Forwards Info Notice 88-046 Re How Defective Refurbished Electrical Equipment May Have Been Supplied to Plants. Investigation of Five Circuit Breaker Companies Show That Companies Shipped Breakers to Govt Facilities & Agencies
ML20151N412
Person / Time
Issue date: 08/01/1988
From: Grimes B
Office of Nuclear Reactor Regulation
To:
PRESIDENT OF U.S. & EXECUTIVE OFFICES
References
IEIN-88-046, IEIN-88-46, NUDOCS 8808080209
Download: ML20151N412 (2)


Text

'

c

[o ec%o UNITED STATES 8'

'g NUCLEAR REGULATORY COMMISSION n

h WASHINGTON, D. C. 20555 AUG 0 I 1988 White House Executive Resident East Gate Executive Blvd.

Rear Gate 81 Washington, D.C.

20500

Dear Sir:

SUBJECT:

POTENTIALLY DEFECTIVE REFURBISHED CIRCUIT BREAKERS The enclosed Nuclear Regulatory Commission (NRC) Information Notice (IN) 88-46 describes the circumstances under which defective refurbished electrical equip-ment may have been supplied to nuclear power plants.

Our continuing investiga-tion of the five circuit breaker companies identified in the IN shows that the companies have shipped breakers to a number of government facilities and agencies.

Our review of a sample of invoices indicates that generally the breakers are sold to a distributor, and it was or'.y the occasional shipment direct to the end user that permitted us to identify the final government destination.

I have enclosed a copy of an invoice that identifies your agency as the customer.

These oocuments represent our review of a selection of records spanning the last two or three years from all of the companies. As other records are reviewed, we will provide any additional information that comes to light.

However, since some of the companies have been in business for as many as 30 years, a full historical records search will rot be possible.

The five California companies appear to sell surplus new as well as refurbished breakers.

However, their refurbished equipment may be shipped in containers resembling original manufacturer containers.

If there is any additional information you require, please call me or Mr. Walter Haass at (301) 492-3219.

Sincerely, J

I d~

W i

rian K. Grimes, Director Division of Reactor Inspection and Safeguards Office of Nuclear Reactor Regulation

Enclosures:

Ob f

i 1.

NRC Bulletin (IN) 88-46 e

2.

Invoices / Orders 8808080209 880801 PDR ORG NRRB

D White House Executive ' Resident DISTRIBUTION:w/o Enclosures JTaylor JSniezek TV.artin BGrines JStone P D R,. m m m, u,

JCentral Filesd ORIS Reading-(w/ Enclosures)

I

  • See previous page f co urrences.

7 DRIS:NRR I

JStone:tt*

B a

07/22/88 7/23/88 Sf(

Y',

e,

},.

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C.

20555 July 8, 1988 NRC INFORMATION NOTICE NO. 88-46:

LICENSEE REPORT OF DEFECTIVE REFURBISHED CIRCUIT BREAVERS Addressees:

All holders of operating licenses or construction permits for nuclear power reactors.

Purpose:

This information notice is being provided to alert addressees of licensee reported information that defective refurbished electrical equipment, such as circuit breakers (CBs), may have been supplied to nuclear power plants.

It is expected that recipients will review this information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems.

However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required.

Description of Circumstances:

Pacific Gas and Electric Compan purchase order for 30 new, non y (PG&E) has informed NRC that it placed a safety-related, molded-case, (HL 36125-type CBs manufactured by the Square D Company (Square 0) with a local electrical distributor. These CBs were intended for use in r.on-safety-related applica-tions at PG&E's Diablo Canyon Nuclear Power Plant.

According to PG&E, the distributor in turn placed the order with a local sup-plier who bid the lowest price and promised the quickest delivery. The CBs were delivered directly to the Diablo Canyon plant by the supplier; the dis-tributor did not have an opportunity to inspect the CBs.

Square D aware of the purchase order, questioned its failure to receive an order for the unique vintage KHL 36125-type CBs. With PG&E's permission, Square D inspected the CBs and determined that P3&E had been given refurbished, rather than new, CBs.

Square D tested and performed detailed examinations of the CBs, and the results reported by PGtE follow.

A.

