Monthly Operating Rept for Jan 1988
ML20149J502
Person / Time
Site: Crane 
Issue date: 01/31/1988
From: Hukill H, Smyth C
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
C311-88-2017, NUDOCS 8802230087
Download: ML20149J502 (6)


Text

l \\$

OPERATIONS

SUMMARY

J ANUARY.1988 The unit ertered January operating at 100% power. The plant continued operating at 100% power until Janutry 31, 1988.

On January 31 power was reduced to approximately 75% to supp?rt repair of the "A" Main Feedwater (MFW) pump co6pling. The plant was returned to 100% power within 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />, i4AJOR_,53fETY REi.ATED MAINTENANCE During the month of Janviry, TPS Unit 1 perfortesd the following major maintenance:

Liquid 'J39te Disposal System pipe Rep'acement - During the month of January, a leaking pipe section t3ETEMalvesWDL-7517nd WDL-V-361 was replaced. The leak was a crack in a pipe section at a 90* elbow by diaphragm valve WDL-V-61.

In order te isolate the pipe and still have the capability to add borated water to the Makeup Tank (MU-T !!.. check valve WDL-Y-361 was required to be used as an isolation valve.

A Temporary Mechanical Modification was approved and a globe valve bonnet was installed on WDL-V-361 to isolate the piping.

Interference items (insulation, heat trace, conduit, etc.) were rencved, the piping drained and the piping cut out. The pipe was prepped and a new elbow and piping fit-up and welded in. All NDE inspections were satisf actory. Check valve WDL-Y-361 was restored to its original configuration and an Operational leak test of the affected piping was perforned with satisfactory result *

.nterference items were reinstalled and the system was returned to service.

Main Steam Yalve MS-Y Main steam atmospheric dump valve MS-Y-4B was remved f 6W service Tn January to repair seat leakage.

The valve operator was disconnected and the bonnet / operator removed from the valve body.

Inspection revealed c;ts across the valve seating surface.

The cuts were lapped out and the valve reassembled. Post Maintenance testing was parformed and ndnor leakage was detectec.

No further repairs to MS-Y-48 are scheduled.

l r

i B

-q' L

f l

l['

8802230087 880131 PDR ADOCK 05000289 R

DCD 4

I l

I

/.

v. v.

YT x.=

Ln

L w'

Oh e.

is l

Om COm>F Type 00>OMME9' E-3 Il 4 A Ei j 2 C E E E. R ". 5-y[j jg Duration egcw
y. E (Hours) r_c- -

"m 5 :'

  • h x :.. E.

E. 3

==

sc "F

3. 3 Reasim-e-

=

y-E o

}

Method ut 5

5.,

Shutting E

7 Down Reutor*

k v

E z

a m

C

6:

x e

2 o 5- --

a 5

o 3, 2 gm M

E zm Eg g

z

=

6 M

>zC w

c R

e.s - E System O>EE2 code 4

=

m

&6 c

2

. c 6 6 r

= -

g :- =Ec Eb g

-5 M

m

?

-gR$

Component

(($

Code $ &6

. y '

C 2

m

  • r b

2 O

.n.,

m emmem 0

E CE n

L 58EmL g>n En mn

=

= = 7

=b d qm

..,=V-m:

-r g

7 pq x vy :

5*S m g >2

=m 4

  • >E n r 5=

7 2. n, c-:

e-C 2*

aw x

v x.

=n

: a en =C en m.

s

-a n

r.

O'A E

Pa m

u m o a

n MF.k O

4 7

N, w

O C.,

Mgg d

I sz-e E

3 6 7' M

~i a

m=-5 Co mm e-s M L$

ta j

A 3

7 la W3 m

4<

7 7

CC-t e

r f'T -

N CC t

(4 m

l O

V t

w f

t l

-OPERATING DATA REPORT P

DOCKET NO.

50-289 D ATE _ 01-31-AS..

COMPLETED BY _C,W Smyth_ _

TELEPHONE.,(.7.11L94S-6511 OPERATING STATUS 1.

UNIT NAME:

THREE MILE ISLAND UNIT 1 l l

2. REPORTING PERIOD:

JANUARY

.1988. 1 I

3. LICENSED THERMAL POWER (MWT):

2535. I I

4. NAMEPLATE RATING (GROSS MWE).

871. l l

S. DESIGN ELECTRICAL RATING (NET MWE)-

819. I l

6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):

824. l l

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

776. I i

l__.______________________i 8.

IF CHANGES OCCUR IN (ITEMS 3-7) SINCE LAST REPORT, GIVE REASONS:

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)
10. REASONS FOR RESTRICTIONS, IF ANY:

THIS MONTH YR-TO-DATE CUMMULATIVE

11. HOURS IN REPORTING PERIOD 744.

744.

