Responds to NRC 780913 Telcon Request Re Fire Protection.Discusses Insp & Surveillance Frequency by Util of Outdoor Fire Hydrants
ML20147B067
Person / Time
Site: Crane 
Issue date: 09/21/1978
From: Herbein J
METROPOLITAN EDISON CO.
To: Reid R
Office of Nuclear Reactor Regulation
References
GQL-1538, NUDOCS 7810030142
Download: ML20147B067 (2)


Text

I g MM Q

a

- -m METROPOLITAN EDISON COMPANY SUBSIDIARY OF GENERAL PUBLIC UTILITIES CORPORATION POST OFFICE BOX 542 READ'NG, PENNSYLVANI A 19603 TELEPHCNE 215 - 929-3601 E'

September 21, 1978 GQL 1538 Director of Nuclear Reactor Regulations Attn:

R. W. Reid, Chief Operating Reactors Branch No. h U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 Fire Protection The following is submitted in response to your telecopy of September 13, i

1978.

NRC Concern - All outdoor fire hydrants vill be inspected for drainage of their dry barrels immediately prior to freezing vinter weather and for proper functioning immediately after the vinter season.

Met-Ed Response - Met $d is preparing a change to Station Surveillance Pro-cedure 3391-SA1, Revision 0, 04/27/78, Fire Hydrant Inspection, which vill read as follows:

1.0 PURPOSE Toensurehtydrantintegritybyavisualinspectionandbyverifying 1.1 drainage of the dry barrel after flow before and after freezing weather per Attachment 2 of TMINS-UNIT 2 FACILITY OPERATING LICENSE, February 8, 1978, and per the comitment made by lette> dated September 21, 1978 (G4L 1538), in response to NRC coreerns on Fire Protection for Unit 1.

782020344 7%Io0 % %

f,

R. W. Reid, Chief September 21, 1978 001 1538 2.0 APPLICABLE SURVEIIIANCE FREQUENCY AND MODES 2.1 Surveillance Frequency:

a.

All hydrants shr.11 be inspected during the months of April and October.

b.

Any hydrant used between October 1 and April 30, shall be inspected 1.mmediately following use.

2.2 Surveillance Modes: All modes.

NRC Concern - 1 1h" hose ca.pability will be provided in the outside hydrant hose houses as follows: one 2 " x 1 " x 1 " gated wye with 150' of 1 " hose, and two adjustable 1 " nozzles vill be provided in each hcse house where it may be necessary to extend yard hydrant service into a nearby structure to back up other systems.

Met-Ed Response - There are three outside hydrants which are considered as backup water sources for fire suppression for the Reactor Building, the Diesel Generator Building, and the Intake Screen and Pump House. Met-Ed vill provide the gated wye, hose, and nozzles described above at these outside hydrant hose houses.

Sincerely, J. G. Herbein Vice President-Generation JGH:PJS:ejg j