ML20149J487

From kanterella
Jump to navigation Jump to search
Event Tracking Sheet of 960408 Event Re Crane Valves. Provides Update on Continuing Efforts to Evaluate Whether Erroneous Data to Set Torque Switches for MOVs Supplied to Licensees During mid-1980s.No Contractural Evidence Found
ML20149J487
Person / Time
Site: Prairie Island  
Issue date: 06/30/1997
From: Gray K
NRC
To:
Shared Package
ML20149J390 List:
References
FOIA-97-177 NUDOCS 9707280238
Download: ML20149J487 (8)


Text

-

~ -. -

=

1, EVENT FOLLOW-UP ASSIGNMENT SHEET No Sort Specifled QUERTP "HODGE" $ Assigned To & Assigned Date >= 04/08/96 & Assigned Date <= 04/08/96 & " CRANE" $ Plant Name ASSIGNMENT DATE:

04/08/96 ASSIGNED TO:

HODGE V.

PLANT & UNIT:

CRANE-ALOYCO EVENT DATE:

04/08/96 50.72 REPORT NO:

0 DAILY REPORT DATE:

01/17/95 OTHER REPORT:

EVENT DESCRIPTION CRANE VALVES PROVIDES UPDATE ON CONTINUING EFFORTS TO EVALUATE WHETHER ERRONEOUS DATA TO SET TORQUE SWITCHES FOR MOVs WAS SUPPLIED TO LICENSEES DURING MID-1980s. NO CONTRACTURAL EVIDENCE FOUND YET. SEE LOG #94150/95007 ET AL.

SPECIFIC FOLLOW-UP ASSIGNMENT DETERMINE DETAILS, EVALUATE SAFETY $1GNIFICANCE AND GENERIC IMPLICATIONS.

SAFETY SIGNIFICANCE:

SIGEVENT AO OTHER OR ERIEFING:

EVENT FOLLOW-UP REPORT: INFORMAL CLOSEOUT DESCRIPTION PART 21 #95 005 FOR CLOSECUT INFORMATION, SEE PART 21 #95 006 (EVENT DATE 1/23/95).

REGULATORY ASSESSMENT: This report does not describe a safety problem but does describe misplaced analytical expectations for motor-operated valve operation based on an inadequate model. This model, the first used by Crane to support its customers, has been improved over time, partly in response to NRC generic conmiunications.

Th3 panel agrees that this report does not meet the notion of deviation intended by 10 CFR Part 21 and closes it cs an other event.

SUNMARY ASSESSMENT: Crane Valves Nuclear Operations (Crane; formerly Crane Aloyco) supplies analytical support fte motor operated valves to the nuclear power industry. At first it used its original model for this support.

In response to NRC Generic Letter 85 03 and supplements, trane customers specified design parameters outside the triginal model, pronpting Crane to derive a current model. The Part 21 concern arose because the current model ru ults differed from the original model results. Crane contacted its customers, holds itself available to s@ port any customer in better understanding and predicting motor-operated valve behavior, provided its customers with current-model analyses as requested, and concludes that data supplied in prior analyses does not constitute a reportable item under Part 21. The Mechanical Engineering Branch concurs that this issue is r:szived.

~ CLOSEOUT / FINDINGS: This issue, called Crane torque data for short (94150, 94292, 95005, and 95 U 4) has been confused with another issue called yoke shim for short (94254, 95006, 95007, and 95035). Severa of the reports in each issue refer to log numbers in the other issue. The yoke shim issue is closed in ETS (C"ane Aloyco SUBMITTED BY: HODGE V.

DATE: 11/14/96 I

-APPROVED BY:

R. DENNIG DATE: 11/15/96 CLOSEOUT. NARRATIVE ENTERED:

K. Gray DATE: 11/21/96 ETS 01 9707200238 970722 Page:1 06/30/97 PDR FOIA FOWLER 97-177 PDR J

1

),

EVENT FOLLOW-UP ASSIGNMENT SHEET No Sort Spectfied QUERY > "HODGE" $ Assigned To & Assigned Date >= 04/08/M & Assigned Date <= 04/08/96 & " CRANE" S Plant Name CLOSEOUT DESCRIPTION (Continued) cesignment to N. Hunemuller 012395, closed 081696).

All the tog nunbers for the Crane torque data issue are briefly described here. References to other tog numbers should be disregarded. Report 94292 is not marked closed, but technical review of the issue by the Mechanical I

Engineering Branch applies to the whole set.

i 94150 CRANE VALVE /ALO1CO REPORTS CONDUCT OF EVALUATION TO DETERMINE IF DATA SUPPLIED IN MID-1980s AS CRANE-ALOYC0 "0TC" REPORTS WAS USE TO SET TORQUE SWITCHES IN MOVs. DATA MAY HAVE BEEN USED BEYOND INTENDED SCOPE. SEE l

LOG # 94254/ 94292/ 9500.V 95024.

