Monthly Operating Rept for Sept 1985
ML20138C615
Person / Time
Site: Summer 
Issue date: 09/30/1985
From: Dixon O, Loignon G
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Barry L
NRC OFFICE OF RESOURCE MANAGEMENT (ORM)
References
NUDOCS 8512130055
Download: ML20138C615 (5)


Text

--

O' Director, Office of Resource Management September Monthly Operating Report October 7,-1985 ATTACHMENT I AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.

50/395 UNIT V.

C. SUMMER I DATE 10/07/85 4

COMPLETED BY G.

A.

Loignon TELEPHONE (803) 345-5209 MONTH SEPTEMBER 1985 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1.

885 17.

890 2.

885 18.

892 3.

884 19.

891 4.

883 20.

774 5

884 21.

-32 6.

884 22.

64 7;

885 23.

546 8.

885 24.

883 9.

884 25.

885 10.

883 26.

886 11 1.

883 2 7 ~.

888 12.

885 28.

887 13.

'847 29.

887 l14.

848 30.

887

- 15.

888 31.

16.

888

~

8512130055 850930 PDR ADOCK'05000395 R

PDR k.

., g. Ghd

\\

s

=

. Director,. Office of Resource knagement

' September Monthly Operating Report Page 2 October 7,1985 ATPACHMENP II OPERATING DATA REPORT DOCKEP NO. 50/395 UNIT V. C. SUMMER I IMTE 10/07/85 COMPLEIED BY G. A. Loignon TELEPHONE (803) 345-5209 OPERATING SPA'IUS

1. Reporting Period: SEPTEMBER 1985 Gross Hours in Reporting Period: 720
2. Currently Authorized Power Level (MWt):

2775 Max. Depend. Capacity (MWe-Net):

885 Design Electrical Rating (MWe-Net):

900

3. Power Level to which mstricted (If Any)(MWe-Net): N/A
4. Reasons for Restrictions-(If Any): N/A THIS 10NITI YR 'IO DATE CUMULATIVE i
5. Nunber of Hours Reactor Was Critical 690.6 5,945.7 11,499.1
6. Reactor Reserve Shutdown Hours 0

0 0

- 7.. Hours Generator on Line 679.4 5,846.5 11,212.2

8. Unit Reserve Shutdown Hours 0

0 0

9. Gross 'Ihennal Energy Generated (MWH) 1,836,663 15,550,788 28,883,374
10. Gross Electrical Energy Generated (MWH) 609,490 5,187,670 9,619,819 s
11. Net Electrical Energy Generated (MWH) 583,469 4,956,184 9,148,280
12. Reactor Service Pactor.

95.9 90.8 75.0 l

13. Reactor Availability Factor 95.9 90.8 75.0
14. Unit Service Pactor ~

94.4 89.2 73.1

15. Unit Availability Pactor 94.4 89.2 73.1
16. Unit Capacity Factor (Using MDC) 91.6-85.5 67.4
17. Unit Capacity Factor-(Using Design MWe) 90.0 84.1 66.3
18. Unit Forced Outage Rate 5.6 6.1 8.4 l
19. -Shutdowns Scheduled Over Next 6 It>nths (Type, Date, and Duration of Each):

Refueling Outage presently scheduled for October 5,1985 (60 Days).

'20.'If Shut.Down at End of Report Period, Estimated Date of Startup:

N/A j

21. Units in Test Status (Prior to Cmunerical Operation):

FORECASP ACHIEVED Initial Criticality N/A 10-22-82 Initial Electricity N/A 11-16-82 Comnercial Operation N/A 01-01-84 I

.s 1

Director, Office of Resource Management Stptember Monthly;0perating Report Page-3 October 7 ', _1985

-ATTACHMENT III UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50/395 UNIT V.

C.

SUMMER I DATE 10/07/85 COMPLETED BY G.

A.

Loignon TELEPHONE (803) 345-5209 (1)

METHOD OF (2)

TYPE SHUTTING-DOWN F: FORCED DURATION THE REACTOR OR CORRECTIVE ACTIONS /

NO.

DATE S: SCHEDULED (HOURS) REASON REDUCING POWER COMMENTS 11 850920 F.

40.6 B

'3-

11) Loss of Feedwater During Condensate Pump Test A

1 4

^s Director, Office of Resource Management September' Monthly Operating Report Page 4

- October 7, 1985 ATTACHMENT IV NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE On-September 1, 1985, the Virgil C. Summer Nuclear Station, Unit No.1 was operating at approximately 100% power.

On September 20, 1985, at'2058 hours0.0238 days <br />0.572 hours <br />0.0034 weeks <br />7.83069e-4 months <br />, the plant tripped from 1005 power due to loss'of feedwater which resulted from loss of all three condensate pumps during condensate pump speed controller testing.

On September 30, 1985, the plant was operating at full power.

I

P T

SOUTH CAROLINA ELECTRIC & GAS COMPANY P<0st o7FICE 764 CotuusiA south CAROLINA 29218 O. W. OsmoN, Jn.

V4CE PRESIDENT Nucutan OPEmanONS October 7, 1985 Director, Office of Resource Management U.S. Nuclear Regulatory Commission MNBB 7602 Washington, DC 20555 ATTN:

Mr. Learned W.

Barry

SUBJECT:

Virgil C.

Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 September Monthly Operating Report

Dear Mr. Barry:

Please find enclosed the September 1985 Monthly Operating Report for the Virgil C. Summer Nuclear Station Unit No.

1.

This submittal is made in accordance with the requirements of Technical Specification 6.9.1.10.

If there are any questions, please call us at your convenience.

Ver truly yours, O. W. Dixo r.

CJM: GAL:0WD/ led Attachment cc:

V. C. Summer K.

E. Nodland T. C. Nichols, Jr./0. W. Dixon, Jr.

R.

A. Stough E. H. Crews, Jr.

G.

Percival E. C. Roberts C. W. Hehl W. A. Williams, Jr.

J.

B. Knotts, Jr.

H. R. Denton S. D. Hogge J. Nelson Grace INPO Records Center Group Managers ANI Library D. A. Nauman L. N. Carter O. S. Bradham R. E. Rainear C. A.

Price NPCP C. L. Ligon (NSRC)

FILE