7/
Dbb
?W i
SOUTH TEXAS PROJECT Q
= =.
=..
l
-14926-001 FIGURE - S i
- m