L Sheet-1 of 1 NRC MONTHLY OPERATING REPORT

SUMMARY

OF OPERATIONS WATERFORD 3 DECEMBER 1985 The unit started the month at 100% power. On December 4 a power reduction to approximately 70% power was initiated to perform control element assembly exercising required by technical specifications. On December 5 the unit returned to 100% power. On December 6 at 1819, at 100% power, a reactor trip on low departure from nucleate boiling ratio (DNBR) occurred when an incorrect value was entered for an addressable constant in the core protection calculators. The unit remained shutdown to replace reactor coolant pump seals.

On December 18 at 0638, the generator was back on line. On December 19 at 1443, at 100% power, a reactor trip occurred on low steam generator-level resulting from a feedwater pump trip due to an operator error while isolating the condenser water box. On December 20 at 0706 the generator was back on line. On December 22, 23 and 24, feedwater pump problems caused operation at reduced power levels for short durations. On December 24 the unit reached 100% power. The unit continued operation at approximately 100% power for the remainder of the month.

~$I

c PRESSURIZER SAFETY VALVE FAILURES AND CHALLENGES ^

-WATERFORD 3 During the month of December 1985, there_were no pressurizer-safety valve failures or challenges.

s J

i 4

4 i

n s

i t

t t

J i

i P

S l

I 1

8

+ - - - - - - -

1--

OPERATING DATA REPORT UNIT NAME: WATERFORD 3 CITY / STATE: KILLONA/LA-DATE: JANUARY 1986 OPERATING STATUS

1. Docket: 50-382 Notes (1) Maximum Dependable
2. Reporting Period: DECEMBER 1985 Capacity (Gross and Net MWe) will be
3. Utility

Contact:

GEORGE MILLER bi t

Phone Number:

(504) 467-8211

4. Licensed Thermal Power (NWt): 3390
5. Nameplate Rating (Gross Mwe): 1153
6. Design Electrical Rating (Net MWe): 1104
7. Maximum Dependable Capacity (Gross MWe): (Note 1)
8. Maximum Dependable Capacity (Net NWe): (Note 1)
9. If Changes Occur in Capacity Ratings (Items Number 4 Through 8) Since Last Report, Give Reasons:

N/A 10.

Power Level To Which Restricted, if Any (Net MWe):

NONE 11.

Reasons For Restrictions, If Any: N/A This Month Yr.-to-Date Cumulative 1

12.

Hours In Reporting Period 744.0 2377.0 2377.0 13.

Number Of Hours Reactor Was Critical 462.1 1868.7 1868.7 14.

Reactor Reserve Shutdown Hours 15 Hours Generator On-Line 451.3 1801.8 1801.8 16.

Unit Reserve Shutdown Hours -0--

OPERATING DATA REPORT (Continued)

This Month Yr.-to-Date Cumul'ative 17.

Gross Thermal Energy Generated (MWH) 1,423,475 5,642,439 5,G,42,439

- 18.

Gross Electrical Energy Generated (MWH) 478,270 1,897,850 1,89),850-19.

Net Electrical Energy Generated (MWH) 450,694 1,805,153 1,805,153 20.

Unit Service Factor

-60.7 76.1 76.1 21.

Unit Availability Factor 60.7 76.1 76.1 22.

Unit Capacity Factor (Using MDC Net)

(NOTE 1)

(NOTE 1)

(NOTE 1) 4 23.

Unit Capacity Factor (Using DER Net) 54.9 68.8 68.8 24.

Unit Forced Outage Rate 39.3 23.8 23.8 25.

Unit Forced Outsge Hours 292.7 564.8 564.8 26.

Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

Unit shutdown scheduled in March 1986 to perform Technical Specification surveillances requirina a unit shutdown, duration: approximately 28 days.

27.

If Shut Down At End of Report Period, Estimated Date Of Startup:

28.

