___

g 4

~

ULO 15 19/e f;

i THIS DOCUMENT CONTAINS lir. Robert L. Canipe 1

Corporate Quality Assurance Manaaer POOR QUAllTY PAGES J

"r: lear Division - Hanford j

University ilechanical Engineers -

Constructors Ccller Box 700 l

Ih c:: land, Washington 99352

Dear lir. Canipe:

SUBJECT:

IMTERIAL TRACEABILITY - HVAC DUCTWORK AND STRUCTURAL SUPPORTS CLASSIFIED AS SEISMIC I In your letter' dated Octcber 30, 1978, the following position on the above subject was noted:

~

" Certified Hill Test Reports must be provided for all ductwork and structural HVAC supports. llowever, there does not have to be traceability from the Certified Mill Test Report to the ductwork and structural steel-after it has been installed.

It is acceptabl_e to maintain the traceability during storage; to assure that only certified material is purchased for instal-1 lation. Once this material is issued, the require-

{

~

ment for traceability is not necessary."

f As noted in a discussion between you and Jim Conway on December ll,1978, the above quoted statement is not a documented NRC position, but this subject was discussed during a telephone conversation in 1977 involving Mr. Mazo of.

Ebasco Services and our Mr. C. J. Helteme:.

In response to your letter, the NRC finds this " position" acceptable with the addition.of a qualifier that there is documented evidence that previous data (e.g., mill test reports);were found acceptable and are traceable :to a particular item prior to its issuance for fabrication and/or installation. This' documented evidence sho.uld be maintained as a permanent record in accordance with ' ANSI of Quality Assurance Records f;or Nuclear Power Plants.N45.2.9-1974, " Requireme In the case of other naterial items (eeg.,- screws, bolts, weld rod, etc.)

,,,, pgs ition" wourd apply, and doctmented evidence of acceptabiTects, thc n' ea u:cd in thc. Febricatica cad inshilation of dsctueck e 'w ity would not be rddifGs'C'"""""" " " ' " " " " ' " ". '

s.

.va= = e-

.m >.

Inc FORM 318 '(p.74) NRCM tide k u.a. **vs aam mar 'a'ana* ** *,ce s e,,e - se s. s e,

y.

D I

l Robert L. Canipe It should also be understood that this " position" as qualified above should retain its consistency with a traceability require'nent iarosed on University Mechanical. Engineers - Constructors by WPPSS.

If you have additional questions in this matter, plecse contact myself or Jin Comtay on (301) 492-7741.

-Sincerely.

Original signed by Y/ alter P. Haass Walter P. Haass, Chief Qualtty Assurance Branch Division of Project Managenent-

~

u DISTRIBUTION:

~

Central File QAB "rojects QAB Chron. File DJSkovholt, DPM Dross,'DPM NPF R$ading File..

i UNRC PDR JConway, QAB >

JGilray, QAB

^

WV1orrison, SD -

. y CJHelt( ves, DPM -

\\

~.

\\.

\\

s i