Discusses Facility Periodic Testing of Dow Corning Silicone Foam.Based on Facility Decision to Continue in-plant Penetration Seal Insp,Surveillance & Proposal to Discontinue Commitment to Maintain Test Silicone Samples,Acceptable
ML20141J833
Person / Time
Site: North Anna Dominion icon.png
Issue date: 08/13/1997
From: Kalyanam N
NRC (Affiliation Not Assigned)
To: Ohanlon J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
References
NUDOCS 9708210353
Download: ML20141J833 (3)


Text

gu*s Jb-398' b,

y

. p-UNITED STATES

-[

WUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. SBEAMSM August 13, 1997 Mr. J. P. O'Hanlon Senior Vice President - Nuclear Virginia Electric and Power Company 5000-Dominion B1yd.

Glen Allen. Virginia 23060

SUBJECT:

NORTH ANNA POWER STATION UNITS 1 AND 2.

PERIODIC TESTING OF DOW CORNING SILICONE FOAM

Dear Mr. O'Hanlon:

By letter dated February 10, 1997 Virginia Electric & Powe-Company (VEPCO) had stated that during the construction of North Anna Power Station. Units 1 and 2. Dow Corning Silicone Foam was used as fire barrier )enetration sealant.

Since the data on the long time aging characteristics of t11s material was not available at that time. VEPC0 committed to maintain foam samples and observe-these samples periodically o',er the life of the plant for signs of deterioration.- Since 1976, the sample material has been maintained and periodically (approximately every 5 years) evaluated for density changes as-well as comparatively tested in flamability tests. Additionally, installed.

penetration seals using this foam have been subject to inspection for cracking-and foam depth as part of a general plant periodic test of penetration seals.

Based on the sample evaluation results. VEPC0 has determined that the fire.

protection pro >erties of Dow Corning Silicone Foam are not adversely affected by aging.and tlat the continued maintenance, periodic observation and testing i

of the sam)le are no longer warranted and the commitment to maintain, observe and test tie samples is discontinued.

~

The U.S. Nuclear Regulatory Comission (NRC) staff has reviewed your letter.

i Based on your decision to continue the in-plant penetration seal inspections and surveillance, your proposal to discontinue your comitment to maintain and periodically observe / test silicone samples is acceptable.

ti y

10 t

3. g

, u --

gge2;ggggg;geg,,

g P

PDR lllllllll1,1ll lll EE

4 2-If you have any-questions regarding this matter, please contacy N.= Kalyanam at (301) 415-1480, Sincerely, (Origina1' Signed By)-

l Nageswaran Kalyanam, Project Manager Project Directorate 11-1 Division of Reactor Projects -'I/II Office of Nuclear Reactor Regulation Docket Nos: ~50 338 and 50-339 cc: See next page listrib; tion 70ectetJHles PUBLIC PDII-1 RF

.B.

Boger.

~ACRS S. West J. Johnson,-RII FILENAME: G:\\NOANNA\\DCORNING.CLO OFFICE PM:POII-1 LA:PDII-1 SPLB PD:PDII-1f(-

WAME Ndyanamn Dunnik$n-SWest M GEdison 71 DATE-08/12./97-1//4/97 08/1 3 /97 08/f$/97 COPY.

((e's)/No b No M/No --

Yes[d) v v

v

'l

t a

Mr. J. P. O'Hanlon North Anna Power Station Virginia Electric & Power Company Units 1 and 2 cc:

Mr. J. Jeffrey Lunsford County Administrator Louisa County Regional Administrator, Region !!

P.O. Box 360 U.S. Nuclear Regulatory Comission Atlanta Federal Center Louisa, Virginia 23093 61 Forsyth St., SW, Suite 23T85 Atlanta, Georgia 30303 Michael W. Maupin, Esquire Hunton and Williams Riverfront Plaza, East Tower Mr. W. R. Matthews, Manager North Anna Power Station 951 E. Byrd Street P. O. Box 402 Richmond, Virginia 23219 Mineral, Virginia 23117 Dr. W. T. Lough Mr. Al Belisle Virginia State Corporation U.S. Nuclear Regulatory Comission Comission Atlanta Federal Center Division of Energy Regulation 61 Forsyth St., SW, Suite 23T85 P. O. Box 1197 Atlanta, Georgia 30303 Richmond, Virginia 23209 Old Dominion Electric Cooperative Mr. David Christian, Manager Surry Power Station 4201 Dominion Blvd.

Virginia Electric and Power Company Glen Allen, Virginia 23060 5570 Hog Island Road Mr. M. L. Bowling, Manager Nuclear Licensing & Operations Support Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Blvd.

Glen Allen, Virginia 23060 Office of the Attorney General Commonwealth of Virginia 900 East Main Street Richmond, Virginia 23219 Senior Resident Inspector North Anna Power Station U.S. Nuclear Regulatory Comission 1024 Haley Drive Mineral, Virginia 23117 Robert B. Strobe, M.D., M.P.H.

State Health Comissioner Office of the Comissioner Virginia Department of Health P.O. Box 2448 Richmond, Virginia 23218 7

- - - - -