-to,.

S SOUTH CAROLINA ELECTRIC & GAS COMPANY Post orrice 7e4 CptuotA. south CAnoWNA 29218 M ri } ** D D r

l

o. w. osmou,s..

Nuc$e5."o',*e2rYo,..

'dh June 18, 1985 Dr.

J.

Nelson Grace Regional Administrator U.S.

Nuclear Regulatory Commission Suite 2900 101 Mariett'a Street, NW Atlanta, Georgia 30323

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. N P F-12 Special Report (SPR 85-005)

Dear Dr. Grace:

Attached is a Special Report for the Virgil C.

Summer Nuclear Station.

This Special Report is required by Section 6 of the Technical Specifications.

Sh ou ld there be any questions, please call us at your convenience.

r-ery t u y yours,

\\

hbW+vs hN 1 on, Jr.

RMF:0WD/csw Attachment cc:

V.

C.

Summer K.

E.

Nodland T.

C.

Nichols, Jr./O.

W.

Dixon, Jr.

R.

A.

Stough E.

H.

Crews, Jr.

G.

Pe r c iv a l E.

C.

Roberts C.

W.

Hehl W.

A.

Williams, Jr.

J.

B.

Knotts, Jr.

D.

A.

Nauman S.

D.

Hogge Group Managers I&E Washington O.

S.

Bradham Document Man age men t C.

A.

Price Branch S.

R.

Hunt INPO Records Center J.

F.

Heilman ANI Lib r a ry C.

L. Ligon (NSRC)

NPCF File

-[g 7,Te 8507120610 850618 PDR ADOCK 05000395

/

S PDR L

O Dr.

J.

Nelson Grace SPR 85-005 June 18, 1985 EVENT DESCRIPTION On May 17, 1985 the Licensee's Appendix R Task Force id en t i f ie d that separation of the Nuclear Instrument (NI) Source Range (SR) Detectors (N-31, N-32, and N-33) did not meet the requirements of 10 CFR 50 Appendix R.

The "B"

train power supply for NI SR channel N-33 shares a common breaker with a 7200 volt cable which runs in the same fire. area ("B" train cable chase, Room 36-03CB) as the "A"

train s ignal cab les for NI SR channel N-31 and N-32.

A fire in this area c ou ld damage channel N-31 and N-32 and als o dis rupt power to N-33.

These circuts are separated by a horizontal dis tance of greater than twenty feet; however, because of intervening c omb u s t ib l e s,

i.e, insulation of electrical cables, the requirements of Appendix R are not satisfied.

There were no adverse consequences due to this event.

Detector N-33 is the SR indicator located on the Control Room Evacuation Panel (CREP).

A fire in the "B"

train c ab le chase wou ld not require a Control Room evacuation or the use of the CREP.

Shutdown wou ld be accomplished from the Control Room using "A" train equipment.

CORRECTIVE ACTION The Licensee e s t ab lis hed a one hour fire watch patrol o f the area as required by Technical ' Specification 3.7.10, " Fire Rated As s emb li e s. "

A modification to the existing installation of NI-33 is presently being processed wh ic h will provide isolation of NI-33 from.NI-31 and NI-32.

This modification will be implemented no later than March 31, 1986.

L