ML20141M498

From kanterella
Jump to navigation Jump to search
Submits Addl Info in Response to NRC 920730 & 31 Telcon Requests Re TS Change Request NPF-38-118 Re TS Surveillance Testing on ESFAS Automatic Actuation Logic Initiation Relays.Table Listing Logic Relays Encl
ML20141M498
Person / Time
Site: Waterford 
Issue date: 08/27/1992
From: Burski R
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
W3F192-0310, W3F192-310, NUDOCS 9208310258
Download: ML20141M498 (3)


Text

' &. ~

F ENTERGY me 4

-~-

R. F. Durski W3F192-0310 A4.05 QA August 27, 1992 U.S.

Nuclear Regulatory Commission Attn:-

Document Control Desk Washington, D.C.

20555

Subject:

Waterford 3 SES Docket No. 50-382 License No. NPF-30 Roquest for Additional Information Concerning Waterford 3 Technical Specification Change Request (TSCR) NPF-38-118

. Gentlemen:

This letter is provided as follow-up to telephone conversations occurring on July 30 and 31, 1992 between Waterford 3 and members of your staff.

During the July 30th conference

call, specifics concerning technical specification surveillance testing en the engineered safety features (E5PA5) actuaatic actuation logic initiation relays were discussed. This discussion' centered around the testing and the types of relays involved (Matrix Logic Relays).

As a result of this conversation the. staf f requestod Waterford 3 to suppletrent licensee-letters associated with the subject TSCR (i.e.,

submittals dated October 11, 1991 and December 18, 1991) with additional ~information describint the type, manufacture and model numbers of the relays involved.

Attachment A of this submittal provides the-requested information.

On July 31, 1992 Materford 3 contacted the staff in order to provide clarification concerning the relays appearing in Attachment A under group listing "ESF Relay Logic'. Although not discussed in the July 30th conversation, these relays are part of the ESFAS automatic actuation logic initiation and therefore, within the scope of the subject license amendment and Combustion Engineering Owners Group Topical Report CEN-327, "RPS/ESFAS Extended Test Interval Evaluation".

-It should be noted that the testing

- frequency acsociated with the "ESF Relay Logic" is four to one over the " Matrix Logic Relays".

Relays listed under " ESP Relay Logic" on Attachnent A are located downstream of the matrix relays and as such they are subjected to testing each time a channel is tested.

Currently one channel out of four is tested each week (i.e.

\\

920031025G 920827 b

PDR ADOCK 05000302 P

PDR

[

\\ \\

\\

p.

I U.S. Nuclear' Regulatory Commission Request for Additional Information Concerning Waterford 3 Technical Specification Change Request (TSCR) NPF-38-118 W3F192-0310 Page 2 August 27, 1992 staggered testing) such that all four channels are tested monthly.

Under the subject TSCR one channel could be tented every three weeks such that all four channels are tested quarterly.

This would subject the relays listed Undet "ESF Relay Logic" on Attachment A to testing approximately every three weeks.

Should you have any additional questions concerning this issue, please contact Paul Caropino at (504) 739-6692.

Very truly yours,

,[ IN R.F.

Burski Director, Nuclear Safety RFB/PLC/dc Attachment cc:

J.L. Milhoan, NRC Region IV-D.L..Wigginton, NRC-NRR R.D. McGehee N.S. Reynolds NRC Resident Inspectors Office

I d

t

.. PLANT PROTECTION SYSTEM-LOGIC RELAYS MATRIX LOGIC RELAYS.

i l

Type Martufacturer Model #

Total #/W3 failures -

4 so m. '

Bistable /Auxilbry Relay Cards Electro-Mechanics 31340 216/0 Matrix Relay Cards -

Electro-Mechanics *" *

31335 72/1 ESF RELAY LOGIC Type Manufacturer Model #

Total #/W3 failures SSRs (for indication a annunciation)

Toledyne 643-1 88/0 r

Lockout Relays -

Magnecraft W171 DIP-8 24/0 Lockout Reset Relays Potter & Brumfield R10-E3-Y8 4/0 SSRs (to ESF aux relay cabinets)

Teledyne 603-10001 48/1 l Mechan! cal relays (to ESF aux relay cabinets)

Potter & Brumfie!d KR3DH12V 16/0 g

i Attachment A to W3F192-0310

(-

    • 'Each relay card has 4 relaya Relays are manufac" red by Douglas Randall (model #M350).

u s

. -m

.