4w Tennessee Valley Authority, Post Ofrice Box 2000. Soddy-Daisy, Tennessee 37379-2000 i

1 May 15,1997 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Gentlemen:

la the Metter of

)

Docket Nos. 50-327 Tennessee Valley Authority

)

SEQUOYAH NUCLEAR PLANT (SON)- CHANGE OF UNIT 1 ELBOW TAP FLOW CORRELATION COEFFICIENTS

Reference:

NRC letter to TVA dated April 26,1996, " Issuance of Technical Specification _ Amendments for theSequoyah Nuclear Plant, Units 1 and2 (TAC NOS. M84390 and M84391) (TS 92-07)

The purpose of this letter is to provide the revised elbow tap flow correlation coefficient as requested by the reference. The Unit 1 reactor coolant flow elbow tap transmitter 1-FT-68-6A flow correlation coefficient K value has been changed to 5679.58 from 5679.10. This change resulted from the discovery of a small calculation error that was created by the use of the wrong initial span for the transmitter of 355.17 inches water instead of 355.11 inches water. This change is so small that transmitter recalibration was not necessary.

\\O Please direct questions concerning this issue to KeithWeller at (423) 843-7527.

S)O}0 Sincerely, g,

2001G7 R. H. Shell Site Licensing and Industry Affairs Manager

]

cc: See page 2 kkl y

9705210402 970515

)

PDR ADOCK 0500 7

P

4 I

Th.

i U.S. Nuclear Regulatory Commission Page 2 -

' May 15,1997 i

~

cc: Mr. R. W. Hernan, Project Manager -

Nuclear Regulatory Commission j

~ One White Flint, North 11555 Rockville Pike l

Rockville, Maryland 20852-2739 i

NRC Resident inspector Sequoyah Nuclear Plant l

2600 Igou Ferry Road '

]

Soddy-Daisy, Tennessee 37379-3624 j

. Regional Administrator U.S. Nuclear Regulatory Commission Region ll.

l 61 Forsythe St., SW, Suite 23T85 i

' Atlanta, Georgia 30303 3415

't i

w i

s i

.a j_

I d

v

'\\. r