Jump to navigation Jump to search
Special Rept Spr 85-006:Div a Vital Power Sys Tray Not Separated from Div B Trays Containing Cables for Redundant Functions.Roving Fire Watch Established for Area.Mods to Meet App R to Be Completed by 860331
ML20140G305
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 06/18/1985
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
SPR-85-006, SPR-85-6, NUDOCS 8507120608
Download: ML20140G305 (2)


Text

r-- -

SOUTH CAROLINA ELECTRIC & GAS COMPANY POST OFFICE 764 e Agurs camouuA asais ct g@

j o.w.omon.3.

VrCE PatssosNT June 18, 1985 NuCLeas onnanopes

~Dr.

J.

Nelson Grace Regional Administrator U.S.

Nuclear Regulatory Commission Suite 2900 101'Marietta Street, NW Atlanta, Georgia 30323

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. N P F-12 Special Report (SPR 85-006)

Dear Dr. Grace:

Attached is a Special Report for the Virgil C.

Summer Nuclear Station.

This Special Report is required by Section 6 of the Techni' cal Specifications.

- Sh ou ld there be any questions, please call us at your convenience.

r tr 1

urs, ch

~

W.

Dixon, Jr.

JAW:0WD/csw Attachment e c:

V.

C.

Summer K.

E. Nodland T.

C.

Nichols, Jr./0.

W.

Dixon, Jr.

R.

A.

Stough E.

H.

Crews, Jr.

G.

Pe r c iv a l E.

C.

Roberts C.

W. Hehl W.

A.

Williams, Jr.

J.

B.

Kn o t t s, Jr.

D.

A.

Nauman S.

D.

Hogge Gr ou p Managers I&E Washington O.

S.

Bradham Document Management C.

A.

Price Branch S ~.. R. Hunt INPO Records Center I

J.

F. Heilman ANI Lib r a r y C.

L.

Ligon (NSRC)

NPCF File j

i 3 a JqW s

B507120608 850618 PDR ADOCK 05000395' d(

S PDR

\\

P Dr.

J.

Nelson Grace SPR 85-006 June 18, 1985 EVENT DESCRIPTION During the course of a re-evaluation of South Carolina Electric and Gas Company's (SCE&G) compliance with 10CFR50 Appendix R,

" Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1,

1979," it was identified that an "A" d ivis io n vital power system tray was not separated from "B" d iv is ion trays containing cables for redundant func t ion s.

Appendix R requires one redundant train to be wrapped in a one hour fire barrier where separation is less than twenty feet with fire detection and automatic fire suppression in the area.

A fire which cou ld damage these "A"

and "B"

d ivis ion trays wou ld compromise or p r e c lu d e the use of redundant systems and equipment necessary for operation and safe shutdown.

CORRECTIVE ACTION A one-hour roving fire watch was e s t ab lis hed for the area.

The feas ibility of wrapping the "A"

division tray inv o lv e d is being eva lu a t ed.

Modifications to meet Appendix R requirements will be completed by March 31, 1986.