d>

Thomas J, Martin Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 201/430 8316 vice President November 9, 1978 Mr. Boyce H.

Grier, Director U.S.

Nuclear Regulatory Commission Office of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

NRC INSPECTION REPORT NO. 50-311/78-26 SUPPLEMENTAL INFORMATION NO. 2 UNIT SALEM NUCLEAR GENERATING STATION Pursuant to our letter of October 18,1978 in response to the sub-ject inspection report, we wish to advise your office of the fol-lowing supplemental information:

As a result of a question raised by J.

Durr, Reactor Inspector, of your staff regarding the slope of one (1) of the reworked fil-let welds, the UE&C Quality Control Department was directed to perform a re-inspection of all 171 reworked field welds.

This re-inspection revealed that seventy-eight (78) welds still failed to meet the 2x1 leg size requirement given on the applic-able drawing detail.

Examination of the subject welds indicated that both legs were " built up" during the course of rework.

All responsible personnel were given explicit instructions on the drawing detail to preclude recurrence.

Seventy-five (75) of the subject welds were satisfactorily re-worked and accepted.

The remaining three (3) welds have been appropriately identified and will be completed subsequent to Hot Functional Testing.

Full compliance will be achieved prior to Core Load.

7812280 M

Boyce H.

Grier 11/9/78 If you require any additional information, we will be pleased to discuss it with you.

Very truly yours,

/]

W~

S&W

/<

/

- - _