PEC8 Consnents on 94150: in a Ltr dtd May 16, 1994, Crane Valves Nuclear Operations (Crane) advises that they are j

undertaking this Part 21 ovaluation. They have generated over 600 contractual reports relating to this issue.

EME8 closed 94150 as CTBI, stating that the issue regards weak link analysis for Movs and continuing to track th3 issue under 94254 (which actually belongs to the yoke shim issue).

l 94292 - CRANE VALVES NUCLEAA OPERATIONS REPORTS INVESTIGATION TO DETERMINE IF DATA SUPPLIED IN MID-1980 WAS USED BY LICENSEES TO SET TORQUE SdITCHES IN MOVs IS CONilNUING. NO EVIDENCE UNCOVERED TO DATE. SEE LOG # 94150.

I PEC8 Consnents on 94292: In a (tr dtd Oct 28, 1994, Crane reports not uncovering any contractual evidence of hiving supplied erroneous dets to utilities.

EME8 closed 94294 as CTBI, coritinuing to track the issue under 95007 (which actually belongs to the yoke shim issue).

95005 CRANE VALVES PROVIDES O'DATE ON CONTINUING EFFORTS TO EVALUATE WHETHER ERRONEOUS DATA TO SET TORQUE SWITCHES FOR MOVs WAS SUPPLIEli TO LICENSEES DURING MID 1980s. NO CONTRACTUAL EVIDENCE FOUND YET. SEE LOG #

94150/95007 ET AL.

TECB consnents on 95005: This log number is the present assignment. In a ltr dtd Dec 28, 1994, Crane repeats the (tr dtd Oct 28, 1994.

95024 CRANE VALVES PROVIDES FIllAL REPORT REGARDING ANALYSES TO DETERMINE REQRD THRUST FOR MOVs IN RESPONSE TO GLs 85-03/89-10. CONCERN AROSE DUE TO DIFFERENCES IN CURRENT MODEL RELATIVE TO ORIGINAL MODEL. DIFF IDENTIFIED.

SEE LOG #94150.

PEC8 Consnents on 95024: In a ltr dtd Jan 12, 1994, Crane reports that their utility customers requested tnalytical support to determire the required thrust for safety related valves for purposes of responding to NRC Generic Letter 85 03 and supplements. These requests specified design conditions containing parameters, for saample, extended structure mass, extended structure center-of gravity, AME and AISC allowable stress, and dynamic loading, that are not in the original analysis model. The original potential Part 21 concern arose because the results generated. from the current model, which supports analyses containing these additional parameters, appear different from the results obtained using the original model.

Crane claims to have supplied its customers with the analyses they requested. When the scope of these analyses came into ouestion, Crane contacted its customers and holds itself available to support any customer in better understanding and predicting MOV behavior. In addition, trane provided its customers, on request, with an cnalysis using the current model. Lastly, Crane concludes that data supplied in prior analyses does not constitute a reportable Itom under Part 21.

EMEB closed 95024 as CTBlo continuing to track the issue under 94292. The ETS disposition for 95024 refers to ths G;G seignment.

Th3 ETS disposition for 95006 refers to 95024: EMEB reviewed 95024, charactertred it as Crane's weak link cnalysis, and initially believed that 95006 was related to 95024. On further review, however, EME8 determined this yoke / adapter plate weld issue (the yoke shim issue) has been adequately addressed.

ETS 01 Page:2 06/30/97

.i.*

EVENT FOLLOW-UP ASSIGNMENT SHEET No Sort Specified QUERY > "HODGE" $ Assigned To & Assigned Date >= 04/08/96 & Assigned Date <= 04/08/96 & " CRANE" $ Plant Name CLOSEOUT DESCRIPTION (Continued)

EME8 has reviewed this sunnery of the many log ranbers and concurs that the Crane torque data issue is resolved.

FINAL PANEL ASSESSMENT: The panel considered the significance of this issue to be consistent with an other event. It was judged to be generic.

