ML20147F406

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept CP-87-28 Re Condensate Storage Tank Overpressurization.Initially Reported on 871202.Addition of safety-related Control Feature for Level Transmitters Will Be Completed by 880516 for Unit 1
ML20147F406
Person / Time
Site: Comanche Peak  
Issue date: 03/04/1988
From: Beck J
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CP-87-28, TXX-88272, NUDOCS 8803070343
Download: ML20147F406 (1)


Text

. _ _ _ _ _ _ _ _ _ _.

s M

~ '

==

Log # TXX-88272

~

File # 10110 C

910.4 Ref. # 10CFR50.55(e) 1UELECTRIC.

March 4, 1988

%miam G. Counsil Execussve Vke President V. S. Nuclear Regulatory Commission Attn: Document Control Desk Washincton, D.C.

20555

SUBJECT:

COMANCHE PEAK STEAM ELECTRIC STATION (CPSES)

DOCKET NOS. 50-445 AND 50-446 CONDENSATE STORAGE TANK OVERPRESSURIZATION SDAR:

CP-87-28 (FINAL REPORT)

Gentlemen:

On December 2,1987, we notified you by our letter logged TXX-6992 of a deficiency involving the ca)acity of the condensate storage tank (CSI), which we determined to be reporta)le under the provisions of 10CFR50.55(e).

This is our final report on this issue to provide the schedule for completion of the corrective action.

Actions taken to resolve this deficiency (described in TXX-6992) consist of adding a safety-related control feature for the CST level transmitters which isolates CST makeup using redundant safety grade valves when the' CST high level setpoint is reached. This addition will be completed by May 16, 1988, for Unit 1 and prior to hot functional testing for Unit 2.

Very truly yours, W. G. Counsil By: CAW.kM _

Joy 4. Beck Vite President, Nuclear Engineering MCP/grr c-Mr. R. D. Martin, Region IV Resident inspectors, CPSES (3) f 8803070343 880304 PDR ADOCK 05000445 i

S DCD

/g 400 North Olive Street LB81 Dallas. Texas 7ml