Special Rept 97-001:on 970704,radiation Monitor R-60C Declared Inoperable Due to Monitor Normal Light Not Being Lit & Erroneous Data Indicated on Plant Computer.Mandatory LCO Written for Monitor R-60C
ML20149G235
Person / Time
Site: Farley 
Issue date: 07/18/1997
From: Dennis Morey
SOUTHERN NUCLEAR OPERATING CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9707230067
Download: ML20149G235 (3)


Text

i-

~

Dan Mmy S:uthern Nuclear Vice President Opuating Company Farley Project P.O. Box 1295 Birmingham. Alabama 35201 Tel 205.992.5131 k

SOUTHERN h COMPANY July 18,1997 Enery to Serve YourWorld" Docket No.:

50-348 10 CFR 50.4 i

U.S. Nuclear Regulatory Commission

. ATTN: Document Control Desk Washington,DC 20555 Joseph M. Farley Nuclear Plant - Unit 1 Snecial Renort No.97-001. Inonerable Radiation Monitor R-60C Ladies and Gentlemen:

In accordance with the requirements of Technical Specification 3.3.3.1, the enclosed Special Report No.97-001, Unit 1, is submitted.

If you have any questions, please advise.

i Respectfully submitted, 1

Dave Morey MJA/ cit:sr-R-60C. doc Enclosure

\\

cc: Mr. L. A Reyes, Region II Administrator gp) j Mr. J. I. Zimmerman, NRR Project Manager Mr. T. M. Ross, Plant Sr. Resident Inspector l

9707230067 970718 PDR ADOCK 05000348:

S PM mittillmII!alflitill

c2cesa,

ENCLOSURE Joseph M. Farley Nuclear Plant, Unit 1 Special Report 97-001 Inonerable Radiation Monitor R-60C l

l l

l l

i ENCLOSURE' i

Snecial Renort for Inonerable Radiation Monitor R-60C l

This Special Report is being submitted due to the Unit I radiation monitor R-60C (Main Steam Relief and Atmospheric Steam Dump Discharge) not being restored to operable status j

within the time required by Technical Specification (TS) 3.3.3.1-TS 3.3.3.1 requires the

' monitor to be restored to operable status within 7 days or submit a Special Report within the next 14 days following the event.

e

. At 0050 on July 4,1997, during performance of FNP-1-STP-1.0, " Operations Daily and Shift

- i L

Surveillance Requirements," radiation monitor R-60C (Main Steam Relief and Atmospheric

- Steam Dump Discharge) was declared inoperable due to the monitor nonnal light not being lit and erroneous data indicated on the plant computer. A mandatory Limiting Condition of

~

Operation (LCO) was written for R-60C requiring restoration to operable status by 0050 on July 11,1997, and a work order was generated to repair R-60C.

Maintenance troubleshooting isolated the problem to the detector. Due to the detector.

l location (main steam valve room roofin close proximity to steam generator safety relief valve discharges), repair of the monitor is a potential safety concern should any relieflift during the repair effort. Therefore, repair of the monitor should be performed only under cold shutdown -

1 conditions to ensure personnel safety. R-60C is scheduled to be repaired during the next

- outage of sufficient duration where the plant will be in cold shutdown. TS action statement i

requirements are being met for radiation monitor R-60C.

AdditionalInformation The following Special Reports have been submitted for similar radiation monitors exceeding the LCO restoration time due to inaccessibility with the unit operating at power:

Special Report 88-023-00 (Unit 1) - Radiation Monitor R-60A Inoperable For More Than Seven Days-

?

Special Report 90-006-01 (Unit 2) - Radiation Monitor Inoperable For More Than Seven Days Special Report 90-007-00 (Unit 2)'- Radiation Monitor Inoperable For More Than Seven Days i