Text

I One First National P: ara Chicago Ilhno s C:mm:nw:alth Edison g-Address Rep!) to Post Office Bo'x 767 t

ChtCago llhnots. 60600 April 12, 1979

.r

  • Mr. James G. Keppler, Director Directorate of Inspection and Enforcement - Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Subject:

Dresden Station Units 1, 2 and 3 Quad-Cities Station Units 1 and 2 Zion Station Units 1 and 2 Response to IE Bulletin No. 79-03 "Longitudinal Weld Defects in ASME SA-312 Type 304 Stainless Steel Pipe Spools Manufactured by Youngstown welding and Engineering Company" NRC Docket Nos. 50-10/237/249, 50-254/265 and 50-295/304 Reference (a):

J. G. Keppler letter to B. Lee, Jr.

dated March 12, 1979 Daar Mr. Keppler:

Reference (a) transmitted IE Bulletin No. 79-03 regarding welding defects in certain longitudinally wolded pipe spools.

I In accordance with that bulletin, we have reviewed our Dresden, Quad-Cities, and Zion generating stations for the use of similar pipe spools.

A review was made of the design specifications and piping design tables for original con-struction and for modifications.

For all units iri these stations, the smaller piping sizes (generally less than 14 inch nerninal pipe i

size) were ASME SA-312 seamless pipe while the larger sizes were ASME SA-358 electric -fusion-welded pipe.

We conclude from this review that ASME SA-312 stainless steel pipe welded without filler metal is not present in the safety-related systems of units at the Dresden, Quad-Cities, or Zion nuclear pcwer stations.

l l

l

\\

79 06150j286 I Q 1

L

1 Commsnw:alth Edison NRC Dockot Neo. 50-10/237/249 50-254/265 50/295/304 l

l l

Mr. James G. Keppler: April 12, 1979 Please address any additional questions concerning this l

matter to this office.

i Very truly yours, pbt Cordell Reed Assistant Vice-President l

l lO l

O f