ML20150B465

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept CP-87-49 Re Solid State Safeguards Sys Internal Wiring Terminations.Initially Reported on 880111. Startup Work Packages 4146 & 4147 Initiated to Inspect for & Reterminate Unit 2 Sequencer Defective Wire Crimp Lugs
ML20150B465
Person / Time
Site: Comanche Peak  
Issue date: 03/11/1988
From: Counsil W
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-49, TXX-88296, NUDOCS 8803160446
Download: ML20150B465 (1)


Text

_ _ _

~

==

Log # TXX-88296 File #

10110 r

=

908.3 Ref. #

10CFR50.55(e) ft/ ELECTRIC.

March 11, 1988 wim.m c. coumii Execuent Vice Prendent U. S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 SOLID STATE SAFEGUARDS SYSTEMS (SSSS)

INTERNAL WIRING TERMINATIONS SDAR:

CP-87-49 (FINALREPORT)

Gentlemen:

On January 11, 1988, we informed you via our report logged TXX-88021 of a reportable deficiency involving a cmdition cited at another nuclear facility in which an open electrical connection on one crimp lug caused a failure in the Solid State Safeguards System (SSSS) load sequencing equipment.

This is a final report to provide the corrective action implementation schedule pursuant to the provisions of 10CFR50.55(e).

In our previous report (TXX-880?l) we informed you that Startup Work Packages (SWP) No. 4094 and 4095 were initiated to reterminate the deficient wire crimp lugs.

This was for Unit 1 only.

SWP 4146 and 4147 have now been initiated to inspect for and reterminate any Unit 2 sequencer defective wire crimp lugs.

The above stated activities are currently scheduled for completion by June 30, 1988, for Unit 1 and Unit 2 Hot Functional Test for Unit 2.

Supporting information will be available at the CPSES site for your inspector's consideration after these dates.

Very truly yours, IM4&

W. G. Counsil VIP /grr c-Mr. R. D. Martin, Region IV Ip.1 Resident inspectors, CPSES (3) i o 8803160446 880311 PDR ADOCK 05000445 S

DCD 400 North Oliw Street LBof Dallas, Texas 73201 e