Docket No. 50-412 APPLICANT:
Duquesne Light Company (DLC)
FhCILITY:
Beaver Valley Power Station, Unit 2 (BVPS-2)
SUBJECT:
FIRE PROTECTION MEETING
SUMMARY
On April 19, 1984, the staff met with the applicant and representatives from Stone and Webster Engineering Corporation (SWEC) to discuss fire protection open items in the BVPS-2 draft SER. The meeting was held in Bethesda, MaryTand.
The agenda and meeting attendees are attached as Enclosures 1 and 2 respectively.
DLC first presented their draft responses to the thirteen open items (#82-#94).
Subsequent to a discussion on each of the items, the following were determined confirmatory:
- 32 Fire harard analysis
- 83 Fire brigade
- 90 Fire detection
- 92A Capacity of drain tank of oil collection system
- 93 Control room complex The following five items remain open and require additional interaction between the staff and OLC:
- 86 Alternate shutdown
- 87 Hydrogen piping
- 89 Power supplies for control room ventilation
- 94 Cable spreading room Open item #94 will require additional efforts from the staff and applicant in order to resolve this issue. The current status of all fire protection items is listed in Enclosure 3.
Those noted as closed are closed pending formal submittal of the responses discussed. Open items #91 and #928 are closed, but require minor additions.
It is the staff's preference for the submittal to be in the form of an amendment to the FSAR or the Fire Protection Evaluation Report.
In DLC's formal response letter, they will indicate in which of these two documents each item will be addressed.
DLC also identified two items of concern: the absence of a UL label on fire dampers resulting from an alternate installation configuration, and wrapping ventilation ductwork of newly identified fire areas.
Further discussions 8406180136 840531 ome n >
PDR ADOCK 05000412 E
PDR cu m un>.................
unc ronu sia no, sci sacu o24o OFFICIAL RECORD COPY c us.m ass-e2n w.
marzyin:saw?:5g av
-we m-w w
grang 2
b will be dedicated to these two items. The purpose of this meeting was to alert the staff of these issues.
In closing, the present status of the fire protection open items was confirmed.
DLC indicated that the responses would be formally submitted as soon as possible. However, no exact date was determined.
5 Marilyn Ley, roject Manager Licensing' Branch No. 3 Division of Licensing
Enclosures:
As stated cc: See next page a
.0L;.lJ.Gh
- k D
" ' " > P.L.- l.E /.3.......
'1 hton
.q,,,,,,.
.M'g/A.T...
.Eg,1g,},tra
=>.. 3. 1. /. 8. 4........
- 5../.f../../. 8 4........
. 5. /.3.. l../. 8 4......
N:c ro7.u aia sio,soi nacu o24o OFFICIAL. RECORD COPY
- u.s. am 29 3--40o 247
.~..~..~...-...~.-ma
~~
- " ^ ~
~^
^^^
~
r-
,..s t
1)'
f
?
i p.
i MEETING SUMMADV DISTRIBUTION
)
D$cket No(s):, 50,-412 yNRC PDR f -
'J
?
c I
PR6 System '
t,j te, LB3 Reading j
Attorney, CELD GWKnighton Project Manager M. Ley JLee NRC PARTICIPANTS
.R; Eberly Marilyn Ley E' Licitra t:
Vic Benaroya
,/
/
/
)
l 1
/
I L t t -(
?,.-
t
s' W
f '.
a' s
g+
s
- n, nj g
3.
p y *;
f
~
f I'
l g
1 i
I*
[
' /
ii i
)bec: Appitheat & Service List
(
x<
f t
F 4
?i 1
^.
J
')
f-A 3,
- tv
<k
</
/
I i
/
i r
?
6[
. f ausy k
UNITED STATES
^
8
- NUCLEAR REGULATORY COMMISSION o-
' g, E
WASHINGTON, D C. 20555
~
7t, _
I Docket 1No. 50-412 p
APPLICANT: Duquesne Light Company (DLC)
FACILITY:
Beaver Valley-Power Station, Unit 2 (BVPS-2)
SUBJECT:
-FIRE PROTECTION MEETING
SUMMARY
I On April 19, 1984, the staff met with the applicant and representatives from f
Stone and Webster Engineering Corporation.(SWEC) to discuss fire protection L
open items in the.BVPS-2 draft SER. The meeting was held in Bethesda, Maryland.
l The agenda and meeting attendees are attached as Enclosures 1 and 2 respectively.
[
i DLC first presented their draft' responses to the thirteen open items (#82-#94).
j Subsequent to a discussion on each of the items, the following were determined i.
confirmatory:
c
- 82 Fire hazard analysis
- 83 Fire brigade
- 90 Fire detection i-
- 92A Capacity of drain tank of oil collection system i
.#93 Control room complex
' The following five items remain open and require additinnal b+ raction I
~
between the staff and. DLC:
- 85 Safe shutdown f
~
.#86 Alternate shutdown
- 87
. Hydrogen' piping ventilation j
- 89. Power supplies for contro
- 94 Cable spreading room 7
i Open item #94 will require additional efforts from the staff and applicant l
in order'to resolve this issue. The current status of all fire protection items is listed in_ Enclosure 3.
Those noted as closed are closed pending formal submittal of the responses discussed. Open items #91 and #92B are closed, but i
require minor additions. 'It is the staff's preference for the submittal to o_
3-be in the form of an amendment to the FSAR or the Fire Protection Evaluation
- - Report.
