ML20140G305

From kanterella
Jump to navigation Jump to search
Special Rept Spr 85-006:Div a Vital Power Sys Tray Not Separated from Div B Trays Containing Cables for Redundant Functions.Roving Fire Watch Established for Area.Mods to Meet App R to Be Completed by 860331
ML20140G305
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 06/18/1985
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
SPR-85-006, SPR-85-6, NUDOCS 8507120608
Download: ML20140G305 (2)


Text

r-- -

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFICE 764 ct e Agurs camouuA asais o.w.omon.3. g@ j VrCE PatssosNT June 18, 1985

, NuCLeas onnanopes

~Dr. J. Nelson Grace Regional Administrator U.S. Nuclear Regulatory Commission Suite 2900 101'Marietta Street, NW Atlanta, Georgia 30323

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. N P F- 12 Special Report (SPR 85-006)

Dear Dr. Grace:

Attached is a Special Report for the Virgil C. Summer Nuclear Station. This Special Report is required by Section 6 of the Techni' cal Specifications.

- Sh ou ld there be any questions, please call us at your convenience.

r tr 1 urs,

. W.

ch Dixon, Jr.

~

JAW:0WD/csw Attachment e c: V. C. Summer K. E. Nodland T. C. Nichols, Jr./0. W. Dixon, Jr. R. A. Stough E. H. Crews, Jr. G. Pe r c iv a l E. C. Roberts C. W. Hehl W. A. Williams, Jr. J. B. Kn o t t s , Jr. ;

D. A. Nauman S. D. Hogge Gr ou p Managers I&E Washington O. S. Bradham Document Management C. A. Price Branch S ~. . R . Hunt INPO Records Center I J. F. Heilman ANI Lib r a r y C. L. Ligon (NSRC) NPCF j

File i

s

- qW 3 a J B507120608 850618 PDR S ADOCK 05000395' PDR d(

\

P Dr. J. Nelson Grace SPR 85-006 June 18, 1985 EVENT DESCRIPTION During the course of a re-evaluation of South Carolina Electric and Gas Company's (SCE&G) compliance with 10CFR50 Appendix R,

" Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979," it was identified that an "A" d ivis io n vital power system tray was not separated from "B" d iv is ion trays containing cables for redundant func t ion s . Appendix R requires one redundant train to be wrapped in a one hour fire barrier where separation is less than twenty feet with fire detection and automatic fire suppression in the area. A fire which cou ld damage these "A" and "B" d ivis ion trays wou ld compromise or p r e c lu d e the use of redundant systems and equipment necessary for operation and safe shutdown.

CORRECTIVE ACTION A one-hour roving fire watch was e s t ab lis hed for the area. The feas ibility of wrapping the "A" division tray inv o lv e d is being eva lu a t ed . Modifications to meet Appendix R requirements will be completed by March 31, 1986.