DLS February 10, 1986 EN 86-06 0FFICE OF INSPECTION AND ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee: Nebraska Public Power District (CooperNuclearStation)

Docket No. 50-298

Subject:

PROPOSED IMPOSITION-0F CIVIL PENALTY - $50,000 This is to inform the Commission that a Notice of Violation and Proposed Imposition of Civil Penalty in the amount of Fifty Thousand Dollars ($50,000) will be issued on or about February 13, 1986 to the Nebraska Public Power District.

The action involves the failure to properly implement surveillance procedures in that jumper wires used for surveillance testing were left installed after the testing was completed. This rendered the automatic start capability of both trains of the standby gas treatment system inoperable and negated the capability of automatically isolating the reactor building ventilation system if a high radiation condition had occurred. Also, surveillance inspections on drywell snubbers did not detect some that were inoperable. The inoperable snubbers were not discovered until after the unit had entered an operational mode in which they were required to be operable.

It should be noted that the licensee has not been specifically informed of the enforcement action. The Regional Administrator has been authorized by the Director, Office of Inspection and Enforcement, to sign this action. The schedule of issuance and notification is:

Mailing of Notice February 13, 1986 ~

Telephone Notification of Licensee February 13, 1986 A news release has been' prepared and will be issued about the time the licensee receives the Notice. The State of Nebraska will be' notified.

The licensee has thirty days-from the date of the Notice in which to respond.

Following NRC evaluation of the response, the civil penalty may be remitted, mitigated, or imposed by Order.

Contact:

T. C. Poindexter, IE 29635 J. Axelrad, IE 24909 Distribution:

W hs H Street WO:J -

MNBB g Phillipsin,79 EW Willste 10!35 Chairman Palladino ED0 NRR IE NMSS Comm. Roberts DED/ROGR OIA RES Comm. Asselstine PA 01 Comm. Bernthal ELD AE0D Comm. Zech RM ACRS SECY Air Rights /b:3b Regional Offices MAIL CA SP RI /0:v/ RIV d ADM: Doc. Mgt. Br.

PE RII g RV acir; PDR RIII g;gl PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL FEBRUARY 13, 1986 e"J"2 am EN-N m 5= = =2a OO6 PM

- - _. _