_. ~ _ _ _ _.... _ _ _ _ _. _ _. ~. _. _. _ _ _. -. _.. _ _..... ~..... _ _ _.. _. _ _ _. _ _. _ ~..... _ _ _...
REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY)
L: NR-0545-D-101 E DATE: May 2, 1997 PAGE 1 OF 3 DEVICE TYPE:
Ionization Smoke Detector MODEL:
9.0 V Series, 120 V/AC Series I.
MANUFACTURER / DISTRIBUTOR:
Coleman Safety and Security Products, Inc.
l (Formerly Seatt Corporation) 2820 Thatcher Road Downers Grove, IL 60515-1580 SEALED SOURCE MODEL DESIGNATION:
Amersham Model AMM-1001H l
NRD Model A-001 l
l ISOTOPE:
MAXIMUM ACTIVITY:
Americium-241 1.0 microcurie (37 kBq) l l
LEAK TEST FREOUENCY:
Nct Required-PRINCIPAL USE:
(P). Ion Generator, Smoke' Detector CUSTOM DEVICE:
YES X
NO i}.
1
(
i t
9705130413 97050P.
POR RC PDR SSD i
-. ~
~....-
I 1
i REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES i
-SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY) i hot: NR-0545-D-101-E DATE: May 2, 1997 PAGE 2 OF 3 i
1 l
l DEVICE TYPE:
Ionization Smoke Detector i
i i
DESCRIPTION:
i 3
The Models 9.0 V and 120 V/AC Series devices are ionization type smoke detectors containing a maximum of 1.0 pCi (37 kBq) of i
Each of the series use the same ionization chamber.
The
)
models in the series are essentially similar in design and construction with size and cosmetic differences being the primary variations between the series.
The models in the 9.0 V series are powered by a 9 volt DC battery while the models in the l
120 V/AC series are powered by a 120 AC line voltage.
Models in the 120 V/AC series can come equipped with or without a battery back-up.
The external dimensions of the models within the series range from 4" (101.6 mm) to 5" (127 mm) in circumference and 1" l
(25.4 mm) to 1.5" (38.1 mm) in height.
The circuit board is common between'all models with exception of added space for i-additional features, i.e.,
escape light, alarm silence, etc.
The 4
i chambers all incorporate either a NRD or Amersham source with l
maximum activity of 1.0 mci (37 kBq)..
'Although these devices l-were originally approved for a maximum activity of 1.3 yCi (48.1 kBq), - Coleman Safety and Security Products, Inc. (formerly Seatt Corporation) never manufactured or intends to manufacturer i
at an activity' greater than 1.0 pCi (37 kBq).
Coleman Safety and-Security Products, Inc. distributes the smoke detectors under various marketing names.
However, the labels will bear Coleman's i
i license number.
4 Coleman Safety and Security Products, Inc. previously distributed i
these detectors under numerous separate model numbers.
For marketing purposes, Coleman will now distribute the detectors under the 9.0 V and 120 V/AC Series designations.
1 The elimination of the multiple models numbers does not imply any changes to the ion chamber or design.
\\
~
REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY)
NO.: NR-0545-D-101-E DATE: May 2, 1997 E_ AGE 3 OF 3 DEVICE TYPE:
Ionization Smoke Detector EEFERENCES:
The following supporting documents for the Model 9.0 V and 120 V/AC Series smoke detector devices are hereby incorporated by reference and are made a part of this registry document.
Seatt Corporation's letters dated October 12, 1995, November 22, 1995, May 14, 1996, and November 25, 1996, with enclosures thereto.
Seatt Corporation's facsimiles dated June 7, 1996, June 10, 1996, June 11, 1996, June 13, 1996, June 14, 1996, and August 29, 1996, with enclosures thereto.
ISSUING AGENCY:
U.S. Nuclear Regulatory Commission I ucvk Date:
May 2, 1997 Reviewer:
y Dougl6s A. Broaddus Date:
May 2, 1997 Concurrence:
M
'sEeven L.
Baggett