Physical Examination The yellow side labels used on the CBs were suspect in that the CB model numbers were typed on the labels whereas authentic labels are preprinted.

The CBs departed from normal appearance in other respects us well.

,.ASG708000;=

IN 88-46 July 8, 1980 Page 2 of 3 The individual CB cases and each of the CB components appeared to be Square D products; however, the individual CBs incorporated components of different years of manufacture.

Each CB bore evidence of having been opened and reassembled.

B.

Electric Testing Square D subjected the CBs to five electrical tests.

None of the C8s complied with Square D or Underwriters' Laboratory (UL) specifications for all of the tests, and several of the CBs were out of tolerance on each of the tests.

At least four of the CBs failed to trip under circum-stances in which they are designed to trip.

_ Discussion:

In the past, there have been instances in which licensees purchased comercial-grade components, such as CRs, relays, trip units, and other electrical compo-nents, from electrical distributors and have received components that did not meet the original purchase order requirements.

NRC has received additional information indicating that the problem of surplus or defective refurbished CBs may also apply to CBs sold under other manufacturers' names (e.g., General Electric, Westinghouse, ITE, Cutler Hamer, and Sylvania).

The electrical suppliers involved in refurbishing and sales of circuit breakers, including the Diablo Canyon, Square D circuit breakers, apparently include five California corporations.

These companies are (1) General Circuit Breaker &

Electric Supply, Inc., (2) HLC Electric Supply Co., Inc., (3) Pencon Inter-national, Inc., doing business as General Magnetics / Electric Wholesale, (4)

California Breakers, Inc., and (5) Anti-Theft Systens, Inc., doing business as ATS Circuit Breakers and as AC Circuit Breaker-Electrical Supply.

NRC has an investigation and vendor inspection in progress at the above conpe-nies.

On the basis of the information developed to date, a preliminary list of customers of the five companies including a list of nuclear utilities (where available) is provided in Attachment 1. contains a list of original equipment nanufacturers whose names may have been used on surplus or refurbished equipment sold as new equipment.

The information included in Attachments 1 and 2 is only preliminary and is provided to assist licensees in reviewing the potential of having procured suspect electrical equipment at their facilities.

Licensees are reminded of the requirements to ensure that procured items meet the relevant specifications and codes and are suitable for the intended appli-cation.

Licensees should consider, as a matter of prudence, the need to inquire of and to verify with their authorized distributors the sources of procured materials, equipment, and components.

Licensees may meet these re by effectively implementing their quality assurance (QA) programs,quirements particularly in the areas of vendor evaluations, vendor surveillances, receipt inspection, l

bench tests, and post-installation tests.

l l

l l

i

,,--a----------,v,

-~

IN 88-46 July 8, 193P Page 3 of 3 NRC is gathering additional inferwetion to determine what further actions are necessary.

The primary purpose of this information notice is to alert addressees of the situation as soon as possible.

The NRC is considering issuing a bulletin to followup on this information notice when the NRC has sufficient information to define requirements.

No specific action or written response is required by this information notice.

If you have any questions about this matter, please contact one of the techni-cal contacts listed below or the Regional Administrator of the appropriate regional office.

Cha%b h rles t. Rossi. Director Division of Operational Events Assessment Office of Nuclear Reactor Regulation Technical Contacts:

K. R. Naidu, NRR (301) 492-0980 Jaime Guillen, NRR (301) 492-1170 Attachments:

1.

Preliminary List of Customers (Intermediate Suppliers) of Suspect Electrical Equipment 2.

Preliminary List of Original Equipment Manufacturers Yhose Names May Have Been Vsed on Surplus or Pefurbished Equipment Sold as New Equipment 3.

List of Recently Issued NRC In'ormation Notices

- - ~.

