WY f/L E 5>382,l95-3)
IR Louisiama l"
P O W E R & L 1 G H T! WATERFCRO 3 SES
- P.O. BOX B + KILLONA, LA 70066 staaimm December 12',-1985 ' I W3M85-0328
)
h [--
^\\
')
A4.05
,j, P ~
q l
DFC:
0 9^
Ior n h
NRC Region IV.
J Mr. J. R. Boardman
[~'~~
611 Ryan Plaza, Suite 1000
-Arlingt'on, TX 76011 RE: Waterford 3 AKR 30 And AKR 50 CE Circuit Breakers
Dear Mr. Boardman:
The following action will be taken on the AKR 30 and AKR 50 480V CE Circuit Breakers which are used in motor control applications.
For each of the below listed breakers, the contact adjusting screws prevailing torque will be checked prior to entering Mode 1 during the start-up from the present' outage.
If the prevailing torque is less than 40 inch pounds, it will be torqued and Locktite 220 will be applied to the adjusting screw threads. This will satisfy Recommendation 002 from GF. Failure Analysis Report of PO #L-65298-P.
UNID DESCRIPTION SBV-EBKR 31A SBS FAN E-17 CED-EBKR 31A 8B CEDM FAN 3A IA-EBKR 31A 9A Inst. Air Comp. A CED-EBKR 31A 9B CEDM FAN 3C SBV-EBKR 31B 5B FAN E-17 HVR-EBKR 31B 6B FAN E-22 CED-EBKR 31B 8B CEDM FAN 3B IA-EBKR 31B 9A Inst. Air Comp. B CED-EBKR 31B 9B CEDM FAN 3D FP-EBKR 31AB SA Fire Pump CVC-EBKR 31A SC Charging Pump A CVC-EBKR 31B 6C Charging Pump B CVC-EBKR 31AB 4C Charging Pump AB Sincer ly.
%asio
.. Smith Maintenance Superintendent THS/jhf cc:
D. W. Vinci., Nuclear Records, Project Files, Maintenance Files 8512240190 851212 A
PDR ADOCK 05000382 g,6 p
PDR y
O i
<