SACRAMENTO MUNICIPAL UTfuTY DISTRICT O 6201 S Street, P.O. Box 15830. Sacramento CA 95852-1830 (916) 452-3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA RJR 86-103 March 13, 1986 J B MARTIN - REGIONAL ADMINISTRATOR REGION V 0FFICE OF INSPECTION AND ENFORCEMENT U S NUCLEAR REGULATORY COMMISSION 1450 MARIA LANE SUITE 210 WALNUT CREEK CA 94596 Attached is the information requested by John Stolz in his March 11, 1983, letter to J. J. Mattimoe concerning National Pollutant Discharge Elimination System (NPDES) permit.
Further questions may be directed to Mr. George Campbell, who can be reached at; (209) 333-2935, extension 4144.
\\
p R. J. RODRIGUEZ ASSISTANT GENERAL MAf GER, NUCLEAR Attachment
%[hD b'+
n f?
\\
l
\\
e.c l
SACRAMENTO MUNICIPAL UTILITY DISTRICT C 6201 S Street. P.o. Box 15830. Sacramento CA 95852 1830.(916) 452 3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA GAC 86-120 March 4, 1986 V
W H CROOKS CALIFORNIA WATER QUALITY CONTROL BOARD CENTRAL VALLEY REGION 3201 S STREET SACRAMENTO CA 95814
)
ORDER 85-210 WATER DISCHARGE REQUIREMENTS 1
SACRAMENT 0 MUNICIPAL UTILITY DISTRICT RANCHO SEC0 NUCLEAR GENERATING STATION UNIT 1 Ir. accordance with the monitoring and reporting requirements of the subject order, please find attached a summary of the Water Quality Monitoring Program at the Rancho Seco Facility for February, 1986.
Additional comments are as follows:
1.
Rancho Seco has been shut down since December 26 due to a loss of power to the Integrated Control System.
2.
Maximum waste water flow rate was 9,800 gpm for one hour on February 5.
3.
Waste water discharges amounted to 196.8 M gallons.
4.
Maximum TOS in waste water discharge was 360 ppm, based on conductivity which occurred.during a retention basiis release on February 23.
~
Flowthroughthenewsewageplantaveraged25,86bgpdforthe 5.
month of February.
6.
The new sewage plant was put into operation November 30 cnd is still in a testing mode.
7.
Upon examination of the site drawings for the Plant Effluent Orainage System and Site Storm Drainage System, it has been determined that the estimated 800 gallons of rcw sewage water was not diverted to the Retention Basin as reported to the California Regional Water Quality Control Board by telephone on February 5, but left the site through the Site Storm Drainage System.
Therefore, the failure of
],
the sewage sump pump caused an estimated 1300 gallons of raw sewage water to leave the site through the Site Storm Drainage System.
1 i
l
-. _ _ _ _ ~ _ _ _, _ _ _ _ _. -. -... _. ~..,.
r
-W H CROOKS-March 4, 1986 Because of the topography of the area, all drainage flowed to the old construction impoundment just south of the restricted-area fence but still on SMUD's property.
Due to cattle grazing in the area and walking through the impounded water, it was determined to be futile to sample for Coliform, B00, or Suspended-Matter.
8.
Failure of the site well allowed sand into the water system which held flush valves open, causing-high sanitary flows.
The site well pump has been replaced and the screen inspected.
Samples of the sewage plant effluent were taken during the high f-low of~
February 5, and for the next few days until the flows were back to normal. All test results indicated that the Suspended Matter, Settleable Matter, 800, and Total Coliform remained within specifi-cation during the period, flI j p f 341
$L
~e GEORGE COWARD MANAGER, NUCLEAR PLANT RANCHO SECO NUCLEAR GENERATING STATION 14440 TWIN CITIES ROAD HERALD CA 95638 Enclosure (4) cc:
R. J. Rodriguez L. Keilman i
};
$*ItSMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT O 62o1 S Street, P.O. Box 15530. Sacramento CA 95852-1830,1916) 452-3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA
,,a 1
GAC 86-121 March 4, 1986 S
hx\\
REGIONAL ADMINISTRATOR EllVIRONMENTAL PROTECTION AGENCY REGION IX 215 FREMONT STREET SAN FRANCISCO CA 94105 s.
In accordance with reporting requirements of the California Water Quality Control Board, please find enclosed a copy of Jthe report of waste water quality monitoring at Rancho Seco for the month of February, 1986.
v 9,
GEORGE C0WA D MANAGER, NUCLEAR PLANT RANCHO SEC0 NUCLEAR GEtlERATING STATION 14440 TWIN CITIES ROAD - MS 255 HERALD CA 95638 Enclosure (4) 9 e