ML20137Y774
| ML20137Y774 | |
| Person / Time | |
|---|---|
| Site: | Zion File:ZionSolutions icon.png |
| Issue date: | 11/25/1985 |
| From: | Zukor D NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD) |
| To: | Seyfrit K NRC OFFICE FOR ANALYSIS & EVALUATION OF OPERATIONAL DATA (AEOD) |
| Shared Package | |
| ML20137Y779 | List: |
| References | |
| AEOD-T514, NUDOCS 8603120378 | |
| Download: ML20137Y774 (1) | |
Text
I
^O NOV 2 51985 MEMORANDUM FOR:
Karl V.1Seyfrit, Chief Reactor Operations Analysis Branch Io 79f Office for Analysis and Evaluation i
of Operational Data FROM:
Dorothy J. Zukor, Engineer.
Reactor Systems Section 2 Reactor Operations Analysis Branch Office for Analysis and Evaluation of Operational Data
SUBJECT:
TECHNICAL REVIEW REPORT:
" POTENTIAL LOSS OF COMPONENT COOLING WATER DUE TO MALADJUSTMENT OF RELIEF VALVES" The subject Technical Review Report is enclosed for your information.
On February 16, 1985, a pressure transient in the component cooling water'(CCW) system at the Zion site caused a relief valve to lift. The valve did not reseat until approximately 1700_ gallons of CCW had spilled onto the contain-ment floor and the.CCW system was isolated. Subsequent investigation showed that the nozzle ring settings on the valve were incorrect causing the valve to lift prematurely and to fail'to reseat. The event itself had no serious safety consequences and no generic significance except as an example of a failure mode of the CCW system. AE00 has suggested that this type of event be included in the resolution of Generic Issue 23 which includes CCW system failures. No further action on this event is planned by AE00.
7 6/1 Dorothy
.Z r,
gineer Reactor Systems Section 2 Reactor Operations Analysis Branch Office for Analysis a'nd Evaluation of Operational Data
Enclosure:
As stated cc: w/ enclosure
' Jerry Jackson, NRR DISTRIBUTION:
'PDR '
ROAB SF ROAB CF DZukor
-WLanning KSeyfrit FHebdon KBlack TIppolito CHeltemes.Jr.
0 0FC :ROAB Pg u :
B:
- BC:ROAB /J :DD:AEOD NAME :DZukor:as
- )R nT.
- KVSeyfrit
- TIhpolit 8603120378 851125-DATE :11//'f/85
- 11/14/85
- 11/2985 PDR ADOCK 0 5
8
/
\\ 0FFICIAL RECORD COPY