ML20148K605

From kanterella
Jump to navigation Jump to search
Responds to Generic Ltr 88-03.Requirement for Once Per Shift Check of Auxiliary Feedwater (AFW) Piping Temps Committed to in IE Bulletin 85-001 Confirmed.Removal of Lagging from AFW Piping Per IE Info Notice 84-06 Noted
ML20148K605
Person / Time
Site: Point Beach  
Issue date: 03/23/1988
From: Fay C
WISCONSIN ELECTRIC POWER CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CON-NRC-88-026, CON-NRC-88-26, REF-GTECI-093, REF-GTECI-NI, TASK-093, TASK-93, TASK-OR GL-88-03, GL-88-3, IEB-85-001, IEB-85-1, IEIN-84-06, IEIN-84-6, VPNPD-88-170, NUDOCS 8803310216
Download: ML20148K605 (2)


Text

,

1 G

L Wisconsin Electnc poua couran 231 W MICHIGAN.P.O BOX 2046, MILWAUKEE.W153201 (414)221-2345 VPNPD-8 8 -17 0 NRC-8 8-02 6 March 23, 1988 U.

S.

NUCLEAR REGULATORY COMMISSION Document Control Desk j

Washington, D.C.

20555 Gentlemen:

1 DOCKET NOS. 50-266 AND 50-301 RESPONSE TO GENERIC LETTER 88-03 RESOLUTION OF SAFETY ISSUE 93 STEAM BINDING OF AUXILIARY FEEDWATER PUMPS POINT BEACH NUCLEAR PLANT UNITS 1 AND 2 Generic Letter 88-03 dated February 17, 1988 perpetuated actions taken as a result of IE Bulletin 85-01, "Steam Binding of Auxiliary Feedwater Pumps."

We responded to that bulleti!. by letter dated February 25, 1986..In that letter we committed to once per Fhift monitoring of AFW piping temperatures and j

implementation of procedures for detecting steam binding and restoring AFW pumps to service.

i This letter is to confirm that a once per shift check of AFW piping temperatures is required at PBNP and is included in the Point Beach Fuclear Plant Unit 1 Turbine Auxiliary Operator Logs.

This check will continue to be made.

Abnormal Operating Procedure AOP-2C, Auxiliary Feedwater Pump Steam Binding or Overheating, addresses recognition of potential and actual steam binding and restoration actions at PBNP and will be maintained.

In addition to the above actiot.s, as a' result of our review performed for IE Information Notice 84-06, "Steam Binding of Auxiliary Feedwater Pumps," we removed lagging from portions of AFW piping inside containment.

This increases heat loss should relatively hot main feedwater leak ay AFW check valves.

Thus should leakage occur, the water is cooled prior to reaching the AFW pumps, rainimizing or eliminating the possibility of water flashing to steam in AFW pumps.

8903310216 880333 O

PDR ADOCK 05000266 I

i p E

PDR

'o Document Control Desk March 23, 1988 Page 2 If you have any questions or require additional information, please contact us.

Very truly yours,

/

W/

Cc s -2 C.

W.

Fay Vice President Nuclear Power Copies to NRC Regional Administrator, Region III NRC Resident Inspector Subscribed and sworn to before me this OyO day of March, 1988.

% Q l eto c hd vo.

/

Notary Public, State'of Wisconsin My Commission e.pires I-27'30

_