IN 88-46 July 8, 19PP Page 1 of 2 PRELIMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL EQUIPMENT Organization Location Nuclear Utility fif available)

Westinghouse Electric St. Louis, M0; Boston, MA; Supply Co. (WESCO)

Boise, IL; Atlanta, GA; Charleston, SC; Panama, FL; Santa Clara, CA; Fresno, CA; Sacramento, CA; Shreveport, LA; Green Bay, WI; Elk Creek, IL; Albuquerque, NM; Mobile, AL; Ft. Worth, TX; Baton Rouge, LA; Bimingham, AL; East Hartford, CT; Kokomo, IN; Jackson, MS; Milwaukee, WI; Beaumont TX; Nashville, TN; Skelton, WV; Albany, NY; Hartford, CT; Portland, ME; St. Paul, MN; Minneapolis, MN; other locations Power Conversion Huntington Beach, CA j

Rockwell International Los Angeles, CA Arkansas Power and Light Little Rock, AP ANO Southern California San Clemente, CA; SONGS Edison other locations Phoenix Electric Phoenix, AZ Rensenhouse Electric Topeka, KS Breaker and Control Houston, TX General Electric Company Baltimore, MDi Houston, TX; Landover, MD'; Chantilly, VA; Emeryville, CA; Elmhust, IL Southern Electric Alexandria, LA Supply Company Cleveland Electric Company

IN 88-46 July 8, 1988 Page 2 of 2 PRELIMINARY LIST OF CUSTOMERS (INTERMEDIATE SUPPLIERS) 0F SUSPECT ELECTRICAL EQUIPMEdT Oraanization Location Nuclear Utility fif available)

Stokley interprises Norfolk, VA Taylor Electric Company Portland, OR Graybar Ventura, CA; Atlanta, GA Hughes Aircraft El Segundo, CA Houston Electric Houston, TX Distribution Company ITE Electrical Products Atlanta, GA; Knoxville, TN Knudson Corporation Los Angeles, CA Geeeot Power Company billedgeville, GA r

E I

i f

l l

l l

IN 88-46 July 8, 1988 Page 1 of 2 PRELIMINARY LIST OF ORIGINAL EQUIPMENT MANUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SURPLUS OR REFURBISHED E0VIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number

_Ecuipment Descriptior.

Sc,uare 0 B19.5; B22 Heater for overload relay General Electric 12HGA11552 Auxiliary relay E.xide Company Ny400 Spectro Inc.

V00014 Mercury lamps Bussman Company REN15 15-amp 250-Y fuse Bussman Company N05-30 30-amp 600-V fuse (unknown)

FSN 5925-628-0641 Circuit breaker Westinghcuse DB-50 Trip unit Westinghouse DB-25 400-amp circuit breaker Westinghouse HKB3150T Trip unit Westinghouse KB3250F Frame Westinghouse FB3020 Circuit breaker Westinghouse FB3070 Circuit breaker Westinghouse FB3050 Circuit breaker Westingheuse EHP3040 Circuit breaker Westinghouse EHB3025 Circuit breaker Festinghouse LBB3125 Circuit breaker Westinghouse HKA31250 Trip unit Westinghouse JA3200 Circuit breaker Westinghouse EHB2100 Circuit breaker i

Westinghouse CAH3200 Circuit breaker

k

.i 1

IN 88-46 July 8, 198P l

Page 2 of 2 PRELIMINARY LIST OF ORIGINAL EQUIPMENT MANUFACTURERS WHOSE NAMES MAY HAVE BEEN USED ON SURPLUS OR REFURBISHED EQUIPMENT SOLD AS NEW EQUIPMENT Manufacturer Model Number Equipment Description Westinehouse 225N Navy trip units ITE EF-3B100 100-amp circuit breaker General Electric AK-2-75-3 Circuit breaker deneralElectric AK-2 Circuit breaker General Electric AK-1-50 Circuit breaker Gei.eral Electric AK-1-75 Circuit breaker General Electric B; TD0; TFJ Circuit breakers General Electric TCVVFS Circuit breaker ITE ET; KA Circuit breakers Cutler Henrer Circuit breakers Zinsco/Sylvania Circuit breakers Bryant Circuit breakers Murry Circuit breakers Federal Pacific Electric Circuit breakers Company i

~

~

IN 88-46 July 8, 1988 Page 1 of 1 LIST OF RECENTLY ISSUED NRC INFORMATION NOTICES Information Date of Notice No.

Sub,iect Issuance issued to 88-45 Problems In Protective 7/7/88 All holders of OLs Relay and Circuit or cps for nutlear Breaker Coordination power reactors.

