ML20138A467

From kanterella
Jump to navigation Jump to search
Documents Schedule for Completing Actions Re IE Info Notice 86-03, Potential Deficiencies in Environ Qualification of Limitorque Motor Valve Operator Wiring. Limitorque Operators Will Be Inspected
ML20138A467
Person / Time
Site: Prairie Island  
Issue date: 02/11/1986
From: Larson C
NORTHERN STATES POWER CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
IEIN-86-003, IEIN-86-3, NUDOCS 8603140262
Download: ML20138A467 (1)


Text

<dlllP' l

l Nodhom States Power Company c4 Nicollet Mall u-nooks. Minnesota 55401 rmmy RC'JT19 ie,eprene (612) 330 5500 pg February ll, 1986 A

3-

{ '. U }C 1 ai r

f,r Mr J G Keppler ML_'~I Regional Administrator - Region III FILE

_3 US Nuclear Regulatory Commission 799 Doosevelt Road Glen Ellyn, Illinois 60137 PRAIRIE ISLAND NUCLEAR GENERATING PLANT DOCKET NOS. 50-282 LICENSE NOS. DPR-42 50-306 DPR-60 Information Related to IE Information Notice 86-03 Review On February 6 and 7, 198G Mr A S Gautam and Mr R J Smeenge, NRC Region III, visited the Prairie Island plant to audit.he status l

of our investigation into the problem discussed in IE laformation Notice 86-03, " Potential Deficiencies in Environmental Qualifica-l tion of Limitorque Motor Valve Operator Wiring."

The purpose of this letter is to document our schedule for completing actions related to this Information Notice.

I As discussed during the audit, we have not discovered any wire in j

Limitorque operators not having, in our view, adequate supporting environmental qualification documentation.

We will, however, inspect all Limitorque operators within the scope of 10 CFR Part 50, Section 50.49, and replace all PVC insulated internal wiring.

In Unit No.

1, this inspection and replacement will take place during the 1986 refueling outage now scheduled to begin on March 5,

1986.

In Unit No.

2, this inspection and replacement will be completed

)

during the next scheduled cold shutdown lasting ten days or more.

The latest this work will be completed will be during the 1986 refueling outage now scheduled to begin on October 22, 1986.

Please contact us if you have any questions related to our commitment to complete this work.

M C E Lars a l

Vice President Nuclear Generation c:

NRR Project Manager, NRC Resident Inspector, NHC G Charnoff 8603140262 060211 PDR ADOCK 05000282 FEB 13 id 112 b

/fD