ML20148C437

From kanterella
Jump to navigation Jump to search
Forwards Bailey 862 Solid State Logic Module Bimonthly Failure Rept, Dtd 880205.Rept Covers Both 1E & non-1E Modules & Summarizes Inservice Failures Per Month by Class, Assembly Type & Failure Type
ML20148C437
Person / Time
Site: Hope Creek 
Issue date: 03/16/1988
From: Miltenberger S
Public Service Enterprise Group
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
NLR-N88042, NUDOCS 8803220390
Download: ML20148C437 (6)


Text

..

j?

Public Service Electric and Gas Cornpany Steven E. Miltenberger Public Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609 339-4199 Vice President -

March 16, 1988 NLR-N88042 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

BI-MONTHLY BAILEY FAILURE REPORT HOPE CREEK GENERATING STATION DOCKET NO. 50-354 Pursuant to commitments contained in the Public~ Service Electric and Gas Company (PSE&G) letter from C. A. McNeill, Jr. dated October 15, 1986, attached please find the Bailey 862 Solid State Logic Module (SSLM) Bi-Monthly Failure Report for the Hope Creek Generating Station (HCGS).

This report covers both lE and non-lE 4

modules and summarizes inservice failures per month by class, assembly type and failure type.

With respect to the last two month period, December 1987 - January 1988, 4 Bailey 862 SSLM failures were identified that had an affect on the circuit in which they were used.

These failures are discussed in the attached Bi-Monthly Report.

This constitut<a the last Bi-Monthly Report.

Any additional failures will be included in the Final Bailey Report, to be submitted prior to startup from the first refueling outage.

Should you have any questions on this transmittal, do not hesitate to call.

Sincerely,

[

l l

Attachment i

DO K O R

g R

l

Document Control Desk 2

03-16-88 C

Mr.

G.

W.

Rivenbark USNRC Licensing Project Manager Mr.

R. W.

Borchardt USNRC Senior Resident Inspector Mr.

W.

T.

Russell, Administrator USNRC Region I Mr.

D. M.

Scott, Chief Bureau of Nuclear Engineering Department of Environmental Protection 380 Scotch Road Trenton, NJ 08628

1 l

4 i

BAILEY 862 I

SDLID STATE LOGIC M0DULE l

B1-MONTHLY FAILURE R E P 0 R-T e

HOPE CREEK GENERATING STATION FEBRUARY 5,1988 I

t 1

HOPE CREEK GENERATING STATION BAILEY SOLID STATE LOGIC MODULE FAILURES FOR DECEMDER 1987 AND JANUARY 1988 4 Modules Failures - There were 4 SSLM failures which occurred in the two month beginning December 1, 1987 through January 31, 1988.

SSLM Failure Rate Information 1.06% per year failure rate

1) Based upon data f rom Decembe r 1987 and January 1988, with 3 and 1 f ailures respectively, for a total l

population of 2258 modules.

2) The projected annual failure rate is based Upon bi-monthly data as p re se nted in a le tte r f rom C. A.

McNe ill, Jr. to Dr.

T. E. Murley, dated October 15, 1986 (NLR-N86148).

- 1.72% per year failure rate based upon 39 failures over the last 12 month period.

l l

l 1

BAILEY SSLM FAILURE

SUMMARY

FOR 12/87 THROUGH 1/88 Record #:

12/87-1 Assembly:

DC652 Location:

5 7 S/N: 0384 Fail Date:

12/14/87 Work Order Number:

WRA-0065083 System:

STATION SERVICE WATER Class: 1E Description of Failure:

MODULE INPUT BUFFER NO.

1 FAILED TO THE LOW STATE Affect on System:

MODULE FAILURE RESULTED IN FALSE "MOTOh MALFUNCTION DETHCTION" SIGNALS (FLASHING STOP LIGHT) FOR STATION SERVICE WATER PLMP DP502.

Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERATION

==============================
=a==n==.-===========

Record #:

12/87-2 Assembly:

BC653 Location: 4-64 S/N: 1406 Fail Date:

12/20/87 Work Order Numi,;er :

AOO47251 System:

EXTRACTION STEAM pliss: NON-1E Description of Failure:

MODULE FAILURE CAUSED OUTPUT BUFFER NC, 8 A(ID MLACRY B TO ASSUME INCSRRECT LOGIC STATES.

Affect on System:

MODULE FAILURE CAUSED SOLENOID VALVE 1-AF-GV-15ebA TO JE-ENERGIZE, SUBSEQUENTLY CAUSING LOSS OF LEVEL cot,/ROL AND 76IP OF FEEDWATER HEATER A3E105 (NO. 5).

Time in LCO: LCO NOT ENTERED Couno During: NOPMAL OPERATION

======================,u=======a=======e===es=========,=======

Record #:

12/97-3 Assembly:

CC652 Location:

4-o-

L S/N: 0908 Fail Date:

12/21/87 Work Order Nunter :

E71208082 System:

FILTRATION,RECIRC., L VENT Llass' 1E Description of Failure:

MODULE LOGIC INPUT NO. 2 FAILED TO THE iflGH STATE.

Affect on System:

MODULE FAILURE RESULTED IN FALSE "LOW FLOW" INDICkTION ON FI.TCATION, RECIRCULATION AND VENTILATION SYSTEM (FRVS) RECIRCULATIOt' F AH CV213:

Time in LCO: LCO NOT ENTERED Found During: NORt1AL OPER4TIbw

=============p==============================.:====-,===:=====r

Record #:

1/88-1 Assembly:

AC652 Location: 9-8-13 L'N*.

1859 Fail Date:

01/02/88 Work Order Number:

4003160%

System:

CONTNMT ATMOSPHERE CNTRL Clas-: 1E Description of Failure:

MODULE OUTPUT BUFFER NO. 2 FAILED TO THE "LOW" (DiEN) STATE.

Affect on System:

THE MODULE FAILURE RESULTED IN LOSS OF "CLOSED" STATUG ;MDICAT N ON CONTAINMENT ATMOSPHERE CONTROL VACUUM RELIEF VAL JE i V-%27.

Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERNTION

====================================================.,4=s.-

=============,a END OF RECORDS

- u a.

L

-6 A

n s

BAILEY 862 SSLM FAILURE RATE

~

12 MONTH ROLLING AVERAGE ENDINd JAN 88 i

10 1

3 -

i 4

c O

2 7 -

e a

6 -

1 L

o

~3 E

5 -

3 4.2 w

)

3.9 1

4 -

37 3.5 3.5 l'^

I 3 _

  • %.9 3

m

]

_Ja h-2 -

1 O

i i

i i

i i

i i

i i

FEB MAR APR MAY JUN JLY AUG SEP OCT NOV DEC JAN X

ROLLING AVERAGE

.,.