ML20140E419

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violations Noted in Insp Repts 50-277/84-25 & 50-278/84-21.Corrective Actions:Correction Factors Applied to Harshaw Dosimetry Results & Evaluation & Trending Performed for Loss of Dosimetry for Work Groups
ML20140E419
Person / Time
Site: Peach Bottom  
Issue date: 12/04/1984
From: Daltroff S
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Martin T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20140E416 List:
References
NUDOCS 8501110021
Download: ML20140E419 (3)


Text

p PHILADELPHIA ELECTRIC COMPANY 2301 M ARKET STREET P.O. BOX 8699 PHILADELPHI A. PA.19101 G W "O#

smetos t. oALTnorr tLacTm c ra O CTiom December 4, 1984 Docket Nos. 50-277 50-278 Mr. Thomas T.

Martin, Director Division of Engineering and Technical Programs U.S. Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, PA 19406

Dear Mr. Martin:

Your letter of November 6, 1984, forwarded Combined Inspection Nos. 50-277/84-25 and 50-278/84-21 which cited certain activities at our Peach Bottom Atomic Power Station which did not seem to be in full compliance with NRC requirements.

These apparent violations are restated below followed by our responses.

Finding A.

Appendix "A"

to License Nos. DPR-44 and DPR-56, Technical Specifications Section 6.11, requires that procedures for personnel radiation protection shall be approved, maintained and adhered.tx) for all operations.

(1)

Procedure BPO/CO-32, " Quality Control of Personnel Dosimetry", requires that a correction factor be calculated for Harshaw dosimetry and used to correct the bias of the Harshaw dosimeter results.

(2) Procedure HPO/CO-13E,

" Accounting for Lost Badges", requires that there be an evaluation and trending of the loss of dosimetry for major work groups.

Contrary to the above, as of August 23, 1984, (1) correction factors have not been. calculated and used to correct the bias of Harshaw dosimeter results and (2) there has been no evaluation or trending of the loss of dosimeters for major work groups.

This is a Severity Level V violation.

(Supploment IV);

ohh PDR-

~

F.3 l

Mr. T. Martin Decembsr 4, 1984

~

Page 2 Response-A.1 -

Correction of Harshaw readings had been performed in the past, however, due to personnel error resulting

_from a change in personnel in the dosimetry office,

't the process had been stopped.

The Harshaw readings are not used for official records but rather for administrative control and exposure estimation.

Since they historically have provided high reading, and were therefore on the conservative side, due diligence was not given to the procedural requirements.

Health Physics personnel have now been directed to comply with HPO/CO-32, " Quality Control of Personnel dosimetry", and apply correction factors to Harshaw TLD results.

A conservative correction factor of 1.0 will be substituted when correction factors are calculated to be less than one.

A correction factor of'less than one will not be used without the approval of the Senior Health Physicist.

These actions should prevent future recurrence of this violation.

A.2 This_ failure resulted from administrative oversight following a personnel change in the dosimetry office.

Prior to this change, records of lost dosimetry were

' tabulated and utilized to produce a Lost-Badge Summary Report which is included in the Health Physics and Chemistry Management Report submitted to the Plant Operations Review Committee _(PORC) and-retained as a record in the PORC minutes.

Upon notification of this shortcoming, trending of lost dosimetry was reestablished and lost dosimetry reports were generated for every month since July J

No. unusual or adverse trends were identifibd 1984.

for any one work group or individual'in these reports.

As additional corrective measures, which should serve to prevent recurrence of this failure, 1) a routine test'will be generated and scheduled to ensure that dosimetry. losses are evaluated and 2) HPO/CO-13E, Accounting for Lost Badges, will be revised to-clarify this evaluation program.

These_ corrective actions will.be completed by February 1, 1985.

D 0

Mr. T. M2rtin D cambur 4, 1984 Page 3 Should you have any questions or require further

-information, please contact us.

k Very truly yours, fl i /. /

)

n f'lk d!'(i

\\

cc:

Mr. J. H. Williams, Resident Inspector

. y L

W

.a

.v M d suis mi r'

r u

i ii