Units In Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY 3/4/85 INITIAL ELECTRICITY 3/18/85 COMMERCIAL OPERATION 9/24/85 r

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-382-ITNIT WATERFORD ~ 3 DATE JANUARY 1986 COMPLETED BY GEORGE MILLER TELEPHONE 504-467-8211 MONTH DECEMBER 1985 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER' LEVEL (MWe-Net)

(NWe-Net) 1 1097

. 17 2 1098 18 367 3

1098 19 600-4 1073 20 323 5

767 21 1038 6

820 22 957 7 23 1062 8 24 1009-9 25 1097 10 26 1101 11 27 1095 12 28-1096 13 29 1104 14 30

-1105 15 31 1103 16 INSTRUCTIONS On this format, List the average daily unit power level'in MWe-Net' for each

- day in the reporting month. Compute to the nearest whole megawatt.

-(9/77)

_.u m

UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT FOR DECEMBER 1985 DOCKET NO 50-382 UNIT NAME WATERFORD 3 DATE JANUARY 1986 COMPLETED BY GEORGE MILLER TELEPHONE 504-467-8211 Method of Licensee Cause & Corrective Duration Shutting Event System Component Action to No.

Date Type' (HOURS)

REASON 2 Down Reactor 3 Report #

Code 4 Codc5 Prevent Recurrence 85-023 851204 N/A 0.0 B

5 N/A N/A N/A Power reduction to 70%

to perform control element assembly exercising required by technical specifications.85-024 851206 F

276.3 G

3 85-051 JC,AB ZZZZ, SEAL At 100% power, a reactor trip occurred on low DNBR when an incorrect value was entered for an addressable constant'in the core protection calculators. The unit remained shutdown to replace reactor coolant pump seals.

I 7

3 F: Forced Reason:

Method S: Scheduled A-Equipment Failure (Explain) 1-Manual B-Maintenance or Test 2-Manual' Scram.

C-Refueling 3-Automatic Scram.

D-Regulatory Restriction 4-Continuation 4

E-Operator Training &

5-Load Reduction IEEE Std.805-1984 License Examination 9-Other 5

F-Administrative IEEE Std. 803A-1983 G-Operational Error (Explain)

H-Other (Explain)

e.

UNIT SHUTDOWNS AND POWER REDUCTIONS l;

REPORT FOR DECEMBER 1985 IX)CKET NO 50-382

-UNIT NAME WATERFORD 3 DATE JANUARY 1986 COMPLETED BY GEORGE MILLER TELEPHONE 504-467-8211 Method of Licensee Cause & Corrective Duration Shutting Event System Component Action to No.

Date Tygel (HOURS)

REASON 2 Down Reactor 3 Report #

Code 4 Code 5 Prevent Recurrence 85-025 851219 F

16.4 G

3 85-056 SG ZZZZ At 100% power, a reactor trip occurred on low steam generator level resulting from a feedwater pump trip due to an operator error while isolating the condenser water box.

I 2

3 F: Forced Reason:

Method-S: Scheduled A-Equipment Failure (Explain) 1-Manual B-Maintenance or Test 2-Manual Scram.

C-Refueling-3-Automatic Scram.

D-Regulatory Restriction 4-Continuation-4 E-Operator Training &

5-Load Reduction IEEE Std. 805-1984 License Examination 9-Other 5-F-Administrative IEEE Std. 803A-1983

~G-Operational Error (Explain)

H-Other (Explain)

,L LOUISIANA P O W E R & L l G H T! P O box 6008. NEW ORLEANS. LOutSIANA 70174 242 oEtanoNot SmEn

. (504) 366-2345 N N SYSYE January 15, 1986 W3P86-0005 A4.05 QA Mr. Ronald M. Scroggins Controller and Director Office of Resource Management U.S. Nuclear Regulatory Commission Washington, D.C. 20555

Dear Mr. Scroggins:

Subject:

Waterford 3 SES Docket No. 50-382 Licence No. NPF-38 MONTHLY OPERATING REPORT Enclosed is the subject monthly report which covers the operating statistics for the month of December 1985. This report is submitted per Section 6.9.1.6 of the Waterford 3 Technical Specifications for Facility Operating License No. NPF-38.

Very truly yours, w %%c4GL K.W. Cook Nuclear Support & Licensing Manager KWC:GEW:sms Enclosure cc:

R.D. Martin, NRC Region IV NRC, Director, Office of I&E G.W. Knighton, NRC-NRR NRC Resident Inspectors Office INPO Records Center (J.T. Wheelock) hg B.W. Churchill W.M. Stevenson 1 \\