1 1

ETS-01 Page:3 06/30/97

REGION MORNING REPORT PAGE 2 JANUARY 17, 1995 Licensee / Facility:

Notification:

Part 21 Database MR Number: H-95-0006 Crane-Aloyco (Crana Valve)

Date: 01/17/95

Subject:

Reportable Event Number: N/A Discussion:

VENDOR: CRANE-ALOYC0 (CRANE VALVES)

PT21 FILE NO: 95005 DATE OF DOCUMENT: 12/28/94 ACCESSION NUMBER: 9501040173 SOURCE DOCUMENT: PART 21 REVIEWER: EMEB: SCARBROUGH CRANE VALVES PROVIDES UPDATE ON CONTINUING EFFORTS TO EVALUATE WHETHER ERR 0NEOUS DATA TO SET TOROVE SWITCHES FOR MOVs WAS SUPPLIED TO LICENSEES DURING MID-1980s. NO CONTRACTURAL EVIDENCE FOUND YET. SEE LOG # 94150 ET AL.

Regional Action:

Contact:

l

1 PRIORITY ATTENTI0i1 REQUIRED MORNING REPORT - REGION JANUARY 20. 1995

?

Licensee / Facility:

Notification:

Part 21-Database MR Number: H-95-0009 Crane-Aloyco (Crane Valve)

Date: 01/20/95

Subject:

Reportable Event Number: N/A Discussion:

VENDOR: CRANE-ALOYC0 (CRANE VALVE)

PT21 FILE NO: 95006 DATE OF DOCUMENT: 08/30/94 ACCESSION NUMBER:

SOURCE DOCUMENT: Part 21 REVIEWER: EMEB: R.WESSMAN CRANE VALVES / NUCLEAR OPERATIONS REPORTS FAILURE OF 10" FIGURE 63174 VALVE AT WELD JOINING YOKE & ADAPTER PLATE & MORE CATASTROPHIC FAILURE TO OTHER PARTS DUE TO INCLUSION OF SHIMS CONTRARY TO DWG..PART OF ORDER TO WEST IN EARLY 1970s. SEE LOG #95007.

Regional Action:

Contact:

b i

i

REGION MORNING REPORT PAGE 2 JANUARY 20, 1995 Licensee / Facility:

Notification:

Part 21 Database MR Number: H-95-0010 Crane-Aloyco (Crane Valve)

Date: 01/20/95

Subject:

Reportable Event Number: N/A Discussion:

VENDOR: CRANE-ALOYC0 (CRANE VALVE)

PT21 FILE NO: 95007 DATE OF DOCUMENT: 12/28/94 ACCESSION NUMBER: 9501040170 SOURCE DOCUMENT: Part 21 REVIEWER: EMEB: R. WESSMAN CRANE VALVES / NUCLEAR OPERATIONS PROVIDES INTERIM REPORT REGARDING INVEST OF VALVE FAILURE AT PRAIRIE ISLAND. INFO RCVD FROM OTHER PLANTS. FINAL REPORT EXPECTED IN 30 DAYS. SEE LOG #95006.

Regional Action:

Contact:

f G/2

REGION MORNING REPORT PAGE 4 JANUARY 27, 1995 Licensee / Facility:

Notification:

Part 21 Database MR Number: H-95-0033 Crane-Aloyco (Crane Valve)

Date: 01/27/95

Subject:

Reportable Event Number: N/A Discussion:

VENDOR: CRANE-ALOYC0 (CRANE VALVE)

PT21 FILE NO: 95024 DATE OF DOCUMENT: 01/12/95 ACCESSION NUMBER: 9501200336 SOURCE DOCUMENT: Part 21 REVIEWER: EMEB: SCARBROUGH CRANE VALVES PROVIDES FINAL REPORT REGARDING ANALYSES TO DETERMINE REORD THRUST FOR MOVs IN RESPONSE TO GLs 85-03/89-10. CONCERNAROSE DUE TO DIFFERENCES IN CURRENT MODEL RELATIVE TO ORIGINAL MODEL. DIFF IDENTIFIED.

SEE LOG #94150.

Regional Action:

Contact:

t

REGION MORNING REPORT PAGE 6 JANUARY 31, 1995 Licensee / Facility:

Notification:

Part 21 Database MR Number: H-95-0044 Crane-Aloyco (Crane Valve)

Date: 01/31/95

Subject:

Reportable Event Number: N/A Discussion:

VENDOR: CRANE-ALOYC0 (CRANE VALVE)

PT21 FILE N0: 95035 DATE OF DOCUMENT: 01/27/95 ACCESSION NUMBER:

SOURCE DOCUMENT: Part 21 REVIEWER: OECB: A. CHAFFEE CRANE VALVES / NUCLEAR OPERATIONS PROVIDES FINAL REPORT REGARDING FAILURE 0F WELDS JOINING YOKE & ADAPTER PLATE ON 10"/12" GATE VALVES. AFFECTED LICENSEES IDENTIFIED & INFORMED. SEE LOG #95006/95007.

Regional Action:

Contact:

i N/0