ML20148H023

From kanterella
Jump to navigation Jump to search
Responds to 781004 NRC Ltr Re Violations Noted in Inspec Rept 50-368/78-23.Corrective Actions:Use of sign-off Steps to Return HPSI Pump Hand Switches to Normal,Install Fire Signs on Fire Doors
ML20148H023
Person / Time
Site: Arkansas Nuclear  
Issue date: 10/24/1978
From: David Williams
ARKANSAS POWER & LIGHT CO.
To: Madsen G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20148G977 List:
References
2-108-15, NUDOCS 7811130327
Download: ML20148H023 (2)


Text

O

. (a.

i

! l fl ARKANSAS POWER & LIGHT COMPANY POST OFFICE BOX 551 UTTLE POCX, ARKANSAS 72203 (5011371-4000

{ l l l October 24, 1978 i !

2-108-15 l

Mr. G. L. Madsen, Chief Reactor Operations and Nuclear Support Branch United States Nuclear Regulatory Commission Office of Inspection and Enforcement Region IV.

611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011

Subject:

Arkansas Nuclear One - Unit 2 Docket No. 50-368 License No. NPF-6 Inspection Report No. 50-368/78-23 (File:

2-0232)

Gentlemen:

The subject inspection report identified three (3) infractions and one (1) deviation from comnitment to the Commission.

Our response to these items is provided below:

Item 1:

Contrary to the requirements of T.S. 3.5.3 for Mode 3 operation, 3 HPSI pump

. handswitches were found to be in the " Pull-to-Lock" position.

Two of the HPSI pump handswitches were immediately returned to the " Normal-After-Stop" status to conform.to the Technical Specifications requirements.

The-failure to return the handswitches to normal was a result of inadvertent omission of that step in the controlling procedure (OP 2102.03) in use at that time.

That procedure has since been revised to include sign-off steps to return the HPSI pump handswitches to normal.

Plant controlling procedures 2102.02, 2102.03, and 2102.10 were reviewed in their entirety for similar errors.

Some unrelated adjustments were made based on these reviews.

We feel we are in compliance with Technical Specifications, and this is not a recurrent problem.

7 811 13 0 3 A7 MEMBEA MCCLE SOUTEUTILITIES SY STEM

.*