117601.

12. NUMBER OF HOURS REACTOR WAS CRITICAL 744.0 744.0 47264.5
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 1886.1 14 HOURS GENERATOR ON-LINE 744.0 744.0 46343.8
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 1874480.

1874480.

112362181.

17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 646084.

646084.

37514305.

18. NET ELECTRICAL ENERGY GENERATED (MWH) 610304.

610304.

35114586.

19. UNIT SERVICE FACTOR 100.0 100.0~

39.4

20. UNIT AVAILABILITY FACTOR 100.0 100.0 39.4
21. UNIT CAPACITY FACTOR (USING MDC NET) 105.7 105.7 38.2
22. UNIT CAPACITY FACTOR (USING DER NET) 100.2 100.2

.36.5

+

23. UNIT FORCED OUTAGE RATE 0.0 0.0 56.3 i
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH 3535Ee~nIahie~.~-! 5 EaTAr~ldpT.13E3 ~eh hiir~yI.iE335.E~4.385li.lif[_~ ~_~_~_~_~ ~_~ ~ ~_E'_~.~.I.~ ~ ~_~_ ~ ~ ~

~

_ _ _ _ _ _ _ _ _ _ _ _ Re fueli nn..Ju ne. _lL _19.382_6.4. days.RBl _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.. _ _ _ _

25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: _ _ JV8_ _. _

EV, -

AVERAGE DAILY UNIT POWER LEVEL' DOCKET NO.

50-289 bNIT TMI-i DATE 01-31-88' COMPLETEDBY_]C_.3]_"$jjj{_

~

TELEPHONE _(7J2)..,9_43-S.5 jib MONTH:

JANUARY-DAY AVERAGE DAILY-POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWE-NET)

(MWE-NET) 1 829.

17 819.

2 833.

18 824.

3 832.

19 825.

4 827.

20 826.

5

829, 21 823.

6 821.

22 825.

7 814.

23 830.

8 813.

24 828.

9 819.

25 827.

to 816' 26 828.

11 807.

27 828.

12 810.

28

.824.

13 821.

29 823.

14 822.30-824.

15 810.

31 764.

16 810.

's i

i k

I i

i i

i

_y-w

.-m.

r,q i

REFUELING INFORMATION REQUEST 1.

Nane of Facility:

.Three Mile Island Nuclear Station, Unit 1 i

2.

Scheduled date for next refueling shutdown:

June 17,1988 (7R) 3.

Scheduled date for restart following refueling: August 19,1988 (7R) 4 Will refueling or' resumption of operation thereaf ter require a technical specification change or other license amendment?

Yes (For 7R)

If answer is yes, in general, what will these be?

Basic Refueling Report.

If answer is no, has the reload fuel design and core configuration been reviewed by your Plant Safety Review Committee to determine whether any unreviewed safety l

questions are associated with the core reload (Ref.10 CFR Section 50.59)?

t l

If no such review has taken place, when is it scheduled?

To be determined.

l S.

Scheduled date(s) for submitting proposed licensing action and supporting information: April 1,1988.

t 6.

Important licensing considerations associated with refueling, e.g. new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new cperating procedures:

None f

i 7.

The number of fuel assemblies (a) in the core, and (b) in the spent fuel storage pool:

(a) 177 (b) 284 l

8.

The present licensed spent fuel pool storage capacity and the size of any

}

increase in licensed storage capacity that has been requested or is planned, in number of fuel assemblies:

r The present licensed capacity is 752. There are no planned increases at this time.

l 9.

The projected date of the last refueling that can be discharged to the f

spent fuel pool assuming the present licensed capacity:

r r

1991 is the last refueling discharge which allows full core off-load capacity (177 fuel assemblies).

I f

P

GPU Nuclear Corporation Nuclear

, oms :=

Middletown, Pennsylvania 17057 o191 717 944 7621 TELEX 84 2386 Writer's Direct Olal Numbec February 16, 1988 C311 2017 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D.C.

20555

Dear Sir:

Three Mile Island.!cclear Station, Unit I (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 Monthly Operating Report Janua ry, 1988 Enclosed please find two (2) copies of the January,1988 Monthly Operating Report for Three Mile Island Nuclear Station, Unit-1.

Sincerely,

. D.

ill Vice President & Director, TMI-l HDH: JAR:spb cc:

W. Russell, USNRC R. Conte, USNRC Attachments 0015C f5 s t GPU Nuclear Corporation is a subsidiary of the General Public Utilities Corporation