88-44 Mechanical Binding of 6/24/88 All holders of OLs Spring Release Device or cps for nuclear in Westinghouse Type power reactors.

DS-416 Circuit Breakers 8'8-43 Solenoid Valve Problems 6/23/88 All holders of OLs or cps for nuclear power reactors.

88-42 Circuit Breaker Failures 6/23/88 All holders of OLs Due to Loose Charging or cps for nuclear Spring Motor Founting Bolts power reactors.

88-41 Physical Protection 6/22/88 All holders of OLs Weaknesses identified or cps for nuclear Through Regulatory Ef-power reactors.

fectiveness Reviews (RERs1 88-40 Examiners' Handbook for 6/22/PP All holders of OLs Developing Operator or cps for nuclear Licensing Examinations power reactors.

88-39 LaSalle Unit 2 Loss of 6/15/8P fill holders of OLs Recirculation Pumps With or cps for BWRs.

Power Oscillation Event i

88-38 Failure of Undervoltage 6/15/88 All holders of OLs Trip Attachment on General or cps for nuclear Electric Circuit Breakers power reactors.

88-37 Flow Blockage of Cooling 6/14/88 All holders of OLs Water to Safety System or cps for nuclear Components power reactors.

88-30 Possible Sudden Loss of RCS 6/8/88 All holders of OLs Inventory During low Coolant or cps for PWRs.

Level Operation OL = Operating License CP = Construction PerTnit

INY0 ICE

-l D

bENERAL k AGNETICS/Electr7c Wholes.:;le 32061; f

c; m u w l

LNG 1NEERED LLECTRICAL CONTHOLb ANI) COMPONE.%7S 5

I 2201 YATES A%'ENUE e COMMERCE. CAUFORNIA 90040 (213) 728 8684 WHITE HOUSE EXECUTIVE RESIDENT O

GENL'RAL ELECTRIC SUPPLY CO.

EAST SATE EXECUTIVE SLVD 7

g 4206 5HANNON 04.

k REAR GATE 41 e

9 i

l L

l 8 A L'T I MO R E.MD.

21213 p

WASHINGTON.

DC.

20500

~~

{

2-22-es 32061 assse E.z _ __s

.....l m n

.i gg (

U.P.S 1770-40302-S.0 30,1 -4 b)- 7100 1..i..

mi

..,.s

......w.

...c.....

[]

G.E. TE122030 8kEAKER 45.00

__0 I.

/4 D 1

v 1

3 l'

l 3

8 I

l 4

'a I

I e

7

?

4 I

MARKf 12172691 l

kn df d--

=

d B ACK ORDERSW1LL BE SHIPPE0 0N CONTINUATION INVOICE NOTE 0 ABOVE SUBTOTAL

-g o

1

[//0 h 4@

W $'

1& s& C/ #

21, y i

Lt v ivu L'

s

(

f-

, 9U, 9, r

g 5T '.i t, %0.V.

j l

% o sifis.;.

P R

l l

3's

'I"tND[','s"iLlLft"o)

.>...m..

ypf i

I I T O T A LJ !'

e/ 71_v '

TERYS NET 30 DAYS

_d l

40 GOODS uav et RtTURNF O WiTMOUT NOTE: A t ATE cwARcs Os t 5% ptR uONTH Ovw v. wit T E N AUT HORIZ ATION WiLL tE ADDE D TO ALL O AL ANCt5 0v t R 60 i

i e

g 8

Rt T UR'.t D **E RCw ANDfSE IS SUBJECT TO A GR ADUA ?(D RE STOCsuNG CH ARGE SILLINO PL E ASE P AY ON P ARTI AL EMiPMENTS

-==

WHENSILLIO.

I

( II!( l IT 1:!:1 U.l.RS.'. I R!l'S j

ap m w 6 :.m osiin esiu.a.:isi 1

H I 1. O A t ON 1 \\C IO P'-

h illi t \\ltl I Y tv.NI lif i Oil % \\(

l l' 51' ( l\\1 11:\\N%i Oll\\t!i,'N liMitl<\\ll l'l ( (iN 112(11 %

Mt tlDR A 4.1 NI F \\ l 811: *

.'l f r I:s t. it 1.l N RI N!%l(ll'%

%hlli 111 s i

_ _.