Confirms Rev to Bailey 862 Solid State Logic Modules Surveillance Test Program Frequency,Per 860219 Telcon W/Nrc & Util .Util Will Test 100% of Total Test Population of Modules During Each Cycle of Operation
ML20141G749
Person / Time
Site: Hope Creek 
Issue date: 02/24/1986
From: Corbin McNeil
Public Service Enterprise Group
To: Adensam E
Office of Nuclear Reactor Regulation
References
NUDOCS 8602260337
Download: ML20141G749 (2)


Text

_

t Public Service Electric and Gas Company Ctrbin A. McNeill, Jr.

Public Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609339-4800 Vice President -

Nuc! ear February 24, 1986 T

Director of Nuclear Reactor Regulation United States Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, Maryland 20814 Attention:

Ms. Elinor Adensam, Director Project Directorate 3 Division of DWR Licensing

Dear Ms. Adensam:

BAILEY SOLID STATE LOGIC MODULE TELECON OF FEBRUARY 19, 1986 HOPE CREEK GENERATING STATION DOCKET NO. 50-354 As a result of the telephone conversation between representatives of Public Service Electric and Gas Company (PSE&G) and the NRC on February 19, 1986 pertaining to the Bailey 862 Solid State Logic Modules (SSLM) surveillance' test program as documented in letter from C.A. McNeill (PSE&G) to E.

Adensam (NRC) dated February 14, 1986, PSE&G notes.the following revision to the SSLM surveillance test program frequency.

PSE&G will test 100% of the total test population of 577 Bailey 862 SSLMs during each cycle of operation.

A minimum number of 5% per month of these modules will be tested.

l Testing will commence at the issuance of a full power license an3 continue until such time as sufficient statistical data is obtained to verify the reliability of the Bailey 862 SSLMs.

At such time, PSE&G will petition the NRC for relief from performing continued testing of the SSLMs.

Should there be any questions uith respect to the above, do not hesitate to contact us.