In DLC's formal response letter, they will indicate in which of these two documents each item will be addressed.
DLC also identified two ' items of concern:
the absence of a UL label on fire
. dampers resulting from an alternate installation configuration, and wrapping ventilation ductwork of newly identified fire areas.
Further discussions f
f
--.,-,~--,-,--+-r----------,--,,
- ~ -
,,--_wm-
-,r-m n.~,-n,~,
(
1 s
2_
hillbededicatedto'these'twoitems. The purpose of this meeting was to alert the staff of these issues.
In closing, the present status of.the fire protection open items was confirmed.
DLC indicated that the.rcsponses would be formally submitted as soon as possible. However, no exact date was determined.
r pilartlLpO $R
~
Marilyn Ley, Project Manager Licensing Branch No. 3 Division of Licensing s
Enclosures:
As stated s
c;c: See next page t
k
\\
.t g
r s
4 I
. g I
b J
I s
q.
I,
s r
i'
)
e
's
- t 3
\\
I N.
\\
\\q\\.
e
{
f
~
x Beaver Valley Mr. Earl J. Woolever Vice President, Nuclear Construction Duquesne_ Light Company Robinson Plaza Building, No. 2, Suite 210 PA Route 60 Pittsburgh, Pennsylvania 15205 Gerald Charnoff, Esq.
Mr. H. M. Siegel, Manager Engineering Jay E. Silberg, Esq.
Beaver Valley Two Pro,iect
[
Shaw, Pittman, Potts & Trowbridge Duquesne Light Company 1800 M Street, N.W.
Robinson Plaza Building No. 2 Washington, DC 20036 Suite 210 PA Route 60 Pittsburgh, Pennsylvania 15205 Mr. C. W. Ewing, Ouality. Assurance Zori Ferkin Manager Assistant Counsel-Ouality Assurance Department Governor Energy Council Duquense Light Company 1625 N. Front Street P. O. Box 186 Harrisburg, PA 15105 Shippingport, Pennsylvania 15077 Mr. R. J. Washabaugh BV-2 Project Manager Duquense Light Company Directpr, Pennsylvania Emergency Robinson Plaza Building No. 2
' Management Agency Suite 210-Room B-151 Pittsburgh, Pennsylvania 15205 Transportation & Safety Building Harrisburg, Pennsylvania 17120 Mr. T._J. Lex Mr. Thomas Gerusky
. Westinghouse Electric Corporation Bureau of Radiation Protection Power Systens PA Department of Environmental P. O. Box 355 Resources Pittsburgh, Pennsylvania 15230 P. O. Box 2063 Harrisburg, Pennsylvania 17120 Mr. P. RaySircar Stone & Webster Engineering Corporation BVPS-2 Records Management Supervisor P. O. Box 2325 Duquesne Light Company Boston, Massachusetts 02107 Post Office Box 4 Shippingport, Pennsylvania 15077 Mr. Glenn Walton U. S. NRC John A. Lee, Esq.
P. O. 181 Duquesne Light Company Shippingport, Pennsylvania 15077 1 0xford Centre 301 Grant Street Mr. Thomas E. Murley, Regional Admin.
Pittsburgh, Pennsylvania 15279 U. S. NRC, Region 1 631 Park Avenue King of Prussia, Pennsylvania 15229 i
/
Mr. E. F. Kurtz, Jr., Manager Regulatory Affairs Beaver Valley Two Project s
Duquense Light Company Robinson Plaza Buidling No. 2 Suite #210 PA Route 60 Pittsburgh, Pennsylvania. 15205 I
1 i
t
e Enclosure i FIRE PROTECTION MEETING BEAVER VALLEY POWER STATION UNIT NO. 2 AGENDA (APRIL 19, 1984 9:00 A.M.)
1 INTRODUCTION II.
SAFETY EVALUATION REPORT OPEN ITEMS lil.
ITEMS OF CONCERN A.
FIRE DAMPERS B.
WRAPPING VENTILATION DUCTWORK
' Enclosure 2 ATTENDANCE LIST Beaver Valley-2 Fire Protection Meeting Thursday, April 19, 1984 9:00 a.m.
Bethesda, Maryland Name Organization R.-Eberly NRR/CMEB Marilyn Ley NRC/DL/LB#3 E. Licitra NRC/DL/LB#3 R. M. Sibulkin SWEC
-Jack Harding' DLC/Eng.
Erv Eilmann DLC/Lic.
' Charles Moehl.
SWEC Larry -Gurevici SWEC-Walter J. Parker SWEC John D. Sutton SWEC Vic Benaroya NRC/CMEB 4
c.
=
Status-of Fire Protection Open Items
- dSER Status Remarks 82 confirmatory DLC will submit methodology for flood level issue 83 confirmatory DLC should provide further details to the physical examination program 84 closed 85 open NRC will review 86 open NRC will review 87 open DLC will provide assurance that the design prevents hydrogen leakage 88 closed 89 open DLC will include portable ventilation information 90 confirmatory DLC will revise response to include information presented in slide pre-sentation 91 closed DLC will include testing frequency in response
'92A-c6nfirmatory DLC will include a brief ~ discussion of supression system 928 closed DLC will include supression system description 1
93 confirmatory DLC will include metal file cabinets and A-rated portable fire extinguisher
- 94 open Requires further staff / applicant discussion
- Pending formal submittal of the responses presented
.