ML20138C311

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Limitorque motor-operated Butterfly Valves Not Opening Electrically After Closed Manually.Initially Reported on 850912.No Corrective Actions Will Be Taken Unless Facility Reactivated
ML20138C311
Person / Time
Site: Midland
Issue date: 10/08/1985
From: Jackie Cook, Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
CON-#485-780 32401, OL, OM, NUDOCS 8510220408
Download: ML20138C311 (4)


Text

_ _ _

h

^

h-i

@ CORSumBIS Power mm Company m, ~ u,n, - ~~nen~+,

and Construction General offices: 1946 West Pernell Mond, Jackson, MI 49201 e (517) 78&O453 October 8, 1985 85-05 #1 Mr J G Keppler, Regional Administrator US Nuclear Regulatory Commission Region III

.799 Roosevelt Road Glen Ellyn, IL 60137 MIDLAND' ENERGY CENTER PROJECT DOCKET NOS 50-329 AND 50-330 LIMITORQUE MOTOR OPERATED BUTTERFLY VALVES FILE:

0.4.9.110 SERIAL: 32401 On September 12, 1985 Consumers Power Company (CPCo) notified your staff of a reportable condition on motor operated butterfly valves which use certain Limitorque motor operators.

In.accordance with the requiremente of 10 CFR 50.55(e) CPCo is making this interim report.

Description of Concern CPCo received a copy of Bechtel De.ficiency Evaluation Report (DER) 84-54 which documents a reportable condition encountered at the Palo Verde Nuclear Generation Station. The report identifies a Limitorque Model H2BC-SMB-00-10 motor operator installed on butterfly valves, as incapable of opening the valve electrically after it has been closed manually. A preliminary investi-gation did not identify any Midland Energy Center valves with the combination limitorque operator described 'above.

However, it is not known at this time if other combination operators installed at the Midland Energy Center have this problem.

Safety Impact-The safety impact of this condition is indeterminate.

Root Cause No root cause has been determined for this condition.

8510220408 851000

~

PDR ADOCK 05000329 S

PDR 0GT 15485-OC0985-0183-QL01

.\\o3D1

m e-2 Serial 85-05 #1 Corrective Action Corrective actions.will-not be pursued and no further reports on this subject will be made unless the Midland Energy Center is reactivated. This item will be entered in our Correspondence and Commitment Management system for long-term tracking.

JWC/MCB/emd CC: NRC, Director of Office of Inspection and Enforcement Washington, DC DSHood, NRC Office of NRR.

Bethesda, MD Document Control Desk, NRC Washington, DC INFO Records Center OC0985-0183-QL01

_~

-w 3

Serial ~

85-05 #1 OM/0L SERVICE LIST-If Mr Frank J Kelley Atomic Safety & Licensing Attorney General of the.

Appeal Board l

State of Michigan-U S Nuclear Regulatory Commission Ms Carole Steinberg Washington, DC 20555 Assistant Attorney General Environmental Protection Division Mr C R Stephens (3) 720 Law Building Chief Docketing & Services i

Lansing, MI 48913 U S Nuclear Regulatory Commission Office of the Secretary Washington, DC 20555 l

Mr Myron M Cherry, Esq l

Suite 3700

-Ms Mary Sinclair Three First National Plaza 5711 Summerset Street Chicago, IL 60602 Midland, M1 48640 r

Mr Wendell H Marshall Mr William D Paton, Esq RFD 10 Counsel for the NRC Staff r

Midland, MI 48640 U S Nuclear Regulatory Commission

[

Washington, DC 20555 l

Mr Charles Bechhoefer, Esq Atomic Safety & Licensing Atomic Safety & Licensing Board Panel Board' Panel

'U S Nuclear Regulatory Commission U S Nuclear Regulatory Commission East-West Towers, Room E-413 Washington, DC 20555 Bethesda, MD 20014 Ms Barbara Stamaris Dr Frederick P Cowan 5795 North River Road 6152 N Verde-Trail Rt 3 Apr B-125

'Freeland, MI 48623 Boca Raton, FL 33433 Dr Jerry Harbour Mr Fred C Williams.

Atomic Safety & Licensing Isham, Lincoln & Beale Board Panel 1120 Connecticut Ave, NW, Suite 840 U S Nuclear Regulatory Commission f

Washington, DC 20036 East-West Towers, Room E-454 Bethesda, MD 20014

'Mr James E Brunner, Esq Consumers Power Company Mr M I Miller, Esq 212 West Michigan Avenue Isham, Lincoln & Beale Jackson, MI 49201 Three First-National Plaza 52nd Floor-Chicago,=IL 60602 t

I 0C0985-0183-QL01-L-

s 4

Serial 85-05 #1 Mr Steve Gadler, Esq Mr John Demeester, Esq 2120 Carter Avenue Dow Chemical Building St Paul, MN 55108 Michigan Division Midland MI 48640 Mr P Robert Brown Clark, Klein & Beaumont Ms Lynne Bernabei 1600 First Federal Bldg Government Accounta'aility Project Woodward Ave 1901 Q Street, NW Detroit, MI 48226 Washington, DC 2000')

a f

5 t

e OC0985-